For the Allen-Bradley 700S-CFB620EJC

Page 196

Relay and Timer Specifications

Photo

Connection Diagrams

Description

Cat. No. (1)

For Use With

24…48V 50/60 Hz RC Module AC Operating Mechanism

Surge Suppressors For limitation of coil switching transients. Plug-in, coil mounted

Varistor Module AC/DC Operating Mechanism

Diode Module DC Operating Mechanism Dropout Time 70…95 ms

100-FSC48

110…280V 50/60 Hz

700-CF with AC coils

100-FSC280

380…480V 50/60 Hz

100-FSC480

12…55V AC/ 12…77V DC

100-FSV55

56…136V AC/ 78…180V DC

100-FSV136

700-CF all

137…277V AC/ 181…350V DC

100-FSV277

278…575V AC

100-FSV575

12…250V DC

700-CF with Conventional DC 100-FSD250 coils

(1) For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFSC48.

Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 100-FL11⊗ becomes Cat. No. 100-FL11J. [V] (1)

24

48

100

110

120

230...240

240

277

380...400

400...415

440

480

50 Hz

K

Y

KP

D, VA

T, N

G

B, 60 Hz

J, - - D, A

T, - N

B

(1) For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Photo

Connection Diagrams

Description (Relays)

DC Interface (electronic) Interface between the DC control signal (PLC) and the AC operating mechanism of the control relay. Control (input) voltage 12V DC 24V DC 48V DC Requires no additional surge suppression on the relay coils

196

For Use With (Relays)

Input: 24V DC Output: 110…240V AC Input: 12V DC Output: 110…240V AC Input: 48V DC Output: 110…240V AC

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Cat. No.

100-JE

700-CF with 110…240V AC coils

100-JE12

100-JE48

Page 197

Relay and Timer Specifications

Specifications 100-J... DC Interfaces Cat. No. 100-JE

Cat. No. 100-JE12

Cat. No. 100-JE48

Electrical Input Voltage

24V DC

12V DC

48V DC

Input Voltage Range

18…30V DC

6…12V DC

35…48V DC

Output Voltage

110…240V AC

110…240V AC

110…240V AC

Power Consumption

0.1…0.4 W

0.02…0.12 W

0.2…0.5 W

Minimum Actuation

5V DC, 2 mA DC

5V DC, 2 mA DC

5V DC, 2 mA DC

IP20

IP20

IP20

Pickup Time

0…10 ms + pickup time of the contactor

0…10 ms + pickup time of the contactor

0…10 ms + pickup time of the contactor

Dropout Time

0…10 ms + dropout time of the contactor

0…10 ms + dropout time of the contactor

0…10 ms + dropout time of the contactor

2 (1)

2 (1)

2 (1)

In: 50V, Out: 250V

In: 50V, Out: 250V

In: 50V, Out: 250V

4 kV

4 kV

4 kV

Ambient Temperature Range

-25…+60 °C

-25…+60 °C

-25…+60 °C

Storage Temperature Range

-50…+80 °C

-50…+80 °C

-50…+80 °C

Operating Life

100 + million ops

100 + million ops

100 + million ops

1 Wire

0.5…2.5 mm2

0.5…2.5 mm2

0.5…2.5 mm2

2 Wire

0.75…2.5 mm2

0.75…2.5 mm2

0.75…2.5 mm2

1 Wire

1.0…2.5 mm2

1.0…2.5 mm2

1.0…2.5 mm2

2 Wire

1.0…2.5 mm2

1.0…2.5 mm2

1.0…2.5 mm2

18…14 AWG

18…14 AWG

18…14 AWG

1…1.5 N•m / 7…15 lb•in

1…1.5 N•m / 7…15 lb•in

1…1.5 N•m / 7…15 lb•in

LED

LED

LED

Mechanical Finger Protection

Max. Cycles Per Second Isolation/Breakdown Voltage Rated Impulse Withstand Voltage Environmental

Construction Flexible wire Wire Size Range

Solid wire Solid and Stranded

Tightening Torque Type of Light (1) To consider the maximum operations/hour of the relays.

