The text of a spec sheet · part 23 of 27

Relay and Timer Specifications, Bulletin Number 700: IEC Control Relays, pages 214 to 219

Pages 214 to 219 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 214

Relay and Timer Specifications

Auxiliary Contact Blocks Photo

Description

Connection Diagrams

For Use With

Pkg. Qty.

Screw Type Terminals

Spring Clamp Terminals

Cat. No.

Cat. No.

(1)

N.O.

N.C.

0

2

100/104-K, 700-K

1

100-KFA02E

100-KRFA02E

1

1

100/104-K, 700-K

1

100-KFA11E

100-KRFA11E

2

0

100/104-K, 700-K

1

100-KFA20E

100-KRFA20E

0

4

100/104-K, 700-K

1

100-KFA04E

100-KRFA04E

1

3

100/104-K, 700-K

1

100-KFA13E

100-KRFA13E

2

2

100/104-K, 700-K

1

100-KFA22Z

100-KRFA22Z

3

1

100/104-K, 700-K

1

100-KFA31Z

100-KRFA31Z

4

0

100/104-K, 700-K

1

100-KFA40E

100-KRFA40E

51 61 52 62 53 61 54 62 53 63 54 64

Front-mounted auxiliary contacts

• Auxiliary Contact Blocks • 2- and 4-pole versions • Choice of contact configurations • Snap on, no tools required • Electronic-compatible bifurcated contacts for signals down to 15V / 2 mA

51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.

Control Modules Description

Photo

Connection Diagrams

For Use With

Pkg. Qty.

Cat. No.

1

100-KMCH

1 (1)

100-KFSC50

(1)

100-KFSC280

1 (1)

100-KFSC480

1 (1)

100-KFSV55

1 (1)

100-KFSV136

1 (1)

100-KFSV277

1 (1)

100-KFSD250

Mechanical Interlock

• For interlocking of two adjacent contactors • No added width to contactor assembly • Front mount plug-in type • Optional auxiliary contact blocks and suppressor modules mount onto the interlock 24…48V AC RC Suppressor

110…280V AC 380…480V AC

100/104-K/KR, 700-K/- KR

12…55V AC, 12…77V DC

Surge Suppressor

• Plug-in type • Limits surge voltage on coil drop-off

100/104-K/KR, 700-K/- KR

MOV Suppressor

56…136V AC, 78…180V DC

100/104-K/KR, 700-K/- KR

137…277V AC, 181…250V DC Diode Suppressor

12…250V DC

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

214

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

100/104-K/KR, 700-K/- KR

1

Page 215

Relay and Timer Specifications

Accessories Photo

Description

Pkg. Qty.

Cat. No.

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

10

100-FMS

Snap-In Marker Card

5

1492-M6X12

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

215

Page 216

Relay and Timer Specifications

IEC Specifications - 700-K... Relays 700-K

700-KR

AC-12 Rated Thermal Current Ambient temperature 40°C

Ith

24…240V

[A]

10

230…500V

[A]

10

230…690V

[A]

10

24…240V

[A]

6

230…500V

[A]

6

230…690V

[A]

6

24V

[A]

3

48V

[A]

3

120V

[A]

3

230V

[A]

2

240V

[A]

2

400V

[A]

1.2

480V

[A]

1

Ambient temperature 60°C

Ith

AC-15/B600 Switching of Solenoids and contactors

Ie

500V

[A]

1

600V

[A]

0.6

690V

[A]

0.6

Fuse gG

[A]

10

[mA]

2

Main current circuit resistance, 1 pole

[mΩ]

6.5

Power dissipation, 4 poles

[W]

2.6

AC control, warm

[W]

4.4

DC control, warm

[W]

5.2

Mechanical

[Mio. op.]

15

Electrical AC-15 (240V / 2 A)

[Mio. op.]

0.7

AC control kg (lbs.)

0.16 (0.35)

DC control kg (lbs.)

0.2 (0.44)

Short-circuit Protection

Min. Switching Capacity 15V

Resistance and Power Dissipation

Total power dissipation

Lifespan

Weight

Load Carrying Capacity per UL/CSA

Rated voltage

AC

[V]

Continuous rating

40 °C

[A]

Switching capacity

AC

[A]

B 600

Rated voltage

DC

[V] max. 600

Switching capacity

DC

[A]

Q 600

216 max. 600 10

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

6

Page 217

Relay and Timer Specifications

700-K DC-13/Q600

1 pole

24V

[A]

2.3

48V

[A]

1

110V

[A]

0.55

125V

[A]

0.55

220V

[A]

0.27

250V

[A]

0.27

400V

[A]

0.15

440V

[A]

0.15

600V

[A]

0.1

Cross Sections Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals

700-K

700-KR (1)

Terminal type

Fine stranded with ferrule

(1) Conductor (2) Conductors

[mm2]

Solid or coarse stranded

(1) Conductor (2) Conductors

[mm2]

0.75…2.5 0.75…2.5

0.50…2.5 0.50…2.5

[mm2]

1…4 1…2.5 + 1…4

0.75…2.5 (3) 0.75…2.5 (3)

[Nm]

1.2, Cross section per UL/CSA

[AWG]

18…12 (2)

18…14 (3)

Recommended torque

[lb-in]

10.6, Recommended torque

[mm2]

(1) Pozidriv No. 2 / Blade No. 3 screw (2) Use same cross sections (3) Stranded wire only

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

217

Page 218

Relay and Timer Specifications

Coil Data 700-K Operating Limits pick-up

[x Us]

0.85…1.1 dropout

[x Us]

0.2…0.75 pick-up

[x Us]

0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 dropout

[x Us]

0.1…0.75 pick-up

[VA/W]

35/32 hold-in

[VA/W]

5/1.8 pick-up

[W] cold 3.0, warm 2.6 hold-in

[W] cold 3.0, warm 2.6 closing delay

[ms]

15…40 opening delay

[ms]

15…33 opening delay

[ms]

15…28 closing delay

[ms]

18…40 opening delay

[ms]

6…12

With integrated diode closing delay

[ms]

8…12

With external diode opening delay

[ms]

35…50

AC control 50 Hz, 60 Hz, 50/60 Hz

DC control Coil Consumption

AC control 50 Hz, 60 Hz, 50/60 Hz DC control Operating Times

AC With RC module DC

Dimensions - 700-K... Relays Approximate dimensions are shown in millimeters. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

(mm)

12 35 45

4

35.2

*)

*) -Minimum distance to grounded parts or walls

49 79

218

180°

54

56

50

25° 25°

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 219

Relay and Timer Specifications

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

219