The text of a spec sheet · part 13 of 27

Relay and Timer Specifications, Bulletin Number 700: General Purpose Electronic Timers and Counters, pages 119 to 128

Pages 119 to 128 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 119

Relay and Timer Specifications

Photo

Description

Pkg. Qty. Cat. No.

Specialty Socket 8-pin backwired socket with solder terminals for use with 700-HR timing relays. Order 10 or multiples of 10.

10

700-HN108

Specialty Socket 11-pin back-wired socket with solder terminals for use with 700-HR timing relays.

10

700-HN129

Frame Adapter For flush or door mounting of all 700-HR and -HX timers.

1

700-HN130

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with all 700-HR Timing Relays Secures timer in socket.

10

700-HN131

Protective Cover Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HRs and -HX timing relays.

1

700-HN132

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Note: Not required for installation

Timer Type

Socket Cat. No.

700-HR52, -HRT6, -HRV, -HRQR

(1)

(2)

700-HRS, -HRT4, -HRP, -HRC, -HRM, -HRF, -HRY, -HRQN

Retainer Clip Cat. No.

700-HN101

700-HN131

700-HN126

Not Required (3)

700-HN129

Not Applicable

700-HN100

700-HN131(See note above)

700-HN108

Not Applicable

700-HN125

Not Required(3)

(1) 11 pins. (2) 8 + pins. (3) Design of these sockets holds the timing relays securely and does not require retainer clips.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

119

Page 120

Relay and Timer Specifications

Specifications - 700-HR Relays 700-HR, 700-HRS, 700-HRV

700-HRP

700-HRC

700-HRM

700-HRF

700-HRY

700-HRQ

700-HRT (Transistor Outputs)

Electrical Ratings Pilot Duty Rating

NEMA B300, Thermal Current (Ith)

5A

100 mA @ 30V DC max.

120V AC

30 A, 240V AC

15 A, 120V AC

3A, 240V AC

1.5 A, Make Break Hp at 120V

1/6 Hp (0.12 kW)

1/4 Hp (0.18 kW)

1/6 Hp (0.12 kW)

Hp at 240V

1/4 Hp (0.18 kW)

1/6 Hp (0.12 kW), 1/3 Hp (0.25 kW), Resistive Load

5 A at 250V AC/30V DC

Inductive Load

AC-15 @ 250V AC, 3 A/DC-13 @ 30V DC, 0.5 A

Accuracy of Operating Time

±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)

Setting Error

±5 % FS ±50 ms (The value is ±5% FS +100 ms to -0 ms max. when the C or D mode signal of the 700-HRVs are OFF.)

Influence of Voltage

±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)

Influence of Temperature

±1% FS max. (±1% ±10 ms max. in a range of 1.2 s)

Permissible Leakage Current Power Consumption

-HR52,-HRS

-HRV

-HRP, -HRC

-HRM

-HRF

-HRY

-HRQ

-HRT

240V AC, Output ON

2.1 VA

2.5 VA

2.0 VA

2.1 VA

10 VA

12 VA

0.4 VA, 240V AC, Output OFF

1.3 VA

1.8 VA

2.0 VA

1.3 VA

10 VA

12 VA

0.4 VA, 24V DC, Output ON

0.8 W

0.9 W

0.9 W

0.8 W

1.0 W, 0.2 W

0.3 W

24V DC, Output OFF

0.2 W

0.3 W

0.9 W

0.2 W

1.0 W, 0.2 W

0.2 W

Design Specifications

Dielectric Strength

2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (contact to frame) 2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2000V AC, 50/60 Hz for 1 min (pole-to-pole) 1000V AC, 50/60 Hz for 1 min (between contacts not located next to each other) 2000V AC, 50/60 Hz for 1 min (contact to coil)

Mechanical Vibration Resistance

Malfunction: 10…55 Hz with 0.5 mm double amplitude each in three directions for ten minutes each

Shock Resistance

Malfunction: 100 m/s2 (10 G)

98 m/s2 (10 G)

294 m/s2 (10 G)

