For the Allen-Bradley 700S-CFB620EJC
Page 119
Relay and Timer Specifications
Photo
Description
Pkg. Qty. Cat. No.
Specialty Socket 8-pin backwired socket with solder terminals for use with 700-HR timing relays. Order 10 or multiples of 10.
10
700-HN108
Specialty Socket 11-pin back-wired socket with solder terminals for use with 700-HR timing relays.
10
700-HN129
Frame Adapter For flush or door mounting of all 700-HR and -HX timers.
1
700-HN130
Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with all 700-HR Timing Relays Secures timer in socket.
10
700-HN131
Protective Cover Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HRs and -HX timing relays.
1
700-HN132
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Note: Not required for installation
Timer Type
Socket Cat. No.
700-HR52, -HRT6, -HRV, -HRQR
(1)
(2)
700-HRS, -HRT4, -HRP, -HRC, -HRM, -HRF, -HRY, -HRQN
Retainer Clip Cat. No.
700-HN101
700-HN131
700-HN126
Not Required (3)
700-HN129
Not Applicable
700-HN100
700-HN131(See note above)
700-HN108
Not Applicable
700-HN125
Not Required(3)
(1) 11 pins. (2) 8 + pins. (3) Design of these sockets holds the timing relays securely and does not require retainer clips.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
119
Page 120
Relay and Timer Specifications
Specifications - 700-HR Relays 700-HR, 700-HRS, 700-HRV
700-HRP
700-HRC
700-HRM
700-HRF
700-HRY
700-HRQ
700-HRT (Transistor Outputs)
Electrical Ratings Pilot Duty Rating
NEMA B300, Thermal Current (Ith)
5A
100 mA @ 30V DC max.
120V AC
30 A, 240V AC
15 A, 120V AC
3A, 240V AC
1.5 A, Make Break Hp at 120V
1/6 Hp (0.12 kW)
1/4 Hp (0.18 kW)
1/6 Hp (0.12 kW)
Hp at 240V
1/4 Hp (0.18 kW)
1/6 Hp (0.12 kW), 1/3 Hp (0.25 kW), Resistive Load
5 A at 250V AC/30V DC
Inductive Load
AC-15 @ 250V AC, 3 A/DC-13 @ 30V DC, 0.5 A
Accuracy of Operating Time
±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)
Setting Error
±5 % FS ±50 ms (The value is ±5% FS +100 ms to -0 ms max. when the C or D mode signal of the 700-HRVs are OFF.)
Influence of Voltage
±0.2% FS max. (±0.2% ±10 ms max. in a range of 1.2 s)
Influence of Temperature
±1% FS max. (±1% ±10 ms max. in a range of 1.2 s)
Permissible Leakage Current Power Consumption
-HR52,-HRS
-HRV
-HRP, -HRC
-HRM
-HRF
-HRY
-HRQ
-HRT
240V AC, Output ON
2.1 VA
2.5 VA
2.0 VA
2.1 VA
10 VA
12 VA
0.4 VA, 240V AC, Output OFF
1.3 VA
1.8 VA
2.0 VA
1.3 VA
10 VA
12 VA
0.4 VA, 24V DC, Output ON
0.8 W
0.9 W
0.9 W
0.8 W
1.0 W, 0.2 W
0.3 W
24V DC, Output OFF
0.2 W
0.3 W
0.9 W
0.2 W
1.0 W, 0.2 W
0.2 W
Design Specifications
Dielectric Strength
2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (contact to frame) 2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2000V AC, 50/60 Hz for 1 min (pole-to-pole) 1000V AC, 50/60 Hz for 1 min (between contacts not located next to each other) 2000V AC, 50/60 Hz for 1 min (contact to coil)
Mechanical Vibration Resistance
Malfunction: 10…55 Hz with 0.5 mm double amplitude each in three directions for ten minutes each
Shock Resistance
Malfunction: 100 m/s2 (10 G)
98 m/s2 (10 G)
294 m/s2 (10 G)
98 m/s2 (10 G)
100 m/s2 (10 G)
±1kV for 48V DC
±1.5 kV for ±600V DC
Environmental Noise Immunity Static Immunity
±1.5 kV for ±600V DC
±400V for 12V DC Malfunction: 8 kV
Ambient Temperature
Operating: -10…55 °C (with no icing) Storage: -25…65 °C (with no icing)
Ambient Humidity
Operating: 35…85 %
Construction Life Rxpectancy (Min. Operations)
120
Mechanical:20 000 000. (under no load at 1800 operations/h) Electrical: 100 000 (5 A at 250V AC, resistive load at 1800 operations/h)
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Mech: 107 Electrical: 104
Page 121
Relay and Timer Specifications
700-HR, 700-HRS, 700-HRV
EMC
Degree of Protection Weight
700-HRP
700-HRC
700-HRM
700-HRF
700-HRY
700-HRQ
700-HRT (Transistor Outputs)
