The text of a spec sheet · part 18 of 27
Relay and Timer Specifications, Bulletin Number 700: NEMA Industrial Relays, pages 169 to 178
Pages 169 to 178 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 169
Relay and Timer Specifications
Specifications - 700S-P Relays Type
700S-P
Electrical 10 A @ 600V AC 5 A @ 600V DC
Contact Rating Continuous AC
NEMA A600
DC
NEMA P600
Ratings Make/ Break Minimum Contact Switching Ratings
10V, 50 mA Volts DC
Contacts in Series DC Switching Inductive Load
24V
64V
125V
250V
500V
600V
1
5A
2.2 A
1.1 A
0.55 A
0.24 A
0.2 A
2
10 A
10 A
5A
2A
0.7 A
0.5 A
3, - 7A
3A
1.5 A
1.0 A
4, - 10 A
5A
2.5 A
1.5 A
1.5 million operations at 10A break at 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC
Contact Electrical Life - Resistive Loads
Coil Voltage Range (1)
AC
85…110%
DC
80…110%
Battery Charging
85…115%
Coil Consumption
50 Hz
60 Hz
Inrush
132 VA
138 VA
Sealed
19.3 VA
19 VA
AC Inrush
12.7 W
Sealed
12.7 W
DC
Mechanical Mechanically Linked Contacts
All contacts are mechanically linked per IEC 947- 5-1 annex L for 2 to 12 poles Pickup
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
Operating Time Mechanical Life
10 million operations
Construction 2…12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum)
Contact Arrangement Contact Material/Design
Silver Nickel/Bifurcated
Mounting
Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended
Environmental Operating Temperature (2)
-20…+65 °C (-4…+149 °F)
Storage Temperature
-40…+65 °C (-40…+149 °F)
Wire Terminations Wire size per UL/CSA
#18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in (0.9…1.4 N•m)
Standards Compliance
UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS
(1) Coil voltage required for proper operation (percent of rated coil voltage). (2) Temperature inside the panel.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
169
Page 170
Relay and Timer Specifications
Specifications - 700S-PK Relays Type
700S-PK
Electrical 20 A @ 600V AC 10 A @ 600V DC
Contact Rating Continuous AC
NEMA A600
DC
NEMA P600
Ratings Make/ Break 3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 HP @ 120V AC - N.O./N.C. 20 A resistive heating to 600V AC 20 A Tungsten lighting load to 480V AC
Additional Contact Ratings for AC Single-Phase Loss
DC Current Ratings Make/Break
Cartridge Cat. No. 700-CMS Volts DC Contacts in Series 24V
DC Switching
Coil Voltage Range (1)
DC
125V
250V
500V
10 A
5A
2.2 A
0.55 A
0.24 A
0.2 A
2
20 A
10 A
5A
2A
0.7 A
0.5 A
3, 15 A
7A
3A
1.5 A
1.0 A
4, 20 A
10 A
5A
2.5 A
1.5 A
AC
85…110%
DC
80…110%
Battery Charging
85…115% 50 Hz
60 Hz
Inrush
132 VA
138 VA
Sealed
19.3 VA
19 VA
Inrush
12.7 W
Sealed
12.7 W
Mechanical All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles
Mechanically Linked Contacts Operating Time
Pickup
AC – 10…20 ms, DC – 30…50 ms
Dropout
AC – 10…20 ms, DC – 20…33 ms
Construction Contact Arrangement Contact Material/Design Mechanical (Mechanically-Linked Contacts) Mounting Environmental Operating Temperature (2) Storage Temperature Wire Terminations Wire size per UL/CSA Tightening Torque
2…12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum) Silver Cadmium Oxide All contacts, are mechanically linked per IEC 947-5-1 Annex L for 2 to 12 poles Panel mount or strip mount recommended -20…+65 °C (-4…+149 °F) -40…+65 °C (-40…+149 °F) #18 AWG…(2) #12 AWG 8…12 lb•in (0.9…1.4 N•m)
Standards Compliance
UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS
(1) Coil voltage required for proper operation (percent of rated coil voltage). (2) Temperature inside the panel.