98 m/s2 (10 G)

100 m/s2 (10 G)

±1kV for 48V DC

±1.5 kV for ±600V DC

Environmental Noise Immunity Static Immunity

±1.5 kV for ±600V DC

±400V for 12V DC Malfunction: 8 kV

Ambient Temperature

Operating: -10…55 °C (with no icing) Storage: -25…65 °C (with no icing)

Ambient Humidity

Operating: 35…85 %

Construction Life Rxpectancy (Min. Operations)

120

Mechanical:20 000 000. (under no load at 1800 operations/h) Electrical: 100 000 (5 A at 250V AC, resistive load at 1800 operations/h)

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Mech: 107 Electrical: 104

Page 121

Relay and Timer Specifications

700-HR, 700-HRS, 700-HRV

EMC

Degree of Protection Weight

700-HRP

700-HRC

700-HRM

700-HRF

700-HRY

700-HRQ

700-HRT (Transistor Outputs)

(EMI) EN50081-2 Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN50082-2 Immunity ESD:EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: ENV50140:10 V/m (80 MHz…1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: ENV50204:10 V/m (900 ±5 MHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10V (0.15…80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3) Immunity Surge: EN61000-4-52 kV I/O signal-line (level 4) 1 kV line to line; 2 kV line to ground (level 3) IP40 (panel surface) Approx. 90 g

Certifications

CSA Certified (File No. 70751), UL Recognized (File No. E14843 Guide No. NRNT2), CE Marked, C-Tick Marked

Standards

UL 508, CSA C22.2 No. 14, EN 61812-1, EN 61000-6-2, -6-4

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

121

Page 122

Relay and Timer Specifications

Timer Functions - 700-HR Relays 700-HR Multifunction Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window Operating mode selector Select a mode from: A, B, B2, C, D, E, J, and G (700-HR52, -HRV, and HRT 6) A, E, B2, J, and B (800-HRS, -HRP, and -HRT4)

Output indicator (orange) (Lit when energized)

Scale range display windows

Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)

Time unit display window

Time setting knob (set time)

Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)

700-HRC -HRM On-Delay Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating)

Output indicator (orange) (Lit when energized)

Scale range display windows Time unit display window Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)

Time setting knob (set time)

Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)

700-HRF Twin Timer OFF indicator (green) Lit when the output is OFF. OFF-time unit display ON indicator (orange) Lit when the output is ON.

OFF-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h) ON-time setting knob (with orange pointer) For ON-time setting

Scale range display windows

OFF-time setting knob (with green pointer) For OFF-time setting Time range selector (select one from 1.2, 3, 12, and 30 at full scale.)

ON-time unit display ON-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h)

700-HRY Star-Delta Timer Star operation indicator (green) Delta operation indicator (orange)

Time unit display (sec. is fixed)

Scale range display windows Time setting knob (for setting star operation time) Star-delta transfer time selector (select one from 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s and 1.0 s)

Star operation time range selector (select one from 6, 12, 60 and 120 at full scale.)

Star-delta transfer time unit display

700-HRQ True Off-Delay Timer Scale range display windows

Output indicator (red) Time setting knob (for setting OFF-delay time)

Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale.) True OFF-Delay time unit display

122

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 123

Relay and Timer Specifications

Specifications for Start, Gate, Reset Signal (Cat. Nos. 700-HR52, -HRT6, -HRV, -HRQR) Start, Reset, and Gate signals are typically contact closures or signals from a solid-state sensor. (R) Reset Signal

The reset signal is not required for normal operation. Reset can be accomplished by removing power from the timing relay. To reset the timer without removing power, a signal must be applied which resets the timing cycle and returns the output contacts to their shelf state. The reset signal will override both the start signal and gate signal. The reset signal can be either momentary or maintained.

Power to Timing Relay t 1< T t1

T t1 t2

Reset Signal Timing Cycle Timing Relay Output

(G) Gate Signal

The gate signal is not required for normal operation. The gate signal provides a pause or retentive timing function. When the gate signal is applied the timing cycle is momentarily interrupted. When the signal is removed, the timing cycle resumes timing at the point the cycle was interrupted and will continue timing until the time delay is completed or the gate signal is re-applied.