Assembly Components Photo

Description

For Use With

Pkg Qty. (1)

Cat. No.

Protective Covers Provides protection against unintended manual operation

700-CF all

1

100-SCCA

Protective Covers • Provides protection against unintended manual operation • For contactors and front-mounted auxiliary contacts, pneumatic timers, and latches

100-FA, -FB, -FC, -FP, -FL; 10

100-SCFA

(1) All Cat. Nos. are factory stocked.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

197

Page 198

Relay and Timer Specifications

Accessories Uniform labeling materials for contactors, motor startup equipment, relays, and circuit breakers. Photo

Pkg. Qty. (1)

Cat. No.

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

10

100-FMS

Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover

10

100-FMP

Transparent Cover To be used with marking tag sheets

100

100-FMC

Marking Tag Adapters To be used with marking tag: System V4/V5

100

100-FMA1

Description

100-FMA2

System 1492 W (1) Must be ordered in multiples of package quantities.

198

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 199

Relay and Timer Specifications

Coils Photo

AC Coil Code Q R J K KJ V W X Y KY KP D KD P S KG H L KL A F KF VA T KA I E N KN G B KB M C

50Hz, 12V, 24V, 32V 36V 42V 48V, 100V 110V, 120V 127V 200V, 200 - 220V, 220V 220 - 230V, 230 - 240V 240V, - - 380 - 400V, 400-415V 440V, 500V 550V

AC Voltages 60Hz 12V, 24V, - 36V, 48V, - 100 - 110V 120V, - - 200 - 220V 208V 208 - 240V, 240V 260V, - 277V, 347V 380V 440V, - 480V, - 600V

50/60Hz, - - - 24V, - - - 48V 100V, 110V, - 200V, - 200 - 230V, - 230V, - 240V, - - 400V, - 440V, - Cat. No. 700-CF TA006 TA404 TA013 TA407 TA855 TA481 TA410 TA482 TA414 TA860 TA861 TA473 TA856 TA425 TA428 TA862 TA049 TA296 TA864 TA474 TA441 TA851 TA440 TA480 TA858 TA065 TA067 TA071 TA863 TA457 TA475 TA859 TA479 TA476

DC Coil Code

DC Voltages

EQ EJ QJ EY EW ED EA

12V 24 V 24V 48…72V 36…48 110…125 220…250

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Cat. No. 700-CF TC708E TC714E TC714Q TC724E TC719E TC733E TC747E

199

Page 200

Relay and Timer Specifications

Specifications - 700-CF..., 700S-CF Relays

Contact Ratings, NEMA Min. Contact Rating

Contact Ratings, IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1

40 °C AC-12 (Control of resistive loads) IEC 60947-5-1 60 °C

DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1

DC-13 IEC 60947-5-1, Solenoids and contactors

Mechanically Linked Contacts (1)