(EMI) EN50081-2 Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN50082-2 Immunity ESD:EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: ENV50140:10 V/m (80 MHz…1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: ENV50204:10 V/m (900 ±5 MHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10V (0.15…80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3) Immunity Surge: EN61000-4-52 kV I/O signal-line (level 4) 1 kV line to line; 2 kV line to ground (level 3) IP40 (panel surface) Approx. 90 g
Certifications
CSA Certified (File No. 70751), UL Recognized (File No. E14843 Guide No. NRNT2), CE Marked, C-Tick Marked
Standards
UL 508, CSA C22.2 No. 14, EN 61812-1, EN 61000-6-2, -6-4
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
121
Page 122
Relay and Timer Specifications
Timer Functions - 700-HR Relays 700-HR Multifunction Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window Operating mode selector Select a mode from: A, B, B2, C, D, E, J, and G (700-HR52, -HRV, and HRT 6) A, E, B2, J, and B (800-HRS, -HRP, and -HRT4)
Output indicator (orange) (Lit when energized)
Scale range display windows
Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)
Time unit display window
Time setting knob (set time)
Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)
700-HRC -HRM On-Delay Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating)
Output indicator (orange) (Lit when energized)
Scale range display windows Time unit display window Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)
Time setting knob (set time)
Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)
700-HRF Twin Timer OFF indicator (green) Lit when the output is OFF. OFF-time unit display ON indicator (orange) Lit when the output is ON.
OFF-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h) ON-time setting knob (with orange pointer) For ON-time setting
Scale range display windows
OFF-time setting knob (with green pointer) For OFF-time setting Time range selector (select one from 1.2, 3, 12, and 30 at full scale.)
ON-time unit display ON-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h)
700-HRY Star-Delta Timer Star operation indicator (green) Delta operation indicator (orange)
Time unit display (sec. is fixed)
Scale range display windows Time setting knob (for setting star operation time) Star-delta transfer time selector (select one from 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s and 1.0 s)
Star operation time range selector (select one from 6, 12, 60 and 120 at full scale.)
Star-delta transfer time unit display
700-HRQ True Off-Delay Timer Scale range display windows
Output indicator (red) Time setting knob (for setting OFF-delay time)
Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale.) True OFF-Delay time unit display
122
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 123
Relay and Timer Specifications
Specifications for Start, Gate, Reset Signal (Cat. Nos. 700-HR52, -HRT6, -HRV, -HRQR) Start, Reset, and Gate signals are typically contact closures or signals from a solid-state sensor. (R) Reset Signal
The reset signal is not required for normal operation. Reset can be accomplished by removing power from the timing relay. To reset the timer without removing power, a signal must be applied which resets the timing cycle and returns the output contacts to their shelf state. The reset signal will override both the start signal and gate signal. The reset signal can be either momentary or maintained.
Power to Timing Relay t 1< T t1
T t1 t2
Reset Signal Timing Cycle Timing Relay Output
(G) Gate Signal
The gate signal is not required for normal operation. The gate signal provides a pause or retentive timing function. When the gate signal is applied the timing cycle is momentarily interrupted. When the signal is removed, the timing cycle resumes timing at the point the cycle was interrupted and will continue timing until the time delay is completed or the gate signal is re-applied.