Power to Timing Relay t1+t2 = T

Gate (pause) Timing Cycle Timing Relay Output

Contact Signal, Cat. Nos. 700-HR52, -HRT6, -HRQR

Contact closure provides signal to timer. A low energy signal is generated by the 700-HR timing relay. For optimum reliability, use contacts designed for low energy switching (5V, 1 mA) (Bul. 800F-X V, 800T-X V). No external voltage should be connected to the contact signal.

R S G

5v, 1mA

Contact Signal, Cat. No. 700-HRV

For use in applications where it is not possible to use contacts designed for low energy switching. Contact closure provides signal to timer. A signal is generated by the 700-HR timing relay, and is the same potential as the supply voltage of the timing relay. No external voltage should be connected to contact signal. 700HRV52TU24 supply voltage: 24...48V AC, 12...48V DC / 700-HRV52TA17 supply voltage: 100...240V AC, 100...125V DC.

S

U

U

( )

(+)

+ 12...24V DC COM

Solid-State Signal, Cat. Nos. 700-HR52, -HRT6 0.1mA

Timing relay is suitable for use with a 3-wire NPN 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.

R S G

COM ( )

(+) 12...24V DC

+ 12...24 V DC COM

+ 12...24V DC COM

Solid-State Signal, Cat. No. 700-HRV

Timing relay is suitable for use with a 3-wire NPN or PNP 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.

S

S

COM ( ) (+) 12...24V DC

PNP Wiring Diagram

NPN Wiring Diagram

COM ( ) (+) 12...24V DC

Signal Specifications Circuit Impedance

Circuit impedance can be used to calculate the maximum wiring distance from the signal switch to the timing relay, for example. Permissiblesignal-ONimpedance:1 kΩ max. Permissible signal-OFF impedance: 100 kΩ min.

Power-OFF Reset

Min. power-off time: 0.1 s, Reset Voltage: 10% max. of rated voltage

Signal Duration

Min. pulse width: 0.05 s 700-HR52

Signal Options

700-HRT6

700-HRV5

700-HRQR

Start

X

X

X

NA

Reset

X

X

NA

X

Gate

X

X

NA

NA

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

123

Page 124

Relay and Timer Specifications

Timing Charts - 700-HR Relays Mode A, ON-Delay a. Needs continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state after timing is complete. d. Additional start signals during timing don't reset timing or contacts. e. When the input power is removed contacts return to shelf state.

Basic Operation T

Power

T

Power

Start

Start

Output (N.C.)

Output

Output (N.O.) Power LED

Mode B, Repeat Cycle, Off Start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts remain in their shelf state. When that time period is complete contacts change state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.

Basic Operation T

T

T

T

T

T

Power Start Output (N.C.) Output (N.O.) Power LED

Power Start Output

Mode B2, Repeat Cycle On start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts change state. When that time period is complete contacts return to the shelf state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state. Basic Operation T

T

Power Start Output (N.C.)

T

Power Start

T

T

T

Output

Output (N.O.) Power LED

Mode C, Watchdog monitor (Trigger = Signal On/Off)

a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied or when start signal is removed (only if timing cycle was complete). c. Timing is initiated at the leading edge of the start signal. After the first timing cycle is complete, timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state. Power

124

T

T t

T t<T

Basic Operation

Start Output (N.C.)

Power Start

Output (N.O.) Power LED

Output

T

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

T

Page 125

Relay and Timer Specifications

Mode D, Off-Delay (Trigger = Signal Off)

a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied. c. Timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.

Basic Operation t

T

Power t<T

Start

Power Start

Output (N.C.)

Output

T

Output (N.O.) Power LED

Mode E, One-Shot (Trigger = Signal On) 700-HR52, -HRV, and -HRT6 a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state immediately when start signal is applied. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to shelf state.