Main Relay Cat. Nos. 700-CF, 700S- CF

Front Mounted Standard Auxiliary Contacts

Main Relay Cat. No. 700-CFB, 700S- CFB

Master Relay Cat. No. 700-CFM

Front Mounted Bifurcated Auxiliary Contacts

Side-mounted Auxiliary Contacts

A600, P600

A600, Q600

A600, Q600

2 x A600, P600

A600, Q600

A600, Q600

17V, 10 mA

17V, 5 mA

8V, 5 mA, 5V, 3 mA

17V, 10 mA

24V

10 A

6A

3A

15 A

3A

6A

48V

10 A

6A

3A

15 A

3A

6A

120V

10 A

6A

3A

15 A

3A

6A

240V

10 A

5A

3A

15 A

3A

5A

400V

6A

3A

2A

7.5 A

2A

3A

480V/500V

2.5 A

1.6 A

1.2 A

5A

1.2 A

1.6 A

600V

1A

1A

0.7 A

2A

0.7 A

1A

690V

1A

1A

0.7 A

2A

0.7 A

1A

10 A

10 A

20 A

10 A

10 A

6A

6A

20 A

6A

6A

10 A

6A

20 A

6A

6A

Ith

20 A

230V

8 kW

400V

14 kW

690V

24 kW

Ith

20 A

230V

8 kW

400V

14 kW

690V

24 kW

24V

15 A

48V

10 A

9A

3.2 A

20 A

3.2 A

3.2 A

110V

6A

3.5 A

1A

8A

1A

1A

220V

1A

0.7 A

0.5 A

1.5 A

0.5 A

0.5 A

440V

0.4 A

0.2 A

0.2 A

0.4 A

0.2 A

0.2 A

24V

5A

5A

2.5 A

5A

2.5 A

5A

48V

3A

3A

1.5 A

3A

1.5 A

2.5 A

110V

1.2 A

1.2 A

0.6 A

1.2 A

0.6 A

0.68 A

220V

0.6 A

0.6 A

0.3 A

0.6 A

0.3 A

0.32 A

440V

0.3 A

0.15 A

0.15 A

0.3 A

0.15 A

0.15 A

State of N.C. Contacts if N.O. contact welds

Location of welded N.O. contacts

Main

Front aux.

Side aux.

Main

Open

Open

Open (2)

Front aux.

Open

Open, (1) Side mounted auxiliary contacts provide “mirror contact” performance with main poles only. (2) Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

200

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 201

Relay and Timer Specifications

Attribute

Aux./Pneumatic Timer Contact (Front mounted)

Cat. No. 700-CF

Mechanical Life

[Mil]

15

5

Electrical Life

AC-15 (240V, 3 A)

[Mil]

1.5

1.5

Weight

AC Coil

[g]

390, 2 x A4

2 x A4

1 Conductor

[mm2]

1.5…6

0.5…2.5

2 Conductor

[mm2]

1.5…6

0.75…2.5

Max. Wire Size per UL/CSA

[AWG]

16…10

18…14

Tightening Torque

[lb·in]

13.3…17.7

8.9…13.3

Tightening Torque

[N·m]

1.5…2.0

1…1.5

Terminal Cross-Sections Terminal Type Terminal Size per IEC60 947-1 Solid/Stranded (1)

(1) For 16 or more strands, end ferrule is required.

DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C) Attribute

1 pole

2 poles

3 poles

24/48V

15/10 A

25 A

25 A

125V

6A

25 A

25 A

220V

1A

6A

25 A

440V

0.4 A

1A

3A

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

201

Page 202

Relay and Timer Specifications

Control Circuit Attribute

Cat. No. 700-CF

Operating Voltage AC 50/60 Hz DC (conventional) (1)

DC (electronic EQ, EW)

DC (electronic EY)

DC (electronic ED)

DC (electronic EA)

Pickup

[x Us]

0.85…1.1

Dropout

[x Us]

0.3…0.6

Pickup

[x Us]

0.8…1.1

Dropout

[x Us]

0.1…0.6

Pickup

[x Us]

0.7...1.25

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.8...1.25

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.7...1.12 (2)

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.8...1.1

Dropout

[x Us]

0.3...0.4

Coil Consumption AC 50/60 Hz

DC (conventional)

DC (electronic EQ, EJ)

DC (electronic EY)

DC (electronic ED)

DC (electronic EA)

Inrush

[VA]

75

Sealed

[VA/W]

9.5/2.7

Inrush

[W]

7.7

Sealed

[W]

6.3

Inrush (avg./ peak)

[W]

10/17

Sealed

[W]

1.7

Inrush (avg./ peak)

[W]

10/17

Sealed

[W]

1.9

Inrush (avg./ peak)

[W]

12/19

Sealed

[W]

2.1

Inrush (avg./ peak)

[W]

14/22

Sealed

[W]

3.0

Pickup Time

[ms]

15…30

Dropout Time

[ms]