Power to Timing Relay t1+t2 = T
Gate (pause) Timing Cycle Timing Relay Output
Contact Signal, Cat. Nos. 700-HR52, -HRT6, -HRQR
Contact closure provides signal to timer. A low energy signal is generated by the 700-HR timing relay. For optimum reliability, use contacts designed for low energy switching (5V, 1 mA) (Bul. 800F-X V, 800T-X V). No external voltage should be connected to the contact signal.
R S G
5v, 1mA
Contact Signal, Cat. No. 700-HRV
For use in applications where it is not possible to use contacts designed for low energy switching. Contact closure provides signal to timer. A signal is generated by the 700-HR timing relay, and is the same potential as the supply voltage of the timing relay. No external voltage should be connected to contact signal. 700HRV52TU24 supply voltage: 24...48V AC, 12...48V DC / 700-HRV52TA17 supply voltage: 100...240V AC, 100...125V DC.
S
U
U
( )
(+)
+ 12...24V DC COM
Solid-State Signal, Cat. Nos. 700-HR52, -HRT6 0.1mA
Timing relay is suitable for use with a 3-wire NPN 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.
R S G
COM ( )
(+) 12...24V DC
+ 12...24 V DC COM
+ 12...24V DC COM
Solid-State Signal, Cat. No. 700-HRV
Timing relay is suitable for use with a 3-wire NPN or PNP 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.
S
S
COM ( ) (+) 12...24V DC
PNP Wiring Diagram
NPN Wiring Diagram
COM ( ) (+) 12...24V DC
Signal Specifications Circuit Impedance
Circuit impedance can be used to calculate the maximum wiring distance from the signal switch to the timing relay, for example. Permissiblesignal-ONimpedance:1 kΩ max. Permissible signal-OFF impedance: 100 kΩ min.
Power-OFF Reset
Min. power-off time: 0.1 s, Reset Voltage: 10% max. of rated voltage
Signal Duration
Min. pulse width: 0.05 s 700-HR52
Signal Options
700-HRT6
700-HRV5
700-HRQR
Start
X
X
X
NA
Reset
X
X
NA
X
Gate
X
X
NA
NA
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
123
Page 124
Relay and Timer Specifications
Timing Charts - 700-HR Relays Mode A, ON-Delay a. Needs continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state after timing is complete. d. Additional start signals during timing don't reset timing or contacts. e. When the input power is removed contacts return to shelf state.
Basic Operation T
Power
T
Power
Start
Start
Output (N.C.)
Output
Output (N.O.) Power LED
Mode B, Repeat Cycle, Off Start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts remain in their shelf state. When that time period is complete contacts change state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.
Basic Operation T
T
T
T
T
T
Power Start Output (N.C.) Output (N.O.) Power LED
Power Start Output
Mode B2, Repeat Cycle On start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts change state. When that time period is complete contacts return to the shelf state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state. Basic Operation T
T
Power Start Output (N.C.)
T
Power Start
T
T
T
Output
Output (N.O.) Power LED
Mode C, Watchdog monitor (Trigger = Signal On/Off)
a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied or when start signal is removed (only if timing cycle was complete). c. Timing is initiated at the leading edge of the start signal. After the first timing cycle is complete, timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state. Power
124
T
T t
T t<T
Basic Operation
Start Output (N.C.)
Power Start
Output (N.O.) Power LED
Output
T
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
T
Page 125
Relay and Timer Specifications
Mode D, Off-Delay (Trigger = Signal Off)
a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied. c. Timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.
Basic Operation t
T
Power t<T
Start
Power Start
Output (N.C.)
Output
T
Output (N.O.) Power LED
Mode E, One-Shot (Trigger = Signal On) 700-HR52, -HRV, and -HRT6 a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state immediately when start signal is applied. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to shelf state.
