The text of a spec sheet · part 15 of 27

Relay and Timer Specifications, Bulletin Number 700: General Purpose Electronic Timers and Counters, pages 139 to 148

Pages 139 to 148 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 139

Relay and Timer Specifications

Photo

Description

Pkg. Quantity

Cat. No.

Specialty Socket 8-pin backwired socket with solder terminals. For use with 700-HX Timing Relays.

10

700-HN108

Retainer Clip for Cat. Nos. 700-HN100 Sockets with all 700-HX Timing Relays Secures timer in socket.

10

700-HN131

Frame Adapter For flush or door mounting of all 700-HR and -HX timers.

1

700-HN130

Protective Cover Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HR and -HX timing relays.

1

700-HN132

Note: Not required for installation

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

139

Page 140

Relay and Timer Specifications

General Timer Functions- 700-HX Relays Display Section

Operation Key

1. Key Protect Indicator (orange)

4

2. Control Output Indicator (orange)

5 1 2 3 8

3. Reset Indicator (orange) 4. Present Value Display (Main display) (Character height: 12 mm, red *) * Characters on models with screw terminals can be switched between red, green, and orange.

8. Mode Key (Changes modes and setting items)

6 7

10 11

9

Front View

9. Reset Key (Resets present value and output) 10. Up Keys 1 to 4 11. Down Keys 1 to 4

12

5. Time Unit Indicators (Color is same as present value display.) (If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators flash to indicate timing operation.) 6. Set Value Display (Sub-display) (Character height: 6 mm, green) 7. Set Value 1, 2 Indicator (green) Character Size for Present Value Display

12 mm

140

Character Size for Set Value Display

6 mm

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Switches 12. Key-protect Switch (Default setting)

OFF (Disabled)

ON (Enabled)

Page 141

Relay and Timer Specifications

Specifications - 700-HX Relays Attribute

700-HX

Electrical Ratings Pilot Duty Rating

NEMA B300

Rated supply voltage

100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.)

Operating voltage range

85…110% of rated supply voltage

Power consumption

Inrush Current

Make

Break

100…240V AC

4.3VA

24V AC/12…24V DC

3.4VA/1.7 W

100…240V AC

3A

24V AC/12…24V DC

5A

120V AC

30 A

240V AC

15 A

120V AC

3A

240V AC

1.5 A

Hp at 120V AC

1/4 Hp

Hp at 240V AC

1/3 Hp Mechanical

Mounting Method

Flush mounting, surface mounting, DIN mounting

Display

Seven-segment, negative transmissive LCD; Present value (red, 12 mm high characters); Set value (green, 6 mm high characters)

Digits

Four digits

Timer

Inputs

Time ranges

0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min 00 s…99 min 59 s, 0.0…999.9 min, 0 hr 00 min…99 hr 59 min, 0.0 hr…999.9 hr, 0 hr…9999 hr

Timer modes

Elapsed time (Up), remaining time (Down), selectable

Output modes

A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, tOFF, tON, tOFF-1, or tON-1

Input signals

Start, reset

Input method

No-voltage input via:NPN transistor or switching of contact

Start, reset, gate

Minimum input signal width: 1 or 20 ms (selectable)

Power reset Control output

Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode) SPDT contact output: 5 A at 250V AC, resistive load (cosine=1) Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value)

External Power Supply

No

Key Protect

Yes

Memory Backup Accuracy of Operating Time and Setting Error (1)

EEP-ROM (overwritten 100 000 times min), which can store data for 10 years min. Power-ON start: +-0.01% +-50 ms max. (1)to be rated against set value Signal start: +- 0.005% +-30 ms max. (1)to be rated against set value Signal start at transistor output model: +- 0.005% +-3 ms max. (2) If the set value is within the sensor waiting time (250 ms max.)

