Page 187

Relay and Timer Specifications

IEC Control Relays Product Overview

Bulletin No.

700-CF and 700S-CF

700-K

Type

Control Relay

Miniature Control Relay

Features

• Mechanically linked contacts • Timer and latch operations • Switch up to 690V AC and DC • 700S-CF for safety circuits

• Smallest size • Long life • Low power consumption • Switch up to 690V AC and DC

Contact Form

4…12 poles, double break

4...8 Poles Double Break

Contact Type

Cross stamp or bifurcated

Bifurcated

Contact Material

Silver, gold

Silver

Max. Current AC Resistive

20 A (relay) 10 A (adder deck)

10 A

Min. load

17V, 10 mA (Silver) 5V, 3 mA (Gold)

15V, 2 mA (700-K)

Coil Voltage

12…600V AC 9…250V DC

12…600V AC 9…250V DC

Coil Voltage Pickup

85…110% AC coils, 80…110% DC coils

85…110% AC Coils, 80…110% DC Coils

Dielectric Withstand

2.5 kV

2640V

Electric Service Life (cycles)

1.2 million at 10 A

800K at 10 A 120V AC

Certifications

CE, cULus, CCC

CE, cULus, CCC

Sockets

DIN Rail or panel mount

DIN Rail or panel mount

Page

188

212

Electrical

Reference

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

187

Page 188

Relay and Timer Specifications

700-CF Control Relay • IEC industrial relays • Mechanically linked contact performance per IEC 60947-5-1 • Gold plated, bifurcated version for low level switching applications • Master control relay version rated 15 A (AC-15) • Solid-state and pneumatic timing modules • 4-…10 Poles

4-Pole AC Coil Voltage (Ratings for 700-CF Only) AC-12

AC-15

Ith [A] 40 °C

20

Contacts

Ie [A] 60 °C

24/48V

20

Gold Plated Bifurcated Contacts(2)

Master Contacts(2)

N.O. N.C. Cat. No.

Cat. No.

Cat. No.

2

2

700-CF220⊗

700-CFB220⊗

700-CFM220⊗

3

1

700-CF310⊗

700-CFB310⊗

700-CFM310⊗

4

0

700-CF400⊗

700-CFB400⊗

700-CFM400⊗

0

4

700-CF040⊗

700-CFB040⊗, Standard Contacts(1)

Connection Diagrams 120V

10

240V

10

10

400V

500V

6

2.5

600V

690V

1

1

(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.

⊗ AC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CF220⊗ becomes Cat. No. 700-CF220D for 120V, 60 Hz. [V]

12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

220... 230

230

230... 240

240

50 Hz

R

K

V

W

X

Y

KP, D

P

S

KG

L, - F, VA

T

60 Hz

Q

J, V, X, KP, D, - KG

H

L, - - A

50/60 Hz, KJ, - - KY

KP, KD, - KG

KL, - KL

KF, KA

[V]

277

347

380

380... 400

400

400... 415

440

480

500

550

600

50 Hz, - - N, G

B, M

C, 60 Hz

T

I

E, - - N

B, - C

50/60 Hz, - - - KN, KB, - - - 188

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 189

Relay and Timer Specifications

4-Pole DC Coil Voltage (Ratings for 700-CF Only) AC-12

AC-15 Connection Diagrams

Ie [A]

Ith[A] 40 °C

Contacts

60 °C

24/48V

120V

240V

400V

500V

600V

690V

Standard Contacts(1)

Gold Plated Bifurcated Contacts(2)

Master Contacts(2) Cat. No.

N.O.

N.C.

Cat. No.

Cat. No.

2

2

700-CF220

700-CFB220⊗ 700-CFM220⊗

⊗

20

20

10

10

10

6

2.5

1

1

3

1

700-CF310⊗ 700-CFB310⊗ 700-CFM310⊗

4

0

700-CF400⊗ 700-CFB400⊗ 700-CFM400⊗

(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.

⊗ DC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. example: Cat. No. 700-CF220⊗ becomes Cat. No. 700-CF220EJ for 24V DC, electronic with diode. [V]

9

12

24

36

48

48... 72

60

64

72

80

110

110... 115 125

125

220

220... 250

230

250

Electronic with diode, EQ

EJ

EW, EY, - - - - ED, - - EA, - Electronic with diode/ Quick Pick-up, - QJ, - - - - - - - - - - - - - - Rockwell Automation Publication 700-TD552C-EN-P - October 2018

189

Page 190

Relay and Timer Specifications

6- and 8-pole Relays Control Relays with Overlapping Side-Mounted Contacts AC-12

AC-15

Ith [A]

Ie [A] 40 60 24/ °C °C 48V

Main Relay

Side Contacts

190

20

10

20

10

10

6

Left Aux. 120 V

10

6

240 V

10

5

400 V

6

3

500 V

2.5

1.6

600 V

1

1

Relay Arrangement

Right Aux.

