The text of a spec sheet · part 12 of 27
Relay and Timer Specifications, Bulletin Number 700: General Purpose Electronic Timers and Counters, pages 109 to 118
Pages 109 to 118 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 109
Relay and Timer Specifications
700-HNK Ultra-Slim Timing Relay • The ultra-slim timing relay is the smallest relay available • It is perfect for converting 700-HK relays into a timing relay • SPDT and DPST-NO contact output • Socket-mounted • Timing range From 0.1 s…10 hr Photo
Timing Mode
Socket Type
Contact Output
Timing Range
0.1 s…10 min 700-HN121
SPDT (1) 0.1 min…10 hr
On-Delay One Shot Repeat Cycle, OFF-start Repeat Cycle, ON-start 0.1 s…10 min 700-HN122
DPST-NO(2) 0.1 min…10 hr
Input Voltage
Cat. No.
12V DC
700-HNK41AZ12
24V DC
700-HNK41AZ24
24V AC
700-HNK41AA24
12V DC
700-HNK41BZ12
24V DC
700-HNK41BZ24
24V AC
700-HNK41BA24
12V DC
700-HNK42AZ12
24V DC
700-HNK42AZ24
24V AC
700-HNK42AA24
12V DC
700-HNK42BZ12
24V DC
700-HNK42BZ24
24V AC
700-HNK42BA24
(1) 5-blade terminal type only. (2) 8-blade terminal type only.
Accessories - 700-HNK Relays Pkg. Quantity
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniatue socket. For use with 1-pole type 700-HNK41 timers. Socket includes a retainer clip.
10
700-HN121
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole, 700-HNK42 timers. This socket includes a retainer clip.
10
700-HN122
Description
Sockets and Retainer Clip Reference Timer Type 700-HNK
Socket Cat. No. 700-HN121 700-HN122
Retainer Clip Cat. No. Provided Provided
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
109
Page 110
Relay and Timer Specifications
Specifications - 700-HNK Relays Attribute
700-HNK
Pilot Duty Rating
NEMA B300
Rated Supply Voltage
24V AC; 12, 24V DC
Pin Type
Plug-in
Operating Mode
ON-delay, One Shot, Repeat Cycle OFF start, or Repeat Cycle ON start selectable with DIP switch.
Operating Voltage Range
85%…110% of rated supply voltage (12 VDC: 90%…110% of rated supply voltage) (1)
Power Consumption
24V AC:Relay ON:approx. 0.8 VA (at 24 VAC, 60 Hz) Relay OFF:0.5 VA (at 24V AC, 60 Hz) 12V DC:Relay ON:approx. 0.4 W (at 12V DC) Relay OFF:0.1 W (at 12V DC) 24V DC:Relay ON:approx. 0.5 W (at 24V DC) Relay OFF:0.2 W (at 24V DC)
Control Outputs
5 A at 250V AC, resistive load (cos φ = 1) The minimum applicable load is 10 mA at 5 VDC (P reference value).
Characteristics Make
Break
120V AC
30 A
240V AC
15 A
120V AC
3A
240V AC
1.5 A
Hp at 240V AC Accuracy of Operating Time
1/6 Hp ±1% FS max. (1 s range: +1% ±10 ms max.)
Setting Error Reset Time
±15% +50 ms FS max. 12, 24V DC: 0.1 s max. (including halfway reset) 24V AC: 0.5 s max. (including halfway reset)
Min. power-opening time:
Influence of Voltage
±2% FS max.
Influence of Temperature
±2% FS max.