10…60

Operating Times AC 50/60 Hz

Pickup Time

[ms]

40…70

Dropout Time

[ms]

7…15

With integrated diode

Opening Delay

[ms]

14...20

With external diode

Opening Delay

[ms]

70...125

Closing Delay

[ms]

25…50

Opening Delay

[ms]

27...45

Closing Delay

[ms]

25...50

Opening Delay

[ms]

23...33

Closing Delay

[ms]

20...50

Opening Delay

[ms]

15…22

DC (conventional)

DC (electronic- EQ, EJ)

DC (electronic - EW EY, ED, EA)

DC (electronic- QJ)

202

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 203

Relay and Timer Specifications

Attribute

Cat. No. 700-CF

Min OFF time

[ms]

Max. ripple

50 ± 15%

Latch Attachment Release, 100-FL Coil Consumption

AC

[VA/W]

45/40

DC

[W]

25

[min./max]

0.03…15 s at min. time setting

[ms]

10 at max. time setting

[ms]

70

Contact Signal Duration Timing Attachment Reset Time, 100- ETA, 100-ETB Repeat Accuracy

± 10%

(1) For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us. (2) At 110V DC, coil code ED has an operating voltage range of 0.7...1.25 x Us.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

203

Page 204

Relay and Timer Specifications

General Specifications - 700-CF Relays Cat. No. 700-CF Rated Insulation Voltage Ui IEC UL; CSA

690V 600V 6 kV 2500V

Rated Impulse Strength Uimp

High Test Voltage 1 minute (per IEC 60947Rated Voltage Ue AC DC

115, 230, 400, 500, 690V 24, 48, 110, 220, 440V Short-Circuit Protection gG Fuse 20 A 50/60 Hz, DC

Rated Frequency

Ambient Temperature Storage Operation at nominal current 15% current reduction for AC-12 at > 60 °C

–55…+80 °C (–67…+176 °F) –25…+60 °C (–13…+140 °F) –25…+70 °C (–13…+158 °F) humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles 2000 m above mean sea level, per IEC 60 947-4

Corrosion Resistance Altitude

Type of Protection IP2X (IEC 60529 and DIN 40050) Shock Resistance Vibration Resistance Standards Compliance

Certifications in connected state IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions) IEC 60068-2: Static >2 G, in normal position no malfunction <5 G UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EUcULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified

Utilization Category Table from EN 60947-5-1 Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories (1) Normal Condition of Use Number and Rate of Making and Breaking Break (3) Make (3) Utilization operations Category No. Operating ON time [s] U/Ue cos φ I/Ie U/Ue cos φ operating I/Ie cycles per (6) (5) cycles minute AC-12 (2) 1 1 0.9 1 1 0.9 6050 6 0.05 AC-13 (2) 2 1 0.65 1 1 0.65 6050 6 0.05 (2) AC-14 6 1 0.3 1 1 0.3 6050 6 0.05 10 1 0.3 1 1 0.3 6050 6 0.05 AC-15 (2), - T0.95, - - DC, - T0.95 DC-12 1 1 1 ms 1 1 1 ms 6050 6 0.05 (6) DC-13 1 1 6 x P (4) 1 1 6 x P (4) 6050 6 0.05 (6) (2) DC-14 10 1 15 ms 1 1 15 ms 6050, 0.05 (6) (1) See sub-clause 8.3.3.5.2. (2) Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s. (3) For tolerances on test quantities, see sub-clause 8.3.2.2. (4) The value ”6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P = 300 W. (5) The first 50 operating cycles shall be run at U/Ue = 1.1 with the loads set at Ue. (6) The ON time shall be at least equal to T0.95. Ie Rated operational current, I Current to be made or broken Ue Rated operational voltage, U Voltage before make PUeIe Steady-state power consumption (W) T0.95 Time to reach 95% of the steady-state current (ms)

204

Rockwell Automation Publication 700-TD552C-EN-P - October 2018