(1) The values are based on the set value. (2) The value is applied for a minimum pulse width of 1 ms.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

141

Page 142

Relay and Timer Specifications

Attribute

700-HX Environmental

Installation environment

Setup category II, pollution degree 2 (as per IEC61010-1)

Ambient temperature

-10 to +55 °C (Avoid freezing or condensation)

Ambient humidity

25 % to 85 %

Storage temperature

-25 to +65 °C (Avoid freezing or condensation)

Altitude

MAX. 2,000 m

Characteristics

(1)

Insulation Resistance

100 mΩ min. (at 500V DC)

Dielectric Strength

2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-current- carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between noncontinuous contacts

Noise Immunity

±1.5 kV (between power terminals) for 100 to 240 VAC, ±480V for 24VAC/12 to 24VDC, and ±600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static Immunity

±8 kV (malfunction), ±15 kV (destruction)

Vibration Resistance

Malfunction

10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min

Shock Resistance

Malfunction

98 m/s2 (approx. 10 G) each in three directions

Mechanical

10 million operations min. (under no load at 18 000 operation/hr)

Electrical

100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)

(EMI)

EN61812-1

Life Expectancy

EMC

Emission Enclosure:

EN55011 Group1 class A

Emission AC mains:

EN55011 Group1 class A

(EMS)

EN61812-1

Immunity ESD:

EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3)

Immunity RF-interference:

EN61000-4-3: 10 V/m Panel surface:IP66 and NEMA Type 4 (indoors) (2)

Enclosure Ratings Weight

Approx. 100 g

Certifications

CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked

Standards

EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508

(1) More information in the 700-HX User Manual, publication 700-UM002. (2) An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.

142

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 143

Relay and Timer Specifications

Timing Charts- 700-HX Relays One-Shot Sustained Output

One-shot outputs can be set to 0.1s, 0.5 s, 1 s, 5 s, 10 s, or 20 s.

Output Mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)

Timing starts when the start signal goes ON. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.

Power

Start signal

Basic Operation

Gate* Reset t t

Control output t

Power ** Start Signal Input Timing

Set value Timing diagram

UP

Output

0

Set value DOWN 0

*Output is instantaneous when setting is 0. ** Start signal input is enabled during timing. Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)

Timing starts when the reset input goes ON and is reset when the start signal goes OFF. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.

Power

Start signal Gate*

Basic Operation

Reset

Power Control output

Start Signal Input

Set value UP Timing diagram

0

Timing

Output

Set value DOWN 0

*Output is instantaneous when setting is 0. Output Mode A-2: Power ON Delay 1 (Timer resets when power comes ON)

Power

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.

Start signal Gate *

Basic Operation

Reset

Power

Control output

Timing Set value Timing diagram

UP

Output

0

*Output is instantaneous when setting is 0.

Set value DOWN 0

Output Mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON) Power

Start signal Gate * Reset Control output Set value Timing diagram

UP

0

Set value DOWN 0

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.

Basic Operation Power Timing Sustained Output *Output is instantaneous when setting is 0.

Gate not included on any mode of this relay.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

143

Page 144

Relay and Timer Specifications

Output Mode B: Repeat Cycle (Timer resets when power comes ON.)

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Sustained Output

Basic Operation

Power

Start signal

Power Gate*

** Start Signal Input

Reset

Timing

Control output

Timing diagram

UP

Timing

Timing

Timing

Output

Set value 0

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled diring timing.

Set value DOWN 0

Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power cones ON or when the reset input goes OFF.

One-Shot Output Power

Basic Operation

Start Signal

Power

Gate*

** Start Signal Input

Reset

Timing

Control Output

Timing

Timing

Timing

Output

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Set Value 0 Timing UP Set Value Diagram 0 DOWN

Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON) Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at the start). While the start signal is ON, the timer starts when the power comes ON or when the rest input goes OFF.

Sustained Output

Basic Operation

Power

Power ** Start Signal Input

Start signal Gate*

Timing

Reset

Set value Timing diagram

Timing

Output

Control output

UP

Sustained

* Normal output operation will not be possible if the set time is too short Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during.

0

Set value DOWN 0

One-Shot Output

Timing starts when the start signal goes ON. The control output comes ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Basic Operation Power

Power Start signal Gate*

** Start Signal Input

Timing

Timing

Reset

Output Control output Set value Timing diagram

UP

0

Set value DOWN 0

Gate not included on any mode of this relay.

144

Sustaining

* Normal outout operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 145

Relay and Timer Specifications

Output Mode D: Signal OFF-Delay (Timer resets when power comes ON.)

The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer is reset when the time is up.

Power

Start signal

Basic Operation Gate*

Power ** Start Signal Input

Reset Control output

Timing

Set value Timing diagram

UP

Output

0

* Output functions only during start signal input when setting is 0. ** Start signal input is enabled during timing.