Insulation Resistance
100 mΩ min. (at 500V DC)
Dielectric Strength
2000V AC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different poles) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration Resistance
Malfunction: 10…55 Hz, 0.5 mm single amplitude
Shock Resistance
Malfunction: 100 m/s2 (approx. 10G)
Ambient Temperature
Operating: -10 °C…50 °C (with no icing) Storage: -25 °C…65 °C (with no icing)
Ambient Humidity
Operating: 35…85%
Life Expectancy
Mechanical: 10 000 000 operations min. (under no load at 1800 operations/hr) Electrical: 100 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
Impulse Withstand Voltage
Between power terminals: 1 kV
Noise Immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static Immunity
Destruction: 8 kV Malfunction: 4 kV
Enclosure Rating
IP20
Weight
110
Approx. 18 g
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 111
Relay and Timer Specifications
Attribute
700-HNK
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A Immunity ESD: EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz…1GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance: ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
EMC
Standards
UL508, CSA C22.2 No. 14, EN/IEC 60947-5-1, EN/IEC 61812-1
Certifications cURus Recognized Component (File No. E14843, Guide NRNTZ/NRNT8), CE Marked, C-Tick Marked
(1) When using 700-HNK timer in any place where the ambient temperature is more than 50 °C, supply 90…110% of the rated voltages (12V DC: 95…11% of the rated voltage).
IMPORTANT t: Set time, Rt:Reset time
General Timer Functions Run/Power Indicator (Green) (Lit: Power ON)
Output Indicator (Orange) (Lit: Output ON)
Main Dial Set the desired time according to time range selectable by DIP switch.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
111
Page 112
Relay and Timer Specifications
Operating Mode
Timing Charts / Wiring Diagram 700-HNK41… Rt t ON-Delay
700-HNK42… t
Power t Output
Rt t
Power (1-5)
t
Power (1-8)
Time limit contact NC (4-2)
Time limit contact NO 4-3, 5-6
Time limit contact NO (4-3)
Run/Power indicator (PW)
Run/ Power
Output indicator (OUT)
Indicator (PW) Output Indicator (OUT)
Power (1-5)
One shot Power t
Time limit contact NO (4-3, 5-6)
Time limit contact NO (4-3)
Output
Rt t Power (1-8)
Time limit contact NC (4-2)
Run/Power indicator (PW)
Run/ Power
Output indicator (OUT)
Indicator (PW) Output Indicator (OUT) t t t t
Power (1-5)
Repeat Cycle OFF-Start
Time limit contact NC (4-2)
Power t t t
Output t t t t t t t t
Power (1-8) Time limit contact NO (4-3, 5-6)
Time limit contact NO (4-3)
Run/Power indicator (PW)
Run/ Power
Output indicator (OUT)
Indicator (PW) Output Indicator (OUT)
t
Time limit contact NC (4-2)
Power Output t t t t t
Power (1-5)
Repeat Cycle ON-Start t
Time limit contact NO (4-3) Run/ Power Indicator (PW)
Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Output Indicator (OUT)
112
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 113
Relay and Timer Specifications
Wiring- 700-HNK Relays
3
4
5
3
6
4
2 Timer Circuit
1
( ) ( )
~
OUT
PW
8
1
( ) ( )
Timer Circuit
( ) ( ~ ) OUT PW
~
Cat. No. 700-HNK42...
5 ( ) (~)
Cat. No. 700-HNK41...
A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNK in interval mode as shown in the following timing chart.
5
4 t
Rt t
Rt t
Power (3-8) 3 1 ( ) ( )
External Short Circuit (1-4)
6 Timer Circuit
~ OUT PW
8
External Input (1-3)
( ) ( )
~
Time Limit Contact NO (6-5) Run/Power Indicator (PW) Output Indicator (OUT)
External Input
~
(
50 ms min.
)
Note:t:Set time Rt: Reset time Mode
Terminals
Pulse Operation
Power supply between 3 and 8 Short-circuit between 4 and 1 Input signal between 3 and 1
Operating mode; One shot and all other modes
Power supply between 1 and 8
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
113
Page 114
Relay and Timer Specifications
Time Ranges- 700-HNK Relays Cat. No.
Time Range
Time Setting Range
1s
0.1…1 s
Yes
10 s
1…10 s
No
1 min
0.1 s…1 min
No
10 min
1…10 min
No
1 min
0.1…1 min
Yes
10 min
1…10 min
No
1 hr
0.1…1 hr
No
10 hr
1…10 hr
No
700-HNK41AZ12 700-HNK41AZ24 700-HNK41AA24 700-HNK42AZ12 700-HNK42AZ24 700-HNK42AA24
700-HNK41BZ12 700-HNK41BZ24 700-HNK41BA24 700-HNK42BZ12 700-HNK42BZ24 700-HNK42BA24
Setting
Factory-Set
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes - 700-HNK Relays Operating Mode
Setting
On-delay
Yes
One Shot
No
Repeat Cycle Off-start
No
Repeat Cycle On-start
No
Note: The right two DIP switch pins are used to select the operating modes.
