Relay and Timer Specifications

Load Connection • For an AC load, use a power supply that is rated at 50 Hz. or 60 Hz. The maximum operating frequency is 10 Hz. • The 700-SH has a built-in varistor for surge/inrush protection of AC loads. If additional suppression is required, connect an external varistor across the load device terminals. Select a varistor, which meets the load voltage condition that is outlined in the table. Load Voltage [V AC]

Varistor Voltage [V]

100…120

240…270

200…240

440…470

380…480

820…1000

TIP

Varistor Surge Resistance

1000 A min.

For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

Zero Cross Function

An SSR with a zero cross function operates when an AC load voltage reaches the zero point or its vicinity. This reduces clicking noises when the load is switched and minimizes the influence of an inductive load, (such as, lamp, heater, or motor) on the power supply because the inrush current of the load is reduced. This can also minimize the scale of the inrush current protection circuit.

Output (load voltage)

Input

ON OFF

At a low applied voltage (for example, 24V AC) the load current is not fully supplied. When the unit is switched ON, the voltage required to power the unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems.

Loss time

For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.

Load Input

SSR

Load power supply

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

243

Page 245

Relay and Timer Specifications

700-SK Slim Line Relays • High-response speed models • Input sensor module to allow high voltage 100…240V AC or 12…24V DC sensor • Interface to low voltage (logic) device such as a PC output module for typical SSR applications • LED indicator • Input modules and output modules can be used with the 700-HN121 or 700-HN221 sockets

Input/Sensor Module Input-to-Output Isolation Method

Status Indicator

Photocoupler

Yes

Response Frequency 10 Hz 1 kHz

Logic Level Supply Voltage

Supply Current

4…32V DC

0.1…100 mA

Rated Input Sensor Voltage

Cat. No.

100…240V AC (1)

700-SKICA18

12…24V DC

700-SKICZ24

(1) 47…63 Hz

Output/SSR Module Input-to-Output Isolation Method

Zero Cross Function

Status Indicator

Yes

Phototriac

No

Photocoupler

Not Applicable

Output (Load) Max. Continuous Current and Rated Voltage Range

Rated Input Control Voltage

700-SKOZ2Z25

2 A @ 100…240V AC (1) Yes

2 A @ 5…48V DC

Cat. No.

5…24V DC

1.5 A @ 48…200V DC

700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

(1) 47…63 Hz

Accessories - 700-SK Relays Photo

244

Description

Pcs./Pkg.

Cat. No.

Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.

10

700-HN121

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 246

Relay and Timer Specifications

Specifications - 700-SK Relays Input Sensor Module Input Sensor Ratings Cat. No.

Rated Input Voltage

Max. Operating Input Voltage Range

Input Current

Pick-up Voltage

Drop-out Voltage

12…24V DC 100…240V AC

6.6…32V DC 60…264V AC

8 mA max. 15 mA max.

6.6V DC max. 60V AC max.

3.6V DC min. 20V AC min.

700-SKICZ24 700-SKICA18

Output Logic Ratings Cat. No. 700-SKICZ24 700-SKICA18

Logic Level Supply Voltage

Logic Level Supply Current Draw

4…32V DC

0.1…100 mA

Cat. No. 700-SKICA18 20 ms max. 20 ms max. 10 Hz

Cat. No. 700-SKICZ24 0.1 ms max. 0.1 ms max. 100 kHz

Characteristics Description Pick-up time Drop-out time Response frequency Output ON voltage drop Leakage current (from SSR)

1.6V max. 5 μA max. 80 (ref. value), - - 150

Output VDRM, VCEO (V)

Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation Resistance Dielectric Strength Vibration Resistance (Max.) Shock Resistance (Max.) Ambient Temperature

80 (ref. value), - - 150

100 MΩ min. between input and output 4000V AC, 50/60 Hz for 1 min between input and output 10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)

Operating Storage

–30…+80 °C (–22…+176 °F) with no icing or condensation –30…+100 °C (–22…+212 °F) with no icing or condensation UL 508, CSA C22.2 No. 14, EN/IEC 60950 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified 45…85% (no condensation) Approx. 18 g

Standards Compliance Certifications Ambient humidity Operating Weight

Output SSR Module Control/Input Ratings Cat. No.

Rated Control Voltage

Max. Operating Control Voltage Range

Max. Reverse Control Voltage

700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

Impedance (1)

Pick-up Voltage

Drop-out Voltage

4V DC max.

1V DC min.

15 mA max. at 25 °C (77 °F) 5…24V DC

4…32V DC

-32V DC 8 mA max.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

245

Page 247

Relay and Timer Specifications

Load/Output Ratings Cat. No.