Set value DOWN 0

Output Mode E: Interval (Timer resets when power comes ON.)

Timing starts when the start signal comes ON. The control output is reset when time is up. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Power

Basic Operation

Start signal Gate*

Power

Reset

** Start Signal Input

Control output

Timing

Set value Timing diagram

UP

0

Output

Set value DOWN 0

* Output is disabled when the setting is 0. ** Start signal input is enabled during timing. Output Mode F: Cumulative (Timer does not reset when power comes ON) Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.

Basic Operation Power Start Signal Input Timing

Output

Timing Sustained

*Output is instantaneous when setting is 0.

Gate not included on any mode of this relay.

Z Mode Output quantity can be adjusted by changing the cycle time set in the adjustment level to 1 and by changing the ON duty (%) set value. The set value shows the ON duty (%) and can be set to a value between 0 and 100 (%). When the cycle time is 0, the output will always be OFF. When the cycle time is not 0 and when ON duty has been set to 0 (%), the output will always be OFF. When ON duty has been set to 100 (%), the output will always be ON.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

145

Page 146

Relay and Timer Specifications

Z mode: ON/OFF-duty Adjustable Repeat Cycle Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Power

Basic Operation

Start signal * Gate

Power

Reset

** Start signal input

Timing ON duty (%)

ON duty setting (%) ON time 0

UP

Timing (cycle time)

Timing (cycle time)

Control Output Cycle time

Timing ON duty (%)

Output

Cycle time Timing diagram

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is enabled during timing.

ON duty setting (%) ON time 0

DOWN

Output Mode S: Stop Watch (Timer resets when power comes ON) Power

Start signal

Gate/Reset

The signal starts and stops timing. The display is held and timing is continued if the reset or gate input is received during timing operation. The timer resets if the reset or gate input is received when the timing operation is stopped.

Basic Operation

9999

Power

Timing diagram

Set time Start signal input

UP

Timing

Gate/Reset

0 Set time DOWN 0

Output

*

Display (for elapsed time)

* RST flashes

Note: Output is instantaneous when setting is 0.

Output Mode T OFF: Twin Timer OFF start

Sustained Output Power

Start signal

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Basic Operation

* Gate

Reset Control Output

Power ** Start Signal Input Timing OFF

OFF Time UP Timing diagram

ON Time

ON Time 0

Timing ON

Output * Normal output operation will not be possible if the ON/OFF set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Gate not included on any mode of this Relay.

146

Timing OFF

0 OFF Time

DOWN

Timing ON

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 147

Relay and Timer Specifications

Output Mode T ON: Twin Timer ON start

Sustained Output

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Power

Start signal

Basic Operation * Gate

Power ** Start Signal Input

Reset Control Output

Timing ON

OFF Time UP

ON Time

Timing diagram

Timing OFF

Timing ON

Timing OFF

Output

0 OFF Time

DOWN

* Normal output operation will not be possible if the ON/OFF set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

ON Time 0

Output Mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Power

Start signal

Basic Operation Gate

Power Reset

* Start signal input

Control output

Timing OFF

Timing ON

Timing OFF a b

Timing diagram

Output OFF time UP ON time

(a + b = ON time)

* Start signal input is disabled during timing. Note: Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type).

0 OFF time DOWN ON time 0

Output Mode TON-1: Flicker ON start 2 (Timer does not reset when power comes ON) Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Basic Operation Power

* Start signal input

Timing ON

Timing OFF

Timing ON a b

Output (a + b = OFF time)

* Start signal input is disabled during timing. Note: Normal output operation will not be possible if the set time is too short.

Gate not included on any mode of this Relay.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

147

Page 148

Relay and Timer Specifications

Dimensions- 700-HX Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 48×48

7.5

14.3

63.7

44.8×44.8

60 min. 45 +0.6 −0 45 +0.6 −0 60 min. 15 min.

Cat. No. 700-HX… Panel Cutout

5.2 (13/64)

6.2 (15/64)

50 (1-63/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

7.5 (0.3)

1000 (39-3/8) Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Terminal Arrangement

Internal circuit Signal Reset

4

5

3

6 7

2 1

8

0V

(–) (+) Cat. No. 700-HX…

148

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

27.0 (1.06)