114
Factory-set
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 115
Relay and Timer Specifications
Dimensions - 700-HNK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
47.4 (1.86) 46.0 (1.81)
12.8 (0.50)
46.0 (1.81)
6.0 (0.23)
31.2 (1.22) 28.8 (1.13)
28.8 (1.30) 31.2 (1.22)
700-HNK41 SPDT Contact
7.11 (9/32)
11 4
47.0 (1.86)
12.8 (0.50)
6 (0.23)
14 3
700-HNK42 DPST-NO Contact
2.03 (5/64) Five M3.5 x 0.315 Screws 4.06 (5/32)
12 2 3.0 Ø (1) (1/8) Use M3 Screws
84.1 (3-5/16) 5 (+) (A1)
21 6
39.5 (1-17/32) 35.5 (1-13/32)
22 7 24 5
4.06 (5/32) 29.9 (1-3/16)
84.1 (3-5/16)
4.06 (5/32)
1 (-) (A2) 15.6 (5/8)
54.1 (2-1/8)
Cat No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in) Total height: 700-HN121 + 700-HNK41 is 78.0 mm.
2.03 (5/64)
11 3 Eight M3.5 x 0.315 Screws 12 2 14 4 3.0 Ø (1) (1/8) Use M3 Screws
8 (+) (A1)
1 (-) (A2)
15.6 (5/8)
7.11 (9/32)
4.06 (5/32) 39.5 (1-17/32) 35.5 (1-13/32)
29.9 (1-3/16) 54.1 (2-1/8)
Cat No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in) Total height: 700-HN122 + 700-HNK42 is 78.0 mm.
(1) Holes required for mounting [3 mm (1/8 in.) diameter].
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
115
Page 116
Relay and Timer Specifications
700-HR Dial Timing Relays • Socket- or panel-mounted • 5 A contact ratings or transistor outputs • Single- or Multi-Function • Timing range from 0.05 s…300 hr • Multi-voltage inputs
Multi-Function Timing Relays with Trigger and Reset Switch Options • Socket or Panel Mounted • Timing Range From 0.05 s…300 hr • 11-pin base for socket cat. nos. 700-HN101, -HN126, -HN129 • Trigger: Power on or optional trigger signal • Reset: Power off or optional reset signal Timing Mode
On-Delay (A) OFF-Delay (D) One Shot (E) Repeat cycle OFF-Start (B) Repeat Cycle ON-Start (B2) Signal ON/OFF-delay (C) Delayed One Shot (J) Signal ON/OFF - Delay (G)
Supply Voltage
24…48V AC 12…48V DC
100…240V AC 100…125V DC
Trigger Options
Reset Options
Outputs
Cat. No.
1. Power On 2. Start Signal - contact closure (zero volts) - NPN transistor 3. Gate Signal (pause)
1. Power Off 2. Reset Signal - contact closure (zero volts) - NPN transistor
DPDT
700-HR52TU24
Transistor
(1)
1. Power On 2. Start Signal - contact closure (voltage) - NPN transistor - PNP transistor
Power Off
DPDT
700-HRV52TU24
1. Power On 2. Start Signal - contact closure (zero volts) 3. Gate Signal (pause)
1. Power Off 2. Reset Signal - contact closure (zero volts)
DPDT
700-HR52TA17
1. Power On 2. Start Signal - contact closure (voltage)
Power Off
DPDT
700-HRT6TTU24
(1)
700-HRV52TA17
(1) Voltage input connection to high signal instead of OV signal.
Multi-Function Timing Relays with Power On Trigger • Socket or Panel Mounted • Timing Range From 0.05 s…300 hr • 8-pin base for socket cat. nos. 700-HN100, -HN125, -HN108 • Trigger: Power on • Reset: Power off Timing Mode
ON-Delay (A) One Shot (E) Repeat Cycle OFF-Start (B) Repeat Cycle ON-Start (B2) Delayed One Shot (J)
Supply Voltage
Trigger Options
Reset Options
24…48V AC 12…48V DC
Power On
Power Off
24…48V AC/DC
Power On
Power Off
100…240V AC 100…125V DC
Power On
Power Off
Outputs
Cat. No.
