Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 14 of 27

Relay and Timer Specifications, Bulletin Number 700: General Purpose Electronic Timers and Counters, pages 129 to 138

Pages 129 to 138 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 129

Relay and Timer Specifications

Fixed Timing Relays 700-HTF Fixed Timing Relays feature a plug-in tube base. Construction is the same as the 700-HT relay except that the adjustment knob has been removed to help prevent unwanted tampering. The timing and output specifications are identical to those of the 700-HT relay. Setting time will be ±5% of the time ordered.

700

– a

HTF

2

2

025

S

A2 b c d e f g

Catalog Number Explanation - 700-HTF Relays a Bulletin Number

700

- b Type of Relay

HTFTube Base Fixed Timing Relay c Operating Mode

1–On-delay 2–Off-delay d Number of Poles e Timing Range

2 - 2PDT

001…999 – The three digit code represents a numeric value with one decimal place. For example: code 001 is 0.1, code 025 is 2.5, and code 999 is 99.9 The acceptable range for each time unit is listed below: Seconds - 001…999 Minutes - 001…999 Hours - 001…100 f Timing Units g Coil Voltage

S –Seconds M –Minutes H –Hours

U12– 12V DC U24– 24V AC/DC, 50/60 Hz U120– 120V AC/DC, 50/60 Hz A2 – 240V AC, 50/60 Hz

Socket and Retainer Clip Reference Relay Type 700-HT12

700-HT22

Socket Cat. No.

Retainer Clip Cat. No.

700-HN100

700-HN110

700-HN125

Not Required(1)

700-HN101

700-HN110

700-HN126

Not Required(1)

(1) Design of these sockets holds the relays securely and does not require retainer clips.

Accessories - 700-HT Relays Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten

10

700-HN100

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.

10

700-HN125

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

129

Page 130

Relay and Timer Specifications

Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays(1)Secures relay in socket. Order must be for 10 clips or multiples of 10.

10

700-HN110

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

(1) Refer to 700-HT Timing Relay, Socket, and Retainer Clip Reference Chart.

130

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 131

Relay and Timer Specifications

Specifications - 700-HT Cat. No. 700-HT…

Cat. No. 700-HTF…

Electrical Ratings

Pilot Duty Rating

(1)

NEMA B300

Rated Thermal Current (Ith)

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Contacts

Inductive

Make

Break

HP

Make

Break

HP

120V AC

30 A

3A

1/2 N.O. 1/3 N.C

30 A

3A

1/3

240V AC

15 A

1.5 A

1/2 N.O. 1/3 N.C

15 A

1.5 A

1/2

Resistive 28V DC

10 A

10 A, 10 A

10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

AC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

DC

1.3 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection Mechanical

Degree of Protection

Open Type (Guarded Terminal Sockets)

Mechanical Life Operations

10 x 106

Switching Frequency Operations

18,000/hr

Timing

Duty Cycle

Continuous

Repeat Accuracy (constant voltage and temperature)

±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

Repeat Accuracy (variable voltage and temperature)

±10%, ±5% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

High End of Range

+5%, Low End of Range

-50%, Fixed Time Setting Accuracy Scale Tolerance

Reset Time

ON Delay

100 ms

OFF Delay

40 ms

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

131

Page 132

Relay and Timer Specifications

Cat. No. 700-HT…

Cat. No. 700-HTF…

Environmental Operating

–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)

Storage

–55…+85 °C (–67…+185 °F)

Temperature

Altitude

2000 m (6560 ft)

Construction Insulating Material

Molded High Dielectric Material

Enclosure

Impact Resistant Dust Cover

Contact Material Terminal Markings on Socket

Silver Cadmium Oxide In accordance with EN50 005 8- or 11-Pin Socket (On = 8, Off = 11) 700-HN100, -HN125 700-HN101, -HN126

Sockets

Certifications

CSA Certified, File 223833, UL Recognized, File E3125 Guide NLDX 2,UL Listed,whe used with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets, File No. E3125 Guide NLDX, CE Marked

Standards

EN 61812-1, EN 60947-1,-5-1, CSA 22.2 No. 14, UL 508

(1) See NEMA Ratings and Test Values on page 5.

Trigger Signal Cat. Nos. 700-HT Contact closure provides signal to timer. A low energy signal is generated by the 700-HT timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Timing Diagrams - 700-HT Relays

ON Delay

132

OFF Delay

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 133

Relay and Timer Specifications

700-HV Timing Relay •Repeat Cycle Timing Relay •10 A Contact Rating •DPDT •Pin Style Terminals •0.1 s…30 min. •Repeat Cycle Adjustable Timing •Two Timing Adjustments T1 ≠ T2

Repeat Cycle Timing Relays with Pin Style Terminations with 2 Adjustments (T1 ≠ T2) Wiring Diagrams

