The text of a spec sheet · part 19 of 27
Relay and Timer Specifications, Bulletin Number 700: NEMA Industrial Relays, pages 179 to 186
Pages 179 to 186 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 179
Relay and Timer Specifications
Maximum Allowable Off-State Leakage Current Voltage
Maximum Off-State Leakage Current [mA]
Maximum Off-State Leakage Current [mA]
Type R
Type RM
24V DC
23
8
24V AC
23
8
120V AC
5
2
Relay Data Type
700-R
Contact Arrangement
Up to 8 poles, available in any combination of N.O. or N.C. contacts
Contact Material
W (tungsten in a controlled gas atmosphere)
Coil Voltage Range
24…250V AC 24…250V DC
Coil Power
Sealed Voltage Range: –15… +10%
5.5 VA, 50/60 Hz 5.5 W DC
Inrush
5.5 VA, 50/60 Hz 5.5 W DC
Pickup Time
30 ms
Dropout Time
30 ms
Operating Temperature
–40…+60 °C (–40…+140 °F)
Mounting
Panel mount
Haz. Loc. Ratings
Class I, Division 2, Groups A, B, C, and D
Standards Compliance
ISA 12.12, CSA C22.2, No. 213, EN/IEC 60947-1, -5-1
Certifications cULus Listed (File No. E10314, Guide NOIV/NOIV7), CE Marked
700-R Operating Coils Coil Volts
700-R 2-…8-Pole AC
700-R 2-…8-Pole DC
24 48 110 115…125 120 208 220 240
60 Hz 77AB27 77AB134 77AB86, 77AB86, 77AB83 77AB83
50 Hz 77AB27 77AB134 77AB86, 77AB86, 77AB83 77AB83
77D152 77D166, 77D155, - - - 230…250, - 77D156
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
179
Page 180
Relay and Timer Specifications
Dimensions - 700-R Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 700-R Relays Type of Relay
No. of Poles
Open Type Without Enclosures
A Wide
B High
C Deep
D
E
B High
C Deep
D
2…4
1
55.56 (2-3/ 16)
88.90 (3-1/2)
92.25 (3-3/8)
79.38 (3-1/8)
0.91 (2)
104.78 (4-1/8)
185.74 (7-5/ 16)
103.19 (4-1/ 16)
146.05 (5-3/4)
85.73 (3-3/8)
1.81 (4)
5…8
2
55.56 (2-3/ 16)
88.90 (3-1/2)
111.13 (4-3/8)
79.38 (3-1/8)
1.02 (2-1/4)
112.71 (4-7/ 16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.49 (5)
C
B
A
B
D
700-R400…
D
700-R800…
160.6 max (6-21/64)
A
C 3.98 (0.16)
700 Type R
700-PS Timer
B
D
0.5 (.02)
2.25 (0.09)
E
700-N26
0.5 (.02)
Type 1 Enclosure
DIN Rail Adapter
Cat. No. 700
Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots. #8 Screws (Captive)
Relay Rail 5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
1000 (39-3/8)
7.5 (0.3)
Cat. No. 199-DR1 DIN Mounting Rail Series B
180
Approx . Ship Wt. [kg (lb)]
A Wide
A
C
Type 1 General Purpose Enclosure
Drawing Number
700 and 700DC
R
Approx . Ship Wt. [kg (lb)]
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
27.0 (1.06)
Page 181
Relay and Timer Specifications
700-RTC, Solid-State Timing Relay • • • • • • • • • • • • •
Timing functions 8 ON-delay 8 OFF-delay Timing ranges Seconds: 0.05…2, 0.2…8, 0.4…30, 2…120 Minutes: 0.015…1, 0.06…4, 0.25…16 and 1…64 AC, 50/60 Hz or DC 600V AC maximum 300V DC maximum Relays with fixed time delay Sealed contacts Harsh environments Hazardous locations Class I, Div. 2, Groups A, B, C and D
700-RTC Relay with Adjustable Time Delay – Relays with Provision for Instantaneous Contacts Relays listed below have slots for two timed contacts and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges. Number of Contact Cartridges Total 0 1
2
3
Open Type Without Enclosure
Instantaneous
Timed
Cat. No.
N.O.
N.C.
N.O.
N.C.
