The text of a spec sheet · part 23 of 27
Relay and Timer Specifications, Bulletin Number 700: IEC Control Relays, pages 214 to 219
Pages 214 to 219 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 214
Relay and Timer Specifications
Auxiliary Contact Blocks Photo
Description
Connection Diagrams
For Use With
Pkg. Qty.
Screw Type Terminals
Spring Clamp Terminals
Cat. No.
Cat. No.
(1)
N.O.
N.C.
0
2
100/104-K, 700-K
1
100-KFA02E
100-KRFA02E
1
1
100/104-K, 700-K
1
100-KFA11E
100-KRFA11E
2
0
100/104-K, 700-K
1
100-KFA20E
100-KRFA20E
0
4
100/104-K, 700-K
1
100-KFA04E
100-KRFA04E
1
3
100/104-K, 700-K
1
100-KFA13E
100-KRFA13E
2
2
100/104-K, 700-K
1
100-KFA22Z
100-KRFA22Z
3
1
100/104-K, 700-K
1
100-KFA31Z
100-KRFA31Z
4
0
100/104-K, 700-K
1
100-KFA40E
100-KRFA40E
51 61 52 62 53 61 54 62 53 63 54 64
Front-mounted auxiliary contacts
• Auxiliary Contact Blocks • 2- and 4-pole versions • Choice of contact configurations • Snap on, no tools required • Electronic-compatible bifurcated contacts for signals down to 15V / 2 mA
51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84
(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.
Control Modules Description
Photo
Connection Diagrams
For Use With
Pkg. Qty.
Cat. No.
1
100-KMCH
1 (1)
100-KFSC50
(1)
100-KFSC280
1 (1)
100-KFSC480
1 (1)
100-KFSV55
1 (1)
100-KFSV136
1 (1)
100-KFSV277
1 (1)
100-KFSD250
Mechanical Interlock
• For interlocking of two adjacent contactors • No added width to contactor assembly • Front mount plug-in type • Optional auxiliary contact blocks and suppressor modules mount onto the interlock 24…48V AC RC Suppressor
110…280V AC 380…480V AC
100/104-K/KR, 700-K/- KR
12…55V AC, 12…77V DC
Surge Suppressor
• Plug-in type • Limits surge voltage on coil drop-off
100/104-K/KR, 700-K/- KR
MOV Suppressor
56…136V AC, 78…180V DC
100/104-K/KR, 700-K/- KR
137…277V AC, 181…250V DC Diode Suppressor
12…250V DC
(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.
214
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
100/104-K/KR, 700-K/- KR
1
Page 215
Relay and Timer Specifications
Accessories Photo
Description
Pkg. Qty.
Cat. No.
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
10
100-FMS
Snap-In Marker Card
5
1492-M6X12
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
215
Page 216
Relay and Timer Specifications
IEC Specifications - 700-K... Relays 700-K
700-KR
AC-12 Rated Thermal Current Ambient temperature 40°C
Ith
24…240V
[A]
10
230…500V
[A]
10
230…690V
[A]
10
24…240V
[A]
6
230…500V
[A]
6
230…690V
[A]
6
24V
[A]
3
48V
[A]
3
120V
[A]
3
230V
[A]
2
240V
[A]
2
400V
[A]
1.2
480V
[A]
1
Ambient temperature 60°C
Ith
AC-15/B600 Switching of Solenoids and contactors
Ie
500V
[A]
1
600V
[A]
0.6
690V
[A]
0.6
Fuse gG
[A]
10
[mA]
2
Main current circuit resistance, 1 pole
[mΩ]
6.5
Power dissipation, 4 poles
[W]
2.6
AC control, warm
[W]
4.4
DC control, warm
[W]
5.2
Mechanical
[Mio. op.]
15
Electrical AC-15 (240V / 2 A)
[Mio. op.]
0.7
AC control kg (lbs.)
0.16 (0.35)
DC control kg (lbs.)
0.2 (0.44)
Short-circuit Protection
Min. Switching Capacity 15V
Resistance and Power Dissipation
Total power dissipation
Lifespan
Weight
Load Carrying Capacity per UL/CSA
Rated voltage
AC
[V]
Continuous rating
40 °C
[A]
Switching capacity
AC
[A]
B 600
Rated voltage
DC
[V] max. 600
Switching capacity
DC
[A]
Q 600
216 max. 600 10
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
6
Page 217
Relay and Timer Specifications
700-K DC-13/Q600
1 pole
24V
[A]
2.3
48V
[A]
1
110V
[A]
0.55
125V
[A]
0.55
220V
[A]
0.27
250V
[A]
0.27
400V
[A]
0.15
440V
[A]
0.15
600V
[A]
0.1
Cross Sections Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals
700-K
700-KR (1)
Terminal type
Fine stranded with ferrule
(1) Conductor (2) Conductors
[mm2]
Solid or coarse stranded
(1) Conductor (2) Conductors
[mm2]
0.75…2.5 0.75…2.5
0.50…2.5 0.50…2.5
[mm2]
1…4 1…2.5 + 1…4
0.75…2.5 (3) 0.75…2.5 (3)
[Nm]
1.2, Cross section per UL/CSA
[AWG]
18…12 (2)
18…14 (3)
Recommended torque
[lb-in]
10.6, Recommended torque
[mm2]
(1) Pozidriv No. 2 / Blade No. 3 screw (2) Use same cross sections (3) Stranded wire only
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
217
Page 218
Relay and Timer Specifications
Coil Data 700-K Operating Limits pick-up
[x Us]
0.85…1.1 dropout
[x Us]
0.2…0.75 pick-up
[x Us]
0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 dropout
[x Us]
0.1…0.75 pick-up
[VA/W]
35/32 hold-in
[VA/W]
5/1.8 pick-up
[W] cold 3.0, warm 2.6 hold-in
[W] cold 3.0, warm 2.6 closing delay
[ms]
15…40 opening delay
[ms]
15…33 opening delay
[ms]
15…28 closing delay
[ms]
18…40 opening delay
[ms]
6…12
With integrated diode closing delay
[ms]
8…12
With external diode opening delay
[ms]
35…50
AC control 50 Hz, 60 Hz, 50/60 Hz
DC control Coil Consumption
AC control 50 Hz, 60 Hz, 50/60 Hz DC control Operating Times
AC With RC module DC
Dimensions - 700-K... Relays Approximate dimensions are shown in millimeters. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.
(mm)
12 35 45
4
35.2
*)
*) -Minimum distance to grounded parts or walls
49 79
218
180°
54
56
50
25° 25°
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 219
Relay and Timer Specifications
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
219