The text of a spec sheet · part 27 of 27
Relay and Timer Specifications, Bulletin Number 700, pages 244 to 250
Pages 244 to 250 of 250
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 244
Relay and Timer Specifications
Load Connection • For an AC load, use a power supply that is rated at 50 Hz. or 60 Hz. The maximum operating frequency is 10 Hz. • The 700-SH has a built-in varistor for surge/inrush protection of AC loads. If additional suppression is required, connect an external varistor across the load device terminals. Select a varistor, which meets the load voltage condition that is outlined in the table. Load Voltage [V AC]
Varistor Voltage [V]
100…120
240…270
200…240
440…470
380…480
820…1000
TIP
Varistor Surge Resistance
1000 A min.
For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.
Zero Cross Function
An SSR with a zero cross function operates when an AC load voltage reaches the zero point or its vicinity. This reduces clicking noises when the load is switched and minimizes the influence of an inductive load, (such as, lamp, heater, or motor) on the power supply because the inrush current of the load is reduced. This can also minimize the scale of the inrush current protection circuit.
Output (load voltage)
Input
ON OFF
At a low applied voltage (for example, 24V AC) the load current is not fully supplied. When the unit is switched ON, the voltage required to power the unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems.
Loss time
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.
Load Input
SSR
Load power supply
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
243
Page 245
Relay and Timer Specifications
700-SK Slim Line Relays • High-response speed models • Input sensor module to allow high voltage 100…240V AC or 12…24V DC sensor • Interface to low voltage (logic) device such as a PC output module for typical SSR applications • LED indicator • Input modules and output modules can be used with the 700-HN121 or 700-HN221 sockets
Input/Sensor Module Input-to-Output Isolation Method
Status Indicator
Photocoupler
Yes
Response Frequency 10 Hz 1 kHz
Logic Level Supply Voltage
Supply Current
4…32V DC
0.1…100 mA
Rated Input Sensor Voltage
Cat. No.
100…240V AC (1)
700-SKICA18
12…24V DC
700-SKICZ24
(1) 47…63 Hz
Output/SSR Module Input-to-Output Isolation Method
Zero Cross Function
Status Indicator
Yes
Phototriac
No
Photocoupler
Not Applicable
Output (Load) Max. Continuous Current and Rated Voltage Range
Rated Input Control Voltage
700-SKOZ2Z25
2 A @ 100…240V AC (1) Yes
2 A @ 5…48V DC
Cat. No.
5…24V DC
1.5 A @ 48…200V DC
700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25
(1) 47…63 Hz
Accessories - 700-SK Relays Photo
244
Description
Pcs./Pkg.
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.
10
700-HN121
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 246
Relay and Timer Specifications
Specifications - 700-SK Relays Input Sensor Module Input Sensor Ratings Cat. No.
Rated Input Voltage
Max. Operating Input Voltage Range
Input Current
Pick-up Voltage
Drop-out Voltage
12…24V DC 100…240V AC
6.6…32V DC 60…264V AC
8 mA max. 15 mA max.
6.6V DC max. 60V AC max.
3.6V DC min. 20V AC min.
700-SKICZ24 700-SKICA18
Output Logic Ratings Cat. No. 700-SKICZ24 700-SKICA18
Logic Level Supply Voltage
Logic Level Supply Current Draw
4…32V DC
0.1…100 mA
Cat. No. 700-SKICA18 20 ms max. 20 ms max. 10 Hz
Cat. No. 700-SKICZ24 0.1 ms max. 0.1 ms max. 100 kHz
Characteristics Description Pick-up time Drop-out time Response frequency Output ON voltage drop Leakage current (from SSR)
1.6V max. 5 μA max. 80 (ref. value), - - 150
Output VDRM, VCEO (V)
Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation Resistance Dielectric Strength Vibration Resistance (Max.) Shock Resistance (Max.) Ambient Temperature
80 (ref. value), - - 150
100 MΩ min. between input and output 4000V AC, 50/60 Hz for 1 min between input and output 10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)
Operating Storage
–30…+80 °C (–22…+176 °F) with no icing or condensation –30…+100 °C (–22…+212 °F) with no icing or condensation UL 508, CSA C22.2 No. 14, EN/IEC 60950 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified 45…85% (no condensation) Approx. 18 g
Standards Compliance Certifications Ambient humidity Operating Weight
Output SSR Module Control/Input Ratings Cat. No.
Rated Control Voltage
Max. Operating Control Voltage Range
Max. Reverse Control Voltage
700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25
Impedance (1)
Pick-up Voltage
Drop-out Voltage
4V DC max.
1V DC min.