Basic Operation t

T

Power

T t<T

T

Power Start

Start Output (N.C.) Output (N.O.) Power LED

Output

Mode E, One-Shot (Trigger = Power On) 700-HRS, -HRP, and -HRT4 a. Need continuous input power applied. b. Timing is initiated when the input power is applied. c. At the end of the time period contacts return to the shelf state. d. Relay timing is reset when input power is removed.

Basic Operation Power Timed Output (N.C.) Timed Output (N.O.) Power LED

T t<T Power

T

Output

Mode G, Watchdog Monitor (Trigger=Signal ON/OFF) a. Need continuous input power applied. b. Timing is initiated by the landing edge of the start signal. c. After the first timing cycle is complete the contacts change state and timing is initiated by the trailing edge of the start signal. d. At the end of the time period the contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. f. When the power is removed contacts return to the shelf state.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

125

Page 126

Relay and Timer Specifications

Mode J, Delayed One-Shot (Trigger = Power On)

a. Need continuous input power applied. b. No start signal applied. c. Timing is initiated when input power is applied. c. Contacts change state after the timing for a fixed time of 1s +/-0.5s d. At the end of the 1 sec period the contacts return to the shelf state. e. When the input power is removed contacts return to the shelf state. Basic Operation T

Power

T

1s ±0.5s

Output (N.C.)

Power

Output (N.O.)

Output (N.O.)

Power LED

Power LED

1s ±0.5s

Mode Star-Delta a. Need continuous input power applied. b. No start signal required. Timing is initiated when input power is applied. c. Star ouput contact changes state when input power is applied. d. After timing is complete star output contact returns to the shelf state then both the star & delta contacts remain in shelf states until transfer time setting is complete. e. Delta output contact changes state after transfer time is complete. f. Instantaneous contact changes state when input power is applied. g. All contacts return to the shelf state when input power is removed. Power

Basic Operation t2 t1

Output (N.C.)

Power

Output (N.O.)

Instantaneous Output

Output 8-5,

LED

Output 8-5,

LED

Output 8-6,

LED

Output 8-6,

LED t1 t2

Mode True Off-Delay (Trigger = Power Off)

a. Continuous input power is NOT required. b. No start signal applied. c. Contacts change state immediately when input power is applied. d. Timing starts when input power is removed. e. At the end of the time period contacts return to the shelf state. f. Relay timing is reset when input power is reapplied while the relay is timing. Contacts remain in energized state. t<T T t

T

Basic Operation

Power

T

126

Output (N.C.)

Power

Output (N.O.)

Output

Relay On LED

Relay On LED

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 127

Relay and Timer Specifications

Dimensions - 700-HR Relays

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

127

Page 128

Relay and Timer Specifications

700-HT Plug-in Timing Relay • Timing Relay (On-Delay or Off-Delay) • Rugged Pin Style Socket Mounting • 10 A, DPDT Contact Ratings • 0.1 s…30 min Fixed Timing Relay • 0.1 s…3 min Single Adjustable Timing Relay • Single or Fixed Timing

Single Range Timing Relay with Pin Style Terminations 700

– a

HT

2

2

A

A2 b c d e f

Catalog Number Explanation - 700-HT Relays a Bulletin Number

700

- b Type of Relay

HT Tube Base Adjustable Timing Relay c Operating Mode

1–On-delay 2–Off-delay

Operating Mode d Number of Poles e Timing Range f Coil Voltage

2 - 2PDT

A– 0.1…10 s B– 1.0…100 s C– 0.1…10 min D– 1.0…100 min E – 0.1…10 hr

U12– 12V DC U24– 24V AC/DC, 50/60 Hz U120– 120V AC/DC, 50/60 Hz A2 – 240V AC, 50/60 Hz

Wiring Diagrams U.S./Canada

International

700-HN125 or 700-HN100

700-HN100

700-HN126 or 700-HN101

700-HN101

On-Delay

Socket

Off-Delay

700-HT DPDT 2-Pole, 2 Form C Contacts

128

Socket

Rockwell Automation Publication 700-TD552C-EN-P - October 2018