Operating Mode

U.S./Canada

International

700-HN125 or 700-HN100

700-HN100

Repeat Cycle

700-HV Repeat Cycle Timing Relay DPDT 2-Pole, 2 Form C Contacts

700

– a

Socket

HV

3

2

A

A

A2 b c d e f g

Catalog Number Explanation - 700-HV Relays a Bulletin Number

700

- b Type of Relay

HV – Tube Base Repeat Cycle Timing Relay c Operating Mode

3 –Power ON Repeat Cycle, OFF Start (Repeat Cycle, OFF/ON Delay)

d Number of Poles

2 - 2PDT e Timing Range OFF Time f Timing Range ON Time g Coil Voltage

Code OFF Time, Type HV A – 0.1…10 s B – 1.0…100 s C – 0.1…10 min D – 1.0…100 min E –0.1…10 hr

Code ON Time, Type HV A 0.1…10 s B 1.0…100 s C 0.1…10 min D 1.0…100 min E 0.1…10 hr

U12 –12V DC U24 –24V AC/DC, 50/60 Hz U120 – 120V AC/DC, 50/60 Hz A2 –240V AC, 50/60 Hz

Socket and Retainer Clip Reference Relay Type 700-HV

Socket Cat. No.

Retainer Clip Cat. No.

700-HN100

700-HN110

700-HN125

Not Required(1)

(1) Design of these sockets holds the relays securely and does not require retainer clips.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

133

Page 134

Relay and Timer Specifications

Accessories - 700-HV Relays Photo

134

Description

Pkg. Qty.

Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) and HRM, -NRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten

10

700-HN100

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing 10 Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.

700-HN125

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 135

Relay and Timer Specifications

Specifications - 700-HV Relays Cat. No. 700-HV… Electrical Ratings Pilot Duty Rating‡

NEMA B300

Rated Thermal Current (Ith)

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Make

Break

Inductive Contacts

Hp

120V AC

30 A

3A

1/2 N.O. 1/3 N.C.

240V AC

15 A

1.5 A

1/2 N.O. 1/3 N.C.

Resistive 28V DC

10 A

10 A, 85…110 of Nominal Voltage at 50 Hz 85…110 of Nominal Voltage at 60 Hz 80…110 of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

AC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

DC

1.3 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection Mechanical

Degree of Protection

Open Type (Guarded Terminal Sockets)

Mechanical Life Operations

10 x 106

Switching Frequency Operations

18,000/hr

Timing

Duty Cycle

Continuous

Repeat Accuracy (constant voltage and temperature)

±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

Repeat Accuracy (variable voltage and temperature)

±10% High End of Range

+5%

Low End of Range

-50%

Scale Tolerance Reset Time

100 ms Environmental Operating

–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)

Storage

–55…+85 °C (–67…+185 °F)

Temperature

Altitude

2000 m (6560 ft.)

Construction Insulating Material

Molded High Dielectric Material

Enclosure

Impact Resistant Dust Cover

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

135

Page 136

Relay and Timer Specifications

Contact Material

Silver Cadmium Oxide

Terminal Markings on Socket

In accordance with EN50 005

Sockets

8-Pin Socket Cat. No. 700-HN100, -HN125

Certifications

CSA Certified, File 223833; UL Recognized, File E3125; Guide NLDX 2; cULus Listed when used with 700-HN100 and 700HN125 sockets; CE Marked

Standards

EN 61812; EN 60947-1, -5-1; CSA 22.2 No. 14; UL 508

Timing Diagram- 700-HV Relays

Dimensions - 700-HV Relays Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

700-HV Timing Relay

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lbs.) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lbs.) (5/pkg)

136

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 137

Relay and Timer Specifications

Cat. No. 700-HN100 Panel Mounting Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)

Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire - Up to #12 AWG Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

137

Page 138

Relay and Timer Specifications

700-HX Multi-Function Digital Timing Relay • Digital timing relay with LCD display • Socket- or panel-mounted (NEMA 4X/IP66) • 5A, B300, SPDT contact ratings • 10 Functions or modes • Environmentally friendly, flash memory, no battery Photo

Operating Mode

Timing Range

A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode: On/Off duty adjustable repeat cycle S mode:stop watch toff: Flicker OFF start 1 ton: Flicker ON start 1 toff-1: Flicker OFF start 2 ton-1: Flicker ON start 2

0.000…9.999 s 0.000…99.99 s 0.000…999.9 s 0.000…9999 s 0.000…99 min 59 s 0.000…999.9 min 0.000…9999 min 0.000…99 hr 59 min 0.000…999.9 hr 0.000…9999 hr

Socket Type

700-HN100 700-HN125

Contact Output

SPDT

No. of Pins

8

Input Voltage

Cat. No.

100…240V AC

700-HX86SA17

24V AC 12…24V DC

700-HX86SU24

Socket and Retainer Clip Reference Timer Type

700-HX

Socket Cat. No.

Retainer Clip Cat. No.

700-HN100

700-HN131

700-HN108

Not Required (1)

700-HN125

Not Required

(1) Design of socket holds the relay securely and does not require retainer clips.

Accessories - 700-HX Relays Photo

138

Description

Pkg. Quantity

Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HX Timing Relays. Order ten or multiples of ten

10

700-HN100

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HX Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.

10

700-HN125

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Rockwell Automation Publication 700-TD552C-EN-P - October 2018