15 mA max. at 25 °C (77 °F) 5…24V DC
4…32V DC
-32V DC 8 mA max.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
245
Page 247
Relay and Timer Specifications
Load/Output Ratings Cat. No.
Max. Inrush Current (3)
Rated Load Voltage
Maximum Load Voltage Range
100…240V AC
75…264V AC
0.05
2
30 A (@50/60 Hz, One cycle)
5…48V DC 48…200V DC
4…60V DC 40…200V DC
0.1 0.1
2 1.5
8 A (10 ms) 8 A (10 ms)
Cat. No. 700-SKOC2Z25
Cat. No. 700-SKOC1Z25
700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25
Continuous Load Current (Resistive) [A] Min. Max. (2)
(1) With a constant current input system. SSR impedance varies with a change in input voltage. (2) See "Load Current vs. Ambient Temperature Characteristics" graphs on page 126 for additional details. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See the “Inrush Current Resistivity” graphs on page 126 for more details.
Characteristics Description
Cat. No. 700-SKOZ2Z25
Load Switching Method/Device
Cat. No. 700-SKON2Z25 Triac
Transistor (1)
Pick-up Time
1/2 cycle of load power source cycle time + 1 ms max.
1 ms max.
Drop-out Time
1/2 of load power source cycle time (1) + 1 ms max.
2 ms max.
20 Hz
100 kHz
Response Frequency Output ON Voltage Drop
1.6V max.
Leakage Current (from SSR)
2.5V max.
1.5 mA max.
1 mA max.
Output VDRM, VCEO (V)
600 (ref.value)
600 (ref.value)
80 (ref.value)
400 (ref.value)
Output di/dt (A/uS)
30
30, - Output dv/dt (V/uS)
300
300, - Output I 2t (A2S)
10.4
10.4, - Output Tj (°C) Max.
125
125
150
150
Insulation Resistance
100 MΩ min. between input and output
Dielectric Strength
4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.)
10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.)
1000 m/s2 (100 G)
Ambient Temperature
Operating
–30…+80 °C (–22…+176 °F) with no icing or condensation
Storage
–30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient Humidity Operating
45…85% (no condensation)
Weight
Approx. 18 g
(1) 60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms.
Load Current vs. Ambient Temperature Characteristics
Ambient Temperature [° C]
246
80
Ambient Temperature [° C]
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
100
40
0
0.5
60
100
80
40
60
0
20
0.5
1
20
1
2 1.5
-20
Maximum Load Current (A)
2 1.5
-20
Maximum Load Current (A)
For 2 A Versions
Page 248
Relay and Timer Specifications
Inrush Current Resistivity (2) 700-SKOC2
700-SKOZ/SKOC1
8
3 2
5 4 3
2
10
2000
100
30 50
Energizing Time (ms)
1000
0
300 500
1
0
10
1
2000
4
6
1000
5
7
300 500
Inrush Current (A)
9
8 6
5000
500
1000
100
200
30 50
10
9 7
Inrush Current (A)
20
10
Inrush Current (A)
30
10
100
10
30 50
700-SKOZ/SKON
Energizing Time (ms)
Energizing Time (ms)
(2) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
Dimensions - 700-SK Relays All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes.
IMPORTANT
The input module (700-SKI) and output module (700-SKO) are compatible with the Cat. No. 700-HN121 socket.
1 5.2
Terminal Arrangement/ Internal Connections (Bottom View)
3 0.5 29 max.
1
28 max.
5
(–)
17.4
4.75
13 max.
(+)
4 9.6
7.5
10
4
Load
5
4.7
Input
0.5 4.75
4
3
1
5
(–)
(+)
2 20
Application Considerations of the700-SK Relay Connection For DC load switching, 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life) Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load.
TIP
For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
247
Page 249
Relay and Timer Specifications
Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource
Description
General Purpose, Interposing, Solid-State and Specialty Relays Brochure publication 700-BR018
Provides product overview and applications for Bul 700 relay line.
Solid-state Relay Application Guide, publication 700-AT001
Provides methods for applying and troubleshooting Solid-state relays.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/global/literature-library/ overview.page.
248
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 250
Rockwell Automation Support Use the following resources to access support information.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
www.rockwellautomation.com/knowledgebase
Local Technical Support Phone Numbers
Locate the phone number for your country.
www.rockwellautomation.com/global/support/get-supportnow.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
www.rockwellautomation.com/global/support/directdial.page
Literature Library
Installation Instructions, Manuals, Brochures, and Technical Data.
www.rockwellautomation.com/literature
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
www.rockwellautomation.com/global/support/pcdc.page
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 700-TD552C-EN-P - October 2018 Supersedes Publication 700-TD552B-EN-P - August 2018
Copyright © 2018 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.