Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 17 of 27

Relay and Timer Specifications, Bulletin Number 700: NEMA Industrial Relays, pages 159 to 168

Pages 159 to 168 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 159

Relay and Timer Specifications

Electrically Held Relays, Typical Wiring Diagrams

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

159

Page 160

Relay and Timer Specifications

Pneumatic Time-Delay Unit • Timing Range, 0.1…60 s • 0, 2, or 4 instantaneous contacts • Two timed contacts, both ON Delay or both OFF Delay • Convertible from ON Delay to OFF Delay and vice versa • Standard contact cartridges rated NEMA A600 (AC) and P600 (DC) • Master contact cartridges rated 2X NEMA A600 (AC) and N150 P600 (DC) No. of Timed Contacts (1) Photo

Operating Mode N.O.

Continuous Carrying Current [A]

Arrangement

Timing Range

N.C.

Cat. No.

10 On-Delay Off-Delay

1

Open Type Without Enclosure(2)

1

700-PT 0.1…60 s

20

700-PKT

(1) In addition to instantaneous cartridges on the relay (2) Mounts on 4-pole Bulletin 700-P or -PK relay or 2-pole Bulletin 700-PH relay.

Mechanical Latch Units Photo

Description

AC-Operated Latch Units

DC-Operated Latch Units

160

Arrangement

Continuous Carrying Current [A]

Cat. No.

No cartridge

700-PLL⊗

10

700-PLL11⊗

20

700-PKLL11⊗

No cartridge

700DC-PLL⊗

10

700DC-PLL10⊗

20

700DC-PKLL10⊗

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 161

Relay and Timer Specifications

Accessories Photo

Relays per Strip

Description

Pkg. Quantity

Cat. No.

4

5

700-MP4

8

5

700-MP8

12

5

700-MP12

16

5

700-MP16

DIN Rail Adapter Can be used with the following relays: Bulletin 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC

1

700-DRA

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Type 1 Enclosure, Use for all Bulletin 700-P relays except 10- and 12-pole DC relays or 6-pole DC Bulletin 700-PH relays.

1

700-N31

Type 4/4X Enclosure, For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays.

1

700-N39

Type 7 & 9 Enclosure, For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays. 1 conduit hub; top and bottom.

1

700-N33

Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

161

Page 162

Relay and Timer Specifications

Accessories Photo

Description

700-N5

Mounting on coil terminal

1

700-N24

24…48V AC/DC

1

199-FSMA9

50…120V AC/ DC

1

199-FSMA10

130…250V AC/ DC

1

199-FSMA11

Diode Surge Suppressor, for 6…300V DC voltage coils. Used on Bulletin 700-P, -PH, -PK, -N, -F, and -R relays.

1

199-FSMZ-1

35 A Jumper Kit – CSA Approved, UL Listed This 35 A Jumper Kit can be used with any Bulletin 700-P and -PK AC or DC relay, Time-Delay relay or Latch Unit equipped with 20 A Master Cartridges. It does not require any additional panel space. Jumper Kit terminals are designed for one #8 AWG wire or two #10 AWG wires. When connecting the two 20 A Master Cartridges in parallel, it is important that they be the same configuration (Normally Open or Normally Closed). Jumpers can be added to any contact cartridge location on a relay except the two center poles because of the wide spacing. An adhesive label is included with each kit listing the contact ratings.

1

700-CPH

Surge Suppressor When the circuit to a DC operating coil is opened, the inductive energy stored in the coil can generate very high transient voltages. With the addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated limiting the voltage spikes. A surge suppressor is not required with AC 700-R or RM relays because the AC operating coil transients are suppressed by a full wave rectifier connected to the coil.

Cat. No. 700-N4

Jumpers (Not applicable for Bulletin 700-PH or -PK relays) – For connection between a middle pole and an outer pole on the left or right side of the relay.

Jumper – For outer poles

Jumpers (Not applicable for Bulletin 700-PH or -PK relays) – For connection between two middle poles.