690 V

Contacts

Overlapping SideMounted Contacts

Cat. No.

N.O. N.C. N.O.

N.C.

4

0

1

1

700-CFZ1510⊗

3

1

1

1

700-CFZ1420⊗

2

2

1

1

700-CFZ1330⊗

4

0

2

2

700-CFZ2620⊗

3

1

2

2

700-CFZ2530⊗

2

2

2

2

700-CFZ2440⊗

1

1

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 191

Relay and Timer Specifications

Control Relays with Standard Side-mounted Contacts AC-12

AC-15

Ith [A]

Ie [A]

Left Aux.

40 60 24/ °C °C 48V

Main Relay

20

20

Side Contacts 10

10

Relay Arrangement

Contacts

Right Aux.

120V 240V 400V 500V 600V 690V

10

10

6

10

6

6

5

2.5

3

1

1.6

1

1

1

Standard SideMounted Contacts

Cat. No. (1)

N.O.

N.C. N.O.

N.C.

4

0

1

1

700CFZ0510⊗

3

1

1

1

700CFZ0420⊗

2

2

1

1

700CFZ0330⊗

4

0

2

2

700CFZ0620⊗

3

1

2

2

700CFZ0530⊗

2

2

2

2

700CFZ0440⊗

(1) All Cat. Nos. are factory stocked.

⊗ AC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CFZ051⊗ becomes Cat. No. 700-CFZ0510F. [V]

12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

220... 230

230

230... 240

240

50 Hz

R

K

V

W

X

Y

KP, D

P

S

KG

L, - F, VA

T

60 Hz

Q

J, V, X, KP, D, - KG

H

L, - - A

50/60 Hz, KJ, - - KY

KP, KD, - KG

KL, - KL

KF, KA

[V]

277

347

380

380... 400

400

400... 415

440

480

500

550

600

50 Hz, - - N, G

B, M

C, 60 Hz

T

I

E, - - N

B, - C

50/60 Hz, - - - KN, KB, - - - Rockwell Automation Publication 700-TD552C-EN-P - October 2018

191

Page 192

Relay and Timer Specifications

Assignment of Contacts Device Combinations in Accordance with IEC 60947-1 / -4-1 Auxiliary Contact Blocks Circuit Diagram

Control Relays 700-CF (AC and DC Control) Control

700-CF⊗220

700-CF⊗310

700-CF⊗400

AC/DC

22E + 02E = 24Y

31E + 02E = 33Y

40E + 02E = 42Y

AC/DC

22E + 11E = 33Y

31E + 11E = 42Y

40E + 11E = 51Y

AC/DC

22E + 20E = 42Y

31E + 20E = 51Y

40E + 20E = 60Y

AC/DC

22E + 22E = 44Y

31E + 22E = 53Y

40E + 22E = 62Y

AC/DC

22E + 31E = 53Y

31E + 31E = 62Y

40E + 31E = 71Y

AC/DC

22E + 40E = 62Y

31E + 40E = 71Y

40E + 40E = 80Y

AC/DC

22E + L22E = L44Y

31E + L22E = L53Y

40E + L22E = L62Y

Front Mounting (1) 51 61

100-FA02 52 62 53 61

100-FA11 54 62 53 63

100-FA20 54 64 53 61 71 83

100-FA22 54 62 72 84 53 61 73 83

100-FA31 54 62 74 84

100-FA40

53 63 73 83 54 64 74 84 53 61 75 87

100-FAL22 54 62 76 88

(1) Control relay and auxiliary contact block AC/DC max. 4 N. C.

192

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 193

Relay and Timer Specifications

Auxiliary Contacts Photo

Description

N.O.

Auxiliary Contact Blocks for Front Mounting§ 2- and 4-pole Quick and easy mounting without tools Electronic-compatible contacts down to 17V, 5 mA Mechanically linked performance between N.O. and N.C. poles and to the main relay poles (except for L types) Models with equal function with several terminal numbering choices 1L = Late break N.C./early make N.O. Bifurcated version for switching down to 5V, 3 mA

N.C.