0
0
0
0
700-RTC00000⊗
0 0 0 1 0 0 1 0 0 1 2 0 1 1 2 0 0 1 1 0 0
0 0 0 0 1 0 0 1 0 0 0 1 1 0 0 2 1 1 0 2 1
1 0 2 1 1 1 0 0 0 2 1 2 1 1 0 1 1 0 0 0 0
0 1 0 0 0 1 1 1 2 0 0 0 0 1 1 0 1 1 2 1 2
700-RTC00100⊗ 700-RTC00010⊗ 700-RTC00200⊗ 700-RTC10100⊗ 700-RTC01100⊗ 700-RTC00110⊗ 700-RTC10010⊗ 700-RTC01010⊗ 700-RTC00020⊗ 700-RTC10200⊗ 700-RTC20100⊗ 700-RTC01200⊗ 700-RTC11100⊗ 700-RTC10110⊗ 700-RTC20010⊗ 700-RTC02100⊗ 700-RTC01110⊗ 700-RTC11010⊗ 700-RTC10020⊗ 700-RTC02010⊗ 700-RTC01020⊗
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
181
Page 182
Relay and Timer Specifications
Number of Contact Cartridges
Open Type Without Enclosure
Instantaneous
Total
4
Timed
N.O.
N.C.
N.O.
N.C.
2 1 2 0 1 2 1 0 0
0 1 0 2 1 0 1 2 2
2 2 1 2 1 0 0 1 0
0 0 1 0 1 2 2 1 2
Cat. No. 700-RTC20200⊗ 700-RTC11200⊗ 700-RTC20110⊗ 700-RTC02200⊗ 700-RTC11110⊗ 700-RTC20020⊗ 700-RTC11020⊗ 700-RTC02110⊗ 700-RTC02020⊗
⊗ Coil Voltage Code The Cat. No. as listed is not complete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-RTC00100⊗ becomes Cat. No. 700-RTC00100U24. For other voltages consult your local Rockwell Automation sales office or Allen-Bradley distributor. [V]
24V DC, 24V AC
120V DC, 110/120V AC
50/60 Hz
U24
U1
700-RTC Relays with Fixed Time Delay - Relays with Provision for Instantaneous Contacts Relays listed below have slots for two timed and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges. Number of Contact Cartridges Total 0 1
2
3
182
Timed
Open Type Without Enclosure Instantaneous
N.O.
N.C.
N.O.
N.C.
0 1 0 2 1 1 1 0 0 0 2 1 2 1 1 0 1 1 0 0 0 0
0 0 1 0 0 0 1 1 1 2 0 0 0 0 1 1 0 1 1 2 1 2
0 0 0 0 1 0 0 1 0 0 1 2 0 1 1 2 0 0 1 1 0 0
0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 0 2 1 1 0 2 1
Cat. No. 700-RTC00#0⊗ 700-RTC10#0⊗ 700-RTC20#0⊗ 700-RTC40#0⊗ 700-RTC11#0⊗ 700-RTC12#0⊗ 700-RTC30#0⊗ 700-RTC21#0⊗ 700-RTC22#0⊗ 700-RTC50#0⊗ 700-RTC41#0⊗ 700-RTC14#0⊗ 700-RTC42#0⊗ 700-RTC13#0⊗ 700-RTC31#0⊗ 700-RTC24#0⊗ 700-RTC15#0⊗ 700-RTC32#0⊗ 700-RTC23#0⊗ 700-RTC51#0⊗ 700-RTC25#0⊗ 700-RTC52#0⊗
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 183
Relay and Timer Specifications
Number of Contact Cartridges
Open Type Without Enclosure
Timed
Total
4
Instantaneous
N.O.
N.C.
N.O.
N.C.
2 2 1 2 1 0 1 0 0
0 0 1 0 1 2 1 2 2
2 1 2 0 1 2 0 1 0
0 1 0 2 1 0 2 1 2
Cat. No. 700-RTC44#0⊗ 700-RTC43#0⊗ 700-RTC34#0⊗ 700-RTC45#0⊗ 700-RTC33#0⊗ 700-RTC54#0⊗ 700-RTC35#0⊗ 700-RTC53#0⊗ 700-RTC55#0⊗
# Operating Mode Replace the # in the cat. no. with the appropriate letter and numbers to indicate the operating mode and the fixed time delay value. Refer to operating mode table below. Digit
Operating Mode
Fixed Time Delay
S
On-Delay – s
Z
Off-Delay – s
Seconds –Two digits indicating the fixed time delay in seconds. Three digits indicating the fixed time delay (first digit indicates seconds, next two digits indicate 1/100 seconds).
Y
On-Delay – Min.
I
Off-Delay – Min.