Jumper – For middle poles

700-N4

Check Out Tool, Mechanically maintains the Bulletin 700-P, -PH, or -PK relay in the energized position for troubleshooting purposes.

700-N23

Adapter Plate, Simplified relay conversion. Allows you to use the existing mounting holes when you replace a Bulletin 700-B, -BR, -BX, or -D relay with a Bulletin 700-P, -PH, or -PK relay.

162

Cat. No.

Mounting behind 1 relay

Surge Suppressors (RC Circuit), Surge suppressors reduce the high transient voltages generated when the coil circuit is opened. These suppressors can be used with Bulletin 700-P, -PH, -PK, and -N relays, and other electromechanical devices. They contain a resistor and capacitor. Maximum ratings: 150V, AC or DC, 35 VA. Cat. No. 700-N5 requires 1 in. additional depth of enclosure.

Cat. No. 700-N3

Pkg. Quantity

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

700-N3 50

1 700-N34

Page 163

Relay and Timer Specifications

IP 2X Finger-Safe Cover Accessories Photo

Description

Pkg. Quantity

Cat. No.

IP2X Top Cover for 700-P

1

700-PFSC

Timer Top Cover Kit

1

700-PFSTC

Latch Top Cover Kit (for Relays with Mechanical Latch Attachment)

1

700-PFSLCK

Timer Top Cover Kit, (for Master Cont. Relays with Pneumatic Timer)

1

700-PFSKTC

Latch Top Cover Kit (for Master Cont. Relays with Mechanical Latch)

1

700-PFSKLCK

Top Covers (Covering Top Level Contact Screws)

Deck Covers (Covering all terminals not on top deck, only for multi-deck relays) IP2X Deck Cover for all AC & DC Relays in the 700P Range

1

700-PFSDEK

IP2X Coil Cover for all AC Relays in the 700P Range

1

700-PFSACC

IP2X Coil Cover for all DC Relays in the 700P Range

1

700-PFSDCC

Coil Covers

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

163

Page 164

Relay and Timer Specifications

Specifications - 700-P Relays Type

Standard Cartridge

Master Cartridge

Heavy duty

700-P

700-PMCKIT

700-PHDKIT

10 A @ 600V AC ; 5 A @ 600V DC

20 A @ 600V AC; 10 A @ 600V DC

35 A @ 600V AC; 20 A @ 600V DC

AC

NEMA A600

2 x NEMA A600

2 x NEMA A600

DC

NEMA P600

N150 P600

N150 P600

Additional Contact Ratings for AC single-phase loads, 3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 Hp @ 120V AC - N.O./N.C. 20 A Resistive Heating to 600V AC 20 A Tungsten Lighting Load to 480V AC

5 Hp @ 240V AC - N.O. 3 Hp @ 240V AC - N.O./N.C. 2 Hp @ 120V AC - N.O./N.C. 35 A General Use At 0.75 PF to 600V AC 35 A Tungsten Lighting Load to 480V AC

DC Current Ratings Make/Break

Cartridge Cat. No. 700-CP1

Cartridge Cat. No. 700-CPM

Cartridge Cat. No. 700-CPH

Bulletin No.

Electrical Contact Rating Continuous Ratings Make/Break

Volts DC Contacts in Series DC Switching Inductive Load

Coil Voltage Range

Coil Consumption

AC DC

PLL - PKLL AC Latch Unit

24

64

125

250

500

600

64

125

250

500

600

480 W

480 W

275 W

138 W

135 W

120 W

10 A

5A

2.2 A

.55 A

.24 A

.2 A

10 A

5A

2.2 A

.55 A

.24 A

.2 A

20 A

10 A

5A

2A

.7 A

.5 A

20 A

10 A

5A

2A

.7 A

.5 A

1.0 A, 15 A

7A

3A

1.5 A

1.0 A, 15 A

7A

3A

1.5 A

1.0 A

1.5 A, 20 A

10 A

5A

2.5 A

1.5 A, 20 A

10 A

5A

2.5 A

1.5 A

24

64

125

250

500

600

24

1

5A

2.2 A

1.1 A

.55 A

.24 A

.2 A

2

10 A

10 A

5A

2A

.7 A

.5 A

3, - 7A

3A

1.5 A

4, - 10 A

5A

2.5 A

AC

85…110%

85…110%

DC

80…110%

80…110%

85…110% 80…110%

Battery

85…115%

85…115%

85…115%

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

60 Hz

Inrush

132VA (2)