DPDT
700-HRS42TU24
SPDT Timed + Instantaneous Contact
(1)
SPDT Timed + Instantaneous Contact
700-HRP42TA17
DPDT
700-HRS42TA17
(1) Voltage input connection to high signal instead of OV signal.
116
700-HRT4TTU24
Transistor
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
700-HRP42TU24
Page 117
Relay and Timer Specifications
ON-Delay Timing Relays • Socket or Panel Mounted • Timing Range From 0.05 s…300 h • 8-pin base for socket cat. nos. 700-HN100, -HN125, -HN108 • Trigger: Power on • Reset: Power off Timing Mode Supply Voltage 24…48V AC/DC 24…48V AC, 12…48V DC ON-Delay (A) 100…240V AC
Trigger Options
Reset Options
Power On
Power Off
Power On
Power Off
Outputs SPDT Timed + Instantaneous Contact DPDT DPDT SPDT Timed + Instantaneous Contact
Cat. No. 700-HRC12TU24 700-HRM12TU24 700-HRM12TA17 700-HRC12TA17
Timing Mode Description
700-HRF Repeat Cycle Timing Relays • • • • • •
Socket or Panel Mounted Independently adjustable on- and off-time 8-Pin base for socket cat. nos. 700-HN100, -HN125, and -HN108 DPDT contact outputs Trigger: Power on Reset: Power off
• Hazardous location version available 700
–
HRF
7
2
D
Z12 b c d e f a
Catalog Number Explanation a Bulletin Number
- b Type of Relay
HRF–Repeat cycle with adjustable ON/OFF times
700 d Contact Output c Function
7–Repeat cycle with OFF start 8–Repeat cycle with ON start
2- DPDT e Timing Range f Supply Voltage
D–0.05 s…300 hr
A18- 100...240V AC 50/60 Hz U25 - 24V AC, 50/60 Hz; 24V DC Z12 - 12V DC Z45 - 48...125V DC
700-HRY Star-Delta Timing Relays • 8-Pin base for socket cat. nos. 700-HN100, -HN125, and -HN108 • SPDT timed + instantaneous contact outputs • Trigger: Power on • Reset: Power off 700 a
–
HRYY
6
F
A12 b c d e
Catalog Number Explanation a Bulletin Number
700
- b Type of Relay
HRYY–YStar-Delta timer c Function d Timing Range e Supply Voltage
6–SPDT timed + SPDT instant
F–Star: 0.5…120 s Delta: 0.05, 0.1, 1.25, 0.5, 0.75, 1.0 s
A12–100…120V AC, 50/60 Hz A22–200…240V AC, 50/60 Hz
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
117
Page 118
Relay and Timer Specifications
700-HRQ True Off-Delay Timing Relays • 11-Pin base for use with reset option, socket cat. nos. 700-HN101, -HN126, and -HN129 • 8-Pin base for use without reset option, socket cat. nos. 700-HN100, -HN125, and -HN108 • DPDT contact outputs • Trigger: Power off • Reset: optional reset signal 700
–
HRQ
N
2
G
A12 b c d e f a
Catalog Number Explanation a Bulletin Number
700
- b Type of Relay
HRQ–True OffDelay Timer c Function
N–No reset option, 8-pin terminals R–Reset option, 11-pin terminals d Contact Output
2–DPDT e Timing Range f Supply Voltage
G–0.05…12 s H–0.05…12 min
A12–100…120V AC, 50/60 Hz A22–200…240V AC, 50/60 Hz U25–24V AC, 50/60 Hz; 24V DC Z48–48V DC Z11–100…125V DC
Accessories - 700-HR Relays Photo
118
Description
Pkg. Qty. Cat. No.
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HR and -HX timing relays.
10
700-HN100
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HR and -HX timing relays. No retainer clip required.
10
700-HN125
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.
10
700-HN101
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.
10
700-HN126
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Rockwell Automation Publication 700-TD552C-EN-P - October 2018