EXAMPLE
Minutes –Two digits indicating the fixed time delay in minutes. Three digits indicating the fixed time delay (first digit indicates minutes, next two digits indicate 1/100 minutes).
Cat. No. 700-RTC00Y200U1 is for a relay without contact cartridges. “Y20” indicates an On-Delay timer with a 20 minute fixed time delay. This is a “standard relay.” Order the contact cartridges separately. Cat. No. 700-RTC42S020U1 is for a relay with 2 N.O. cartridges in the timed position and 1 N.C. cartridge in the instantaneous position. “S02” indicates an On-Delay timer with a 2 second fixed time delay.
⊗ Coil Voltage Code The cat. no. as listed is not complete. To complete the cat. no., add a coil code selected from the table below. [V]
24V DC, 24V AC
120V DC, 110/120V AC
50/60 Hz
U24
U1
Accessories - 700-RTC Relays Description
Photo
Contact Cartridges – These cartridges are used to add contacts to timing relays having unused slots. The N.O., N.C., and Dummy cartridges are interchangeable and can be used in timed or instantaneous contact slots. Dummy cartridges should be placed in unused cartridge slots to guard against entrance of foreign material. Cat. No. 700-CRT5
Cat. No. 700-CRT6
Cat. No. 700-CR9
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Cartridge Type
Color
Cat. No.
N.O.
Grey
700-CRT5
N.C.
Orange
700-CRT6
Dummy Cartridge
Black
700-CR9
183
Page 184
Relay and Timer Specifications
Description
Photo
Cartridge Type
Cat. No.
Color
Type 1 Enclosure, Use for all 700-P relays except 10- and 12-pole DC relays or 6-pole DC 700-PH relays.
700-N31
Relays per Strip
Pkg. Quantity
4
5
8
5
700-MP8
12
5
700-MP12
16
5
700-MP16
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
DIN Rail Adapter Can be used with the following relays: 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC
1
700-DRA
Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC
700-MP4
Specifications - 700-RTC Relays Voltage and Power Requirements
184
AC Voltage +10% –15% 50/60 Hz
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
Coil Code
24V AC
8 VA
4 VA
10 mA
U24
110/120V AC
9 VA
4 VA
2.4 mA
U1
DC Voltage +10% –20%
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
24V DC
10 W
5W
10 mA
U24
120V DC
11 W
5W
2.4 mA
U1
Coil Code
Type
700-RTC
Contact Rating
NEMA B600 600V AC, 5 A NEMA P300 300V DC, 5 A
Contact Arrangement
1…4 poles. Max. of 2 timed and 2 instantaneous. Available in any combination of N.O. and N.C. contacts
Contact Material
W (tungsten in a controlled gas atmosphere)
Operating Mode
Convertible to ON-Delay or OFF-Delay
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 185
Relay and Timer Specifications
Type
700-RTC
Timing Range
0.015…64 minutes; 0.05...120 seconds
Reset Time
25 ms
Repeat Accuracy
±1% (or ±50 ms) at constant voltage and temperature
Mounting
Panel or strip mount
Surge Suppression
Not required. Timers have internal suppression
Haz. Loc. Ratings
Class I, Division 2, Groups A, B, C, and D
Maximum Allowable Leakage Current
24V AC/DC
10 mA
110/120V AC, 120V DC
2.4 mA
Ambient Temperature (1) Operating:
–20…+60 °C (–4…+140 °F)
Storage:
–20…+60 °C (–4…+140 °F)
Standards Compliance
ISA 12.12, CSA C22.2, No. 213
Certifications cULus Listed (File No. E10314, Guide NOIV/NOIV7)
(1) Continuous duty units placed close to each other (3 in a row) have a temperature range of –20…+45 °C (–4…+113 °F) or should have air circulated around the units. Approximate space of 3/4 in (mm) on all sides is needed.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
185
Page 186
Relay and Timer Specifications
Typical Wiring Diagram - 700-RTC Relays L1 External Initiating Contact (N.O. or N.C.) Timed Contacts Any Combination of N.O. and N.C.
Instantaneous Contacts Any Combination of N.O. and N.C.
L2
P TIMED
L1 +
INST
L2
Dimensions - 700-RTC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
5.2 (2-13/64) Dia. Mounting Holes
Approximate Shipping Weight 0.92 kg (2.1 lb.)
186
NEMA Type 1 Enclosure for RTC Relays Approximate Shipping Weight 1.26 kg (2.8 lb.)
Rockwell Automation Publication 700-TD552C-EN-P - October 2018