Basic Operation t
T
Power
T t<T
T
Power Start
Start Output (N.C.) Output (N.O.) Power LED
Output
Mode E, One-Shot (Trigger = Power On) 700-HRS, -HRP, and -HRT4 a. Need continuous input power applied. b. Timing is initiated when the input power is applied. c. At the end of the time period contacts return to the shelf state. d. Relay timing is reset when input power is removed.
Basic Operation Power Timed Output (N.C.) Timed Output (N.O.) Power LED
T t<T Power
T
Output
Mode G, Watchdog Monitor (Trigger=Signal ON/OFF) a. Need continuous input power applied. b. Timing is initiated by the landing edge of the start signal. c. After the first timing cycle is complete the contacts change state and timing is initiated by the trailing edge of the start signal. d. At the end of the time period the contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. f. When the power is removed contacts return to the shelf state.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
125
Page 126
Relay and Timer Specifications
Mode J, Delayed One-Shot (Trigger = Power On)
a. Need continuous input power applied. b. No start signal applied. c. Timing is initiated when input power is applied. c. Contacts change state after the timing for a fixed time of 1s +/-0.5s d. At the end of the 1 sec period the contacts return to the shelf state. e. When the input power is removed contacts return to the shelf state. Basic Operation T
Power
T
1s ±0.5s
Output (N.C.)
Power
Output (N.O.)
Output (N.O.)
Power LED
Power LED
1s ±0.5s
Mode Star-Delta a. Need continuous input power applied. b. No start signal required. Timing is initiated when input power is applied. c. Star ouput contact changes state when input power is applied. d. After timing is complete star output contact returns to the shelf state then both the star & delta contacts remain in shelf states until transfer time setting is complete. e. Delta output contact changes state after transfer time is complete. f. Instantaneous contact changes state when input power is applied. g. All contacts return to the shelf state when input power is removed. Power
Basic Operation t2 t1
Output (N.C.)
Power
Output (N.O.)
Instantaneous Output
Output 8-5,
LED
Output 8-5,
LED
Output 8-6,
LED
Output 8-6,
LED t1 t2
Mode True Off-Delay (Trigger = Power Off)
a. Continuous input power is NOT required. b. No start signal applied. c. Contacts change state immediately when input power is applied. d. Timing starts when input power is removed. e. At the end of the time period contacts return to the shelf state. f. Relay timing is reset when input power is reapplied while the relay is timing. Contacts remain in energized state. t<T T t
T
Basic Operation
Power
T
126
Output (N.C.)
Power
Output (N.O.)
Output
Relay On LED
Relay On LED
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 127
Relay and Timer Specifications
Dimensions - 700-HR Relays
Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
127
Page 128
Relay and Timer Specifications
700-HT Plug-in Timing Relay • Timing Relay (On-Delay or Off-Delay) • Rugged Pin Style Socket Mounting • 10 A, DPDT Contact Ratings • 0.1 s…30 min Fixed Timing Relay • 0.1 s…3 min Single Adjustable Timing Relay • Single or Fixed Timing
Single Range Timing Relay with Pin Style Terminations 700
– a
HT
2
2
A
A2 b c d e f
Catalog Number Explanation - 700-HT Relays a Bulletin Number
700
- b Type of Relay
HT Tube Base Adjustable Timing Relay c Operating Mode
1–On-delay 2–Off-delay
Operating Mode d Number of Poles e Timing Range f Coil Voltage
2 - 2PDT
A– 0.1…10 s B– 1.0…100 s C– 0.1…10 min D– 1.0…100 min E – 0.1…10 hr
U12– 12V DC U24– 24V AC/DC, 50/60 Hz U120– 120V AC/DC, 50/60 Hz A2 – 240V AC, 50/60 Hz
Wiring Diagrams U.S./Canada
International
700-HN125 or 700-HN100
700-HN100
700-HN126 or 700-HN101
700-HN101
On-Delay
Socket
Off-Delay
700-HT DPDT 2-Pole, 2 Form C Contacts
128
Socket