170
600V
1
Coil Consumption AC
64V
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 171
Relay and Timer Specifications
Dimensions - 700S-P Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. AC 136.75 (5-25/64)
103.43 (4-5/64)
1/2
2.77 (7/64)
2.77 (7/64)
2- and 4-pole 700S-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb), DC – 1.34 kg (2.95 lb)
6- and 8-pole 700S-P Relay Approximate Shipping Weight: AC – 0.79 kg (1.75 lb), DC – 1.45 kg (3.20 lb)
170.10 (6-45/64) Cat. No. 700
#8 Screws (Captive)
2.77 (7/64)
10- and 12-pole 700S-P (Captive) Approximate Shipping Weight: AC – 1.02 kg (2.25 lb), DC – 1.68 kg (3.7 lb)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
Relay Rail
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
DIN Rail
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
171
Page 172
Relay and Timer Specifications
700-N Industrial Relays • Contact cartridges convertible from N.O. to N.C. and vice versa • NEMA A300 AC • 24…250V AC coils • Pneumatic timing unit • Solid-state timing unit • Overlap contacts • Logic reed contacts • 4-…8-pole
AC-Operated Relays Contacts
Photo
Type NM Relay 2 Poles§
Open Type
Contact Arrangement
N.O.
N.C.
Cat. No.
4, 700-N400⊗
2, 700-NM200⊗
⊗ AC Coil Voltage Code The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-N200⊗ becomes Cat. No. 700-N200A24 for 24V 60 Hz. For other coil voltages, contact your local Rockwell Automation sales office or Allen-Bradley distributor. [V]
24
110
120
208
220
240
50 Hz, A1, - A2, 60 Hz
A24, A1
A20, A2
IMPORTANT
172
• NORMALLY CLOSED CONTACTS: Listed relays are supplied with all contacts normally open. These contacts can be readily converted to normally closed in the field. • OVERLAP CONTACTS: Overlap contacts (normally open contact closes before the normally closed contact opens) can be supplied. See for information on kits for field installation of overlap contact cartridges. • Location of contacts in 2-pole relays • Permanent Magnet Latch AC Relay. Minimum Operating Time - Type NM - For reliable operation, power to the latch circuit must be maintained for a minimum time of 75 milliseconds and power to the unlatch circuit must be maintained for minimum time of 50 milliseconds.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 173
Relay and Timer Specifications
Operating Coils Photo
Coil Voltage
700-N Relay • 2-…8-Pole 60 Hz
50 Hz
24
84AB27
84AB28
110
84AB01
84AB86
120
84AB86, 208
84AB113, 220
84AB06
84AB83
240
84AB83, 700-NT Pneumatic Timing Unit Timed Contacts
Photo
Contact Arrangement
Description
N.O.
N.C.
Timing Unit Only (for 700-N, 2…4-pole)
1
1
Open Type
Cat. No.
ON-Delay mode is standard. Timer is easily converted to OFF-Delay mode.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
700-NT
173
Page 174
Relay and Timer Specifications
Specifications - 700-N Relays Attribute
Bul. 700-N
Electrical Ratings Rated Thermal Current Ith Rated Insulation Voltage Contact Rating Coil Voltage Range
Bul. 700-NT 10 A 300V 10 A @ 300V AC, NEMA A300
AC DC
85…110% 80…110%, - Coil Consumption 50 Hz AC
Inrush Sealed
60 Hz 120 VA 24 VA, - - 133 VA 20 VA
Mechanical AC
Timing Range Repeat Accuracy Reset Time
14 ms 13 ms, - - Timing Mode, - - - 0.2…60 s ±15% of setting 75 ms On-Delay, convertible to OFF Delay, up to 2 poles convertible to N.O. or N.C.
Up to 8 Poles, Convertible to N.O. or N.C. Silver Panel or strip mount Horizontal mounting recommended, Silver On relay only
Max. Operating Time
Construction Contact Arrangement Contact Material Mounting Environmental Ambient Temperature (Outside Enclosure)
Pickup Drop Out
Operating Storage Operating Temperature Rise (Inside Enclosure) Wire Terminations Wire size per UL/CSA Tightening Torque
–20…+40 °C (–4…+104 °F) –40…+60 °C (–40…+140 °F) +25 °C Max, #18 AWG…(2) #12 AWG 8…12 lb•in. (0.9…1.4 N•m)
Standards Compliance
UL 508, CSA C22.2, No. 14
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7)
174
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 175
Relay and Timer Specifications
Dimensions - 700-N Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. Type of Relay
No. of Poles
Open Type Without Enclosure Drawing Number
A Wide
B High
C Deep
D
Approx . Ship. Wt. kg (lbs.)