138VA (2)

132VA (2)

138VA (2)

132VA (2)

138VA (2)

Sealed

19.3VA (2)

19VA (2)

19.3 VA (2)

19VA (2)

19.3VA (2)

Inrush

12.7VA

Sealed

12.7VA (2)

12.7VA (2)

Sealed Inrush

(2)

19VA (2) 12.7VA (2)

12.7VA (2)

12.7VA (2)

15VA

(2)

15.6VA (2)

5VA (2)

15.6VA (2)

15VA (2)

15.6VA (2)

5.4VA

(2)

(2)

(2)

(2)

(2)

5.5VA (2)

5.5VA

5.4VA

5.5VA

5.4VA

(2)

35VA (2), PLL - PKLL DC Latch Unit

Unlatch

35VA

Intermittent

35 W (2)

35 W (2), Reset Time

PT – PKT

75 ms

75 ms, Minimum Pulse

PLL–PKLL

75 ms

75 ms, Mechanical Operating Time

Pickup

AC – 10…20 ms / DC – 30…50 ms

AC – 10…20 ms / DC – 30…50 ms

AC – 10…20 ms / DC – 30…50 ms

Dropout

AC – 10…20 ms / DC – 20…33 ms

AC – 10…20 ms / DC – 20…33 ms

AC – 10…20 ms / DC – 20…33 ms

Mechanical Life

10 million operations Construction

Contact Arrangement

Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)

Contact Material

Silver Nickel

Mounting

Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum)

Silver Cadmium Oxide

Silver Cadmium Oxide

Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended Environmental

Temperature

Operating (1)

–20…+65 °C (–4…149 °F)

–20…+65 °C (–4…149 °F)

–20…+65 °C (–4…149 °F)

Storage

–40…+65 °C (–40…149 °F)

–40…+65 °C (–40…149 °F)

–40…+65 °C (–40…149 °F)

Wire Terminations

Wire size per UL/CSA Tightening Torque Standards Compliance Certifications

#18 AWG…(2) #12 AWG 8…12 lb•in (0.9…1.4 N•m) UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1 cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS

(1) Temperature inside the panel. (2) Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales office or Allen-Bradley distributor.

164

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 165

Relay and Timer Specifications

International Symbol for Mechanically Linked Contacts

Dimensions - 700-P Relays with standard, master contact, or heavy-duty contact cartridge Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 103.43 (4-5/64), 171.68 (6-49/64)

1/2

2.77 (7/64)

2.77 (7/64)

2- and 4-pole 700-P Relay Approx Shipping Weight: AC – 0.68 kg (1.5 lb), DC – 1.34 kg (2.95 lb)

2- and 4-pole 700-P with Pneumatic Time Delay Attachment Approx Shipping Weight: AC – 0.85 kg (1.88 lb), DC – 1.5 kg (3.33 lb)

AC 136.75 (5-25/64) 171.68 (6-49/64)

2.77 (7/64)

2.77 (7/64)

6- and 8-pole 700-P Relay with one -PB adder deck Approx Shipping Weight: AC – 0.79 kg (1.75 lb), DC – 1.45 kg (3.20 lb)

700-P Relay with Mechanical Latch Attachment Approx Shipping Weight: AC – 0.97 kg (2.13 lb), DC – 1.62 kg (3.58 lb)

AC 136.75 (5-25/64)

Cat. No. 700

#8 Screws (Captive)

2.77 (7/64)

700-P Relay, up to 12 poles with -PB and -PC adder decks Approx Shipping Weight: AC – 1.02 kg (2.25 lb), DC – 1.68 kg (3.7 lb)