Max. Inrush Current (3)

Rated Load Voltage

Maximum Load Voltage Range

100…240V AC

75…264V AC

0.05

2

30 A (@50/60 Hz, One cycle)

5…48V DC 48…200V DC

4…60V DC 40…200V DC

0.1 0.1

2 1.5

8 A (10 ms) 8 A (10 ms)

Cat. No. 700-SKOC2Z25

Cat. No. 700-SKOC1Z25

700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25

Continuous Load Current (Resistive) [A] Min. Max. (2)

(1) With a constant current input system. SSR impedance varies with a change in input voltage. (2) See "Load Current vs. Ambient Temperature Characteristics" graphs on page 126 for additional details. (3) If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See the “Inrush Current Resistivity” graphs on page 126 for more details.

Characteristics Description

Cat. No. 700-SKOZ2Z25

Load Switching Method/Device

Cat. No. 700-SKON2Z25 Triac

Transistor (1)

Pick-up Time

1/2 cycle of load power source cycle time + 1 ms max.

1 ms max.

Drop-out Time

1/2 of load power source cycle time (1) + 1 ms max.

2 ms max.

20 Hz

100 kHz

Response Frequency Output ON Voltage Drop

1.6V max.

Leakage Current (from SSR)

2.5V max.

1.5 mA max.

1 mA max.

Output VDRM, VCEO (V)

600 (ref.value)

600 (ref.value)

80 (ref.value)

400 (ref.value)

Output di/dt (A/uS)

30

30, - Output dv/dt (V/uS)

300

300, - Output I 2t (A2S)

10.4

10.4, - Output Tj (°C) Max.

125

125

150

150

Insulation Resistance

100 MΩ min. between input and output

Dielectric Strength

4000V AC, 50/60 Hz for 1 min between input and output

Vibration Resistance (Max.)

10…55 Hz, 1.5 mm double amplitude (10 G)

Shock Resistance (Max.)

1000 m/s2 (100 G)

Ambient Temperature

Operating

–30…+80 °C (–22…+176 °F) with no icing or condensation

Storage

–30…+100 °C (–22…+212 °F) with no icing or condensation

Standards Compliance

UL 508, CSA C22.2 No. 14, EN/IEC 60950

Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified

Ambient Humidity Operating

45…85% (no condensation)

Weight

Approx. 18 g

(1) 60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms.

Load Current vs. Ambient Temperature Characteristics

Ambient Temperature [° C]

246

80

Ambient Temperature [° C]

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

100

40

0

0.5

60

100

80

40

60

0

20

0.5

1

20

1

2 1.5

-20

Maximum Load Current (A)

2 1.5

-20

Maximum Load Current (A)

For 2 A Versions

Page 248

Relay and Timer Specifications

Inrush Current Resistivity (2) 700-SKOC2

700-SKOZ/SKOC1

8

3 2

5 4 3

2

10

2000

100

30 50

Energizing Time (ms)

1000

0

300 500

1

0

10

1

2000

4

6

1000

5

7

300 500

Inrush Current (A)

9

8 6

5000

500

1000

100

200

30 50

10

9 7

Inrush Current (A)

20

10

Inrush Current (A)

30

10

100

10

30 50

700-SKOZ/SKON

Energizing Time (ms)

Energizing Time (ms)

(2) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

Dimensions - 700-SK Relays All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes.

IMPORTANT

The input module (700-SKI) and output module (700-SKO) are compatible with the Cat. No. 700-HN121 socket.

1 5.2

Terminal Arrangement/ Internal Connections (Bottom View)

3 0.5 29 max.

1

28 max.

5

(–)

17.4

4.75

13 max.

(+)

4 9.6

7.5

10

4

Load

5

4.7

Input

0.5 4.75

4

3

1

5

(–)

(+)

2 20

Application Considerations of the700-SK Relay Connection For DC load switching, 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.

Protective Element (to extend SSR life) Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load.

TIP

For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

247

Page 249

Relay and Timer Specifications

Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource

Description

General Purpose, Interposing, Solid-State and Specialty Relays Brochure publication 700-BR018

Provides product overview and applications for Bul 700 relay line.

Solid-state Relay Application Guide, publication 700-AT001

Provides methods for applying and troubleshooting Solid-state relays.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, rok.auto/certifications.

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/global/literature-library/ overview.page.

248

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 250

Rockwell Automation Support Use the following resources to access support information.

Technical Support Center

Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.

www.rockwellautomation.com/knowledgebase

Local Technical Support Phone Numbers

Locate the phone number for your country.

www.rockwellautomation.com/global/support/get-supportnow.page

Direct Dial Codes

Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.

www.rockwellautomation.com/global/support/directdial.page

Literature Library

Installation Instructions, Manuals, Brochures, and Technical Data.

www.rockwellautomation.com/literature

Product Compatibility and Download Center (PCDC)

Get help determining how products interact, check features and capabilities, and find associated firmware.

www.rockwellautomation.com/global/support/pcdc.page

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication 700-TD552C-EN-P - October 2018 Supersedes Publication 700-TD552B-EN-P - August 2018

Copyright © 2018 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.