Type 1 General Purpose Enclosure A Wide
B High
C Deep
D
E
Approx . Ship. Wt. kg (lbs.)
700
2…4
1
57.15 (2-1/4)
88.90 (3-1/2)
82.55 (3-1/4)
79.38 (3-1/8)
0.68 (1-1/2)
107.95 (4-1/4)
185.74 (7-5/ 16)
103.19 (4-1/ 16)
146.05 (5-3/4)
85.73 (3-3/8)
1.59 (3-1/2)
700
6…8
2
57.15 (2-1/4)
88.90 (3-1/2)
106.36 (4-3/ 16)
79.38 (3-1/8)
0.79 (1-3/4)
112.71 (4-7/ 16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.27 (5)
N with Pneumatic Timer
700
2…4
3
57.15 (2-1/4)
88.90 (3-1/2)
138.11 (5-7/ 16)
79.38 (3-1/8)
0.91 (2), - - - - - N with Solid-State Timer
700
2…4
3
57.15 (2-1/4)
88.90 (3-1/2)
160.34 (6-5/ 16)
79.38 (3-1/8)
1.02 (2-1/4), - - - - - N
C
A
D B
A
C
A
C
D B
D B
Drawing Number 1
Drawing Number 2
Drawing Number 3
178.60 (7-1/32)
Cat. No. 700
#8 Screws (Captive)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
3.98 (0.16)
0.5 (.02)
2.25 (0.09) 0.5 (.02)
DIN Rail Adapter
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
175
Page 176
Relay and Timer Specifications
700-R Sealed Switch Relays • Sealed contacts • Extremely long mechanical and electrical life • Hazardous locations Class 1, Div 2 Groups A, B, C, D • Harsh environments • Suitable for applications with shock and vibration • High reliability circuit integrity No. of Poles 0 2
4
6
8
Electrically Held Contacts N.O. 0 2 1 0 4 3 2 1 0 6 5 4 3 2 1 0 8 7 6 5 4 3 2 1 0
AC-Operated Relay Only Open Type Cat. No. 700-R000⊗ 700-R200⊗ 700-R110⊗ 700-R020⊗ 700-R400⊗ 700-R310⊗ 700-R220⊗ 700-R130⊗ 700-R040⊗ 700-R600 ⊗ 700-R510 ⊗ 700-R420 ⊗ 700-R330 ⊗ 700-R240 ⊗ 700-R150 ⊗ 700-R060 ⊗ 700-R800 ⊗ 700-R710 ⊗ 700-R620 ⊗ 700-R530 ⊗ 700-R440 ⊗ 700-R350 ⊗ 700-R260 ⊗ 700-R170 ⊗ 700-R080 ⊗
Contact Arrangement and Markings‡ N.C. 0 0 1 2 0 1 2 3 4 0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8
Relay without Contact
DC-Operated Relay Only Open Type Cat. No. 700DC-R000⊗ 700DC-R200⊗ 700DC-R110⊗ 700DC-R020⊗ 700DC-R400⊗ 700DC-R310⊗ 700DC-R220⊗ 700DC-R130⊗ 700DC-R040⊗ 700DC-R600 ⊗ 700DC-R510 ⊗ 700DC-R420 ⊗ 700DC-R330 ⊗ 700DC-R240 ⊗ 700DC-R150 ⊗ 700DC-R060 ⊗ 700DC-R800 ⊗ 700DC-R710 ⊗ 700DC-R620 ⊗ 700DC-R530 ⊗ 700DC-R440 ⊗ 700DC-R350 ⊗ 700DC-R260 ⊗ 700DC-R170⊗ 700DC-R080 ⊗
‡ Arrangement displays all N.O. contacts. ♣ Location of contacts in 6-pole relays. Δ Polarity must be observed for DC voltage (700 DC) relays. ♦ Location of contacts in 2-pole relays.