Relay Rail for 700-P, -N, -NM, -R, -RM, -RT, -RTA Relays Secure the mounting strip with two screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

165

Page 166

Relay and Timer Specifications

178.60 (7-1/32)

AC – 170.49 (6-23/32) DC – 187 (7-25/64)

700-PS Timer

Cat. No. 700-N31, Type 1 Enclosure for 700-P, -RTC Relays Approximate Shipping Weight: 1.26 kg (2.8 lb)

5.2 (13/64)

6.2 (15/64)

50 (1-63/64)

12.5 (1/2)

700-PS Timer Mounted on a 700-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb) without 700-PS, DC – 1.34 kg (2.9 lb) without 700-PS

1.0 (0.04) 3.98 (0.16)

35.0 (1.38)

1000 (39-3/8)

27.0 (1.06)

7.5 (0.3)

0.5 (.02)

2.25 (0.09) 0.5 (.02)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

166

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

DIN Rail Adapter

Page 167

Relay and Timer Specifications

700S-P and 700S-PK, Heavy-Duty Safety Control Relays • Mechanically linked contacts meet IEC 947-5-1-L • 2…12 poles – all mechanically linked • Red cover for easy identification of safety circuits • Tamper resistant cover helps prevent changes which could jeopardize safety • IEC mechanically linked contacts symbol displayed on front • Visual indication of contact state • Ideal for use in safety circuits

700S-P (10 A) Safety Control Relays, AC and DC Coil Voltages Contacts

AC Coils

24V DC Coils

Open Type Panel Mount Relay Rail Mount

Open Type Panel Mount Relay Rail Mount

Open Type DIN Rail Mount

N.O.

N.C.

3

1

700S-P310

700S-DCP310Z24

700S-DCP310DZ24

2

2

700S-P220

700S-DCP220Z24

700S-DCP220DZ24

7

1

700S-P710

700S-DCP710Z24

700S-DCP710DZ24

6

2

700S-P620

700S-DCP620Z24

700S-DCP620DZ24

5

3

700S-P530

700S-DCP530Z24

700S-DCP530DZ24

4

4

700S-P440

700S-DCP440Z24

700S-DCP440DZ24

3

5

700S-P350

700S-DCP350Z24

700S-DCP350DZ24

10

2

700S-P1020

700S-DCP1020Z24

700S-DCP1020DZ24

Cat. No.

Cat. No.

Cat. No.

⊗ AC Coil Voltage Code(1) The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 700S-P310 becomes Cat. No. 700S-P310A1 for a 120V AC coil. [V]

24

115-120

230-240

460-480

60 Hz

A24

A1

A2

A4

IEC 947-5-1 Annex L has 2 requirements for a relay to meet for mechanically linked contacts: 1.) If a N.O. contact welds, all the N.C. contacts will remain open and meet a 2500V impulse test. 2.) If a N.C. contact welds, all the N.O. contacts will remain open and meet a 2500V impulse test. 700S-P and 700S-DCP relays meet these requirements including the 2500V impulse test. The relays shown on this page are shipped from the factory with the 700-CPS safety cartridge installed and cannot be converted to N.O. or N.C. in the Field.

(1) For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

167

Page 168

Relay and Timer Specifications

700S-PK (20 A) Safety Control Relays Contacts N.O.

N.C.

7 6 5 4 3 10 3 7 6 5 4 3 10 3

1 2 3 4 5 2 1 1 2 3 4 5 2 1

168

Coil Voltage

Cat. No.

110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC

700S-PK710A1 700S-PK620A1 700S-PK530A1 700S-PK440A1 700S-PK350A1 700S-PK1020A1 700S-PK310A1 700S-DCPK710Z24 700S-DCPK620Z24 700S-DCPK530Z24 700S-DCPK440Z24 700S-DCPK350Z24 700S-DCPK1020Z24 700S-DCPK310Z24

Rockwell Automation Publication 700-TD552C-EN-P - October 2018