Connection Diagrams

For Use With

Standard Contacts (1)

Bifurcated Contacts

Cat. No.

Cat. No.

0

2

100-FA02

100-FAB02

1

1

100-FA11

100-FAB11

2

0

100-FA20

100-FAB20

1L

1L

100-FAL11, 0

4

100-FA04

100-FAB04

1

3

100-FA13

100-FAB13

100-FA22

100-FAB22

700-CF

2

2

3

1

100-FA31

100-FAB31

4

0

100-FA40

100-FAB40

1+1L

1+1L

100-FAL22, (1) For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFA02.

Photo

Description

Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations§ 1- and 2-pole Two-way numbering for right or left mounting on the contactor Quick and easy mounting without tools Electronic-compatible contacts down to 17V, 10 mA Mirror contact performance to the main relay poles 1L = Late break N.C./early make N.O.

N.O.

N.C.

0

1

100-SA01

1

0

100-SA10

0

2

100-SA02

1

1

100-SA11

2

0

100-SA20

For Use With

Cat. No.

700-CF

1L

IMPORTANT

Connection Diagrams

1L

100-SAL11

For maximum number of contacts, see the following tables.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

193

Page 194

Relay and Timer Specifications

700-CF (AC electronic coils), vertical mounting, 60 °C(1) Cat. No. 700…

Max. N.O. Side Aux.

Max. N.C. Side Aux.

Max. N.O. Front Aux.

Max. N.C. Front Aux.

Max. N.O. Front + Side Aux.

Max. N.C. Front + Side Aux.

Max. N.O. + N.C. Front + Side Aux.

CF400 CF310 CF220 CF040

2 2 4 2

4 4 (2) 4 (2) 2

4 4 4 4

4 4(3) 2 0

6 6 8 6

7 5 5 2

8 8 8 6

(1) For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) With no front auxiliary contacts installed. Otherwise 3 N.C. Maximum (3) With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum

700-CF (DC conventional coils), vertical mounting, 60 °C(1) Cat. No. 700…

Max. N.O. Side Aux.

Max. N.C. Side Aux.

Max. N.O. Front Aux.

Max. N.C. Front Aux.

Max. N.O. Front + Side Aux.

Max. N.C. Front + Side Aux.

Max. N.O. + N.C. Front + Side Aux.

CF400 CF310 CF220

2 2 2

2 2 2

4 4 4

4 (2) 4 (2) 2

6 6 6

5 5 4

8 8 8

(1) For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum

194

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 195

Relay and Timer Specifications

Control Modules Photo

Description

Connection Diagrams

Pneumatic Timing Modules(1) ON-Delay Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.

Reset Time

Repeat Accuracy

25…90 ms for AC Coils +/-10%

Pneumatic Timing Modules OFF-Delay Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.

47…85 ms for DC coils

Delay

For Use With

0.3…30 s

100-FPTA30

1.8…180 s

100-FPTA180

0.3…30 s

700-CF all (1)

1.8…180 s

0.1…3 s 1…30 s

Electronic Timing Modules, On-Delay Delay of the control relay coil assembly. The control relay is energized at the end of the delay time.

10…180 s 100 ms

+/-1%

10…180 s 0.3…3 s 1…30 s 10…180 s 100 ms

+/-1%

700-CF 110…240V AC 110…250V DC conventional coils

10…180 s

100-ETA3 100-ETA30 100-ETA180 100-ETAZJ3

700-CF 24…48V DC coils

700-CF 110…240V AC coils

0.3…3 s 1…30 s

100-FPTB30

100-FPTB180

0.1…3 s 1…30 s

Electronic Timing Modules, Off-Delay Delay of the control relay coil assembly. After interruption of the control signal, the control relay is deenergized at the end of the delay time.

Cat. No.

100-ETAZJ30 100-ETAZJ180 100-ETB3 100-ETB30 100-ETB180 100-ETBKJ3

700-CF 24V AC coils

100-ETBKJ30 100-ETBKJ180

(1) On-Delay modules cannot be used with side-mounted auxiliary contacts on DC coil relays.

Photo

Connection Diagrams

Description

Mechanical Latch Following relay latching, the relay coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66). Electrical or manual release 1 N.O. + 1 N.C. auxiliary contacts

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

For Use With

Cat. No.

700-CF with AC coils

100-FL11⊗

195