⊗ Coil Voltage Code The Cat. No. as listed is incomplete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-R000⊗ becomes Cat. No. 700-R000A24. Type of Relay
[V]
AC
25, 50, 60 Hz
DC, 176
Coil Volts 24
48
110
115-125
120
220
230-250
240, A24 Z24, - Z48
A1, - - - Z1, A1, A2, - - - Z2, A2, Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 177
Relay and Timer Specifications
⊗ Coil Voltage Code The Cat. No. as listed is incomplete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-RM000⊗ becomes Cat. No. 700-RM000A24. For other coil voltages, contact your local Rockwell Automation sales office or Allen-Bradley distributor. Type of Relay
[V]
AC
25, 50, 60 Hz
DC, Coil Volts 24
48
110
115-125
120
220
230-250
240, - A1, - A2, - A24, - - A1, - A2
Z24
Z48, Z1, - Z2, Accessories - 700-R Relays Photo
Pkg. Qty.
Cat. No.
4 Relays per Strip
5
700-MP4
8 Relays per Strip
5
700-MP8
12 Relays per Strip
5
700-MP12
16 Relays per Strip
5
700-MP16
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
DIN Rail Adapter Can be used with the following relays: 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC
1
700-DRA
Front Deck with one N.O. Contact 1 Cartridge (700-R Relay)
700-RA10
Front Deck with one N.C. Contact 1 Cartridge (700-R Relay)
700-RA01
Front Deck with one N.O. Contact 1 Cartridge (700-RM Relay)
700-RB10
Front Deck with one N.C. Contact 1 Cartridge (700-RM Relay)
700-RB01
Description
Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC
Front Deck A front deck can be attached to 700 2-, 3-, or 4pole AC and DC Type R or RM relays.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
177
Page 178
Relay and Timer Specifications
Photo
Contact Cartridges These cartridges are used to increase the number of poles of a relay. A dummy cartridge is also available to fill empty space not occupied by a contact cartridge.
Cat. No. 700-CR5
Pkg. Qty.
Cat. No.
N.O. Contact Cartridge - Green (700-R Relay)
1
700-CR5
N.C. Contact Cartridge - Yellow (700-R Relay)
1
700-CR6
N.O. Contact Cartridge - Blue (700-RM Relay)
1
700-CR7
N.C. Contact Cartridge - Red (700-RM Relay)
1
700-CR8
“DUMMY” Cartridge - Black (700-R and -RM Relays)
1
700-CR9
12V DC (700-R Relay)
1
12V DC (700-RM Relay)
2
24V DC (700-R Relay)
1
24V DC (700-RM Relay)
2
48V DC (700-R Relay)
1
48V DC (700-RM Relay)
2
115…125V DC (700-R Relay)
1
115…125V DC (700-RM Relay)
2
230…250V DC (700-R Relay)
1
230…250V DC (700-RM Relay)
2
Description
Cat. No. 700-CR6
Cat. No. 700-CR9
Surge Suppressor When the circuit to a DC operating coil is opened, the inductive energy stored in the coil can generate very high transient voltages. With the addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated limiting the voltage spikes. A surge suppressor is not required with AC 700-R or -RM relays because the AC operating coil transients are suppressed by a full wave rectifier connected to the coil.
199-FSMA9
199-FSMA10
199-FSMA11
700-PS Solid-State Timing Unit You can attach a 700-PS solid-state timing unit to 4-pole 700-R or -RM relays. An adaptor kit, Cat. No. 700-N26, is required.
852S Solid-State Timing Unit You can attach a 852S solid-state timing unit to 4-pole 700-R or -RM relays.
Specifications - 700-R Application Data – Because of the inherent characteristics of this device, the normally open contacts may close before the normally closed contacts open on energization and the normally closed contacts may close before the normally open contacts open on de-energization.
ATTENTION: For 700-RM, energizing both the latch and unlatch coil together will cause the relay to be energized and both latch and unlatch coils can be operated together continuously.
Ratings AC Voltage NEMA Rating Designation
B300
C600
178
Voltage
Up to 300V AC
Above 300V AC
DC Voltage
Make
Break
120V
30
3
240V
15
1.5
480V
3.75
0.375
600V
3.0
0.30
Continuous Carrying Current [A]
NEMA Rating Designation
5
Volts DC
Make/Break
Continuous Carrying Current [A]
46…300
138 VA
5
5…46
3A
5
NEMA P300 2.5
Rockwell Automation Publication 700-TD552C-EN-P - October 2018