The text of a spec sheet · part 5 of 27
Relay and Timer Specifications, Bulletin Number 700: General Purpose Relays, pages 39 to 48
Pages 39 to 48 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 39
Relay and Timer Specifications
700-HC Miniature Ice Cube Relay • 7 or 10 A contact ratings • 2PDT or 4PDT • Standard ON/OFF flag indicator • Blade-style terminals • Choice of standard silver nickel contacts, or silver nickel with gold-plated contacts for low-energy applications • Options: LED, push-to-test with manual override option • Tungsten UL Approvals
Photo
•
4-Pole: 5A @ 24V DC
•
2-Pole: 10A @ 24V DC Wiring Diagrams
Contact Rating
2PDT 2-Pole 2 Form C Contacts: 10 A = AgNi Contacts
U.S./Canada
10 A C300 R300 Low energy rating; (10V, 10 mA) 100 mW
7A = AgNiAu Gold Plated Contacts
Cat. No.
12V DC
700-HC22Z12
24V DC
700-HC22Z24
24V AC
700-HC22A24
120V AC
700-HC22A1
240V AC
700-HC22A2
6V AC
700-HC14A06
12V AC
700-HC14A12
24V AC
700-HC14A24
120V AC
700-HC14A1
240V AC
700-HC14A2
6V DC
700-HC14Z06
12V DC
700-HC14Z12
24V DC
700-HC14Z24
48V DC
700-HC14Z48
110V DC
700-HC14Z1
6V AC
700-HC24A06
12V AC
700-HC24A12
24V AC
700-HC24A24
120V AC
700-HC24A1
240V AC
700-HC24A2
6V DC
700-HC24Z06
12V DC
700-HC24Z12
24V DC
700-HC24Z24
700-HN103
48V DC
700-HC24Z48
700-HN104
110V DC
700-HC24Z1
Input
700-HN128
4PDT 4-Pole 4 Form C Contacts:
Coil Voltage
International
700-HN103 700-HN104
7A Low energy rating; (5V, 10 mA or 25V, 2 mA) 50 mW
Input
4PDT 4-Pole 4 Form C Contacts: 7A = AgNi Silver Contacts
7A C300 R300 Low energy rating; (10V, 10 mA) 100 mW
700-HN128
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
39
Page 40
Relay and Timer Specifications
Accessories - 700-HC Relays Photo
Description
Pkg. Qty.
Cat. No.
Diode with LED Surge Suppressor Voltage Range: 6…24V DC used with 700-HN104 socket
10
700-ADL1
Diode with LED Surge Suppressor Voltage Range: 28…60V DC used with 700-HN104 socket
10
700-ADL2
Diode with LED Surge Suppressor Voltage Range: 110…220V DC used with 700-HN104 socket
10
700-ADL3
Varistor with LED Surge Suppressor Voltage Range: 6…24V AC used with 700-HN104 socket
10
700-AV1R
Varistor with LED Surge Suppressor Voltage Range: 110…240V AC used with 700-HN104 socket
10
700-AV3R
RC Surge Suppressor Voltage Range: 6…24V AC/DC used with 700-HN104 socket
10
700-AR1
RC Surge Suppressor Voltage Range: 110…240V AC/DC used with 700-HN104 socket
10
700-AR2
Timing Module On-Delay or One-Shot selectable voltage range: 12…24V AC/DC used with sockets that accept plug-in accessory modules. Timing Module On-Delay or One-Shot selectable voltage range: 110…125V AC used with sockets that accept plug-in accessory modules.
700-AT3
1
Timing Module On-Delay or One-Shot selectable voltage range: 230…240V AC used with sockets that accept plug-in accessory modules.
40
700-AT3A1
700-AT3A2
Screw Terminal Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction.Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.
10
700-HN103
Screw Terminal Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-HC relays. This socket has coil and contact separation as well as the ability to plug in optional plug in modules (700-A__ accessories: LED, Surge Suppression, Timing Modules)
10
700-HN104
Screw Terminal Base Socket, Panel or DIN Rail Mounting; Open-Style Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-HC Relays.
10
700-HN128
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 41
Relay and Timer Specifications
Photo
Description
Pkg. Qty.
Cat. No.
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays. Secures relay in socket.(1)
10
700-HN114
Plastic Retainer and Ejection Lever For use with the 700-HN104 Sockets for 700-HC relays. Built-in ability to accept 1492 Snap-in Markers
10
700-HN124
(1) See 700-HC Miniature Square Base Relay, Socket, and Retainer Clip Reference Chart
Description
Photo
Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. Squares slip into molded slot on top of product cover.
Pkg. Qty. Cat. No. 5
1492-MS5X12
5
1492-MS6X9
5
1492-MS6X12
5
1492-MS8X9
5
1492-MS8X12
100
1492-MP-Blank
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Markers, Used for terminal identification
50
700-N41
Socket and Retainer Clip Reference Relay Type
700-HC
Socket Cat. No.
Retainer Clip Cat. No.
700-HN103
700-HN114
700-HN128
700-HN114
700-HN104
700-HN114 or 700-HN124
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
41
Page 42
Relay and Timer Specifications
Specifications- 700-HC Relays Attribute
700-HC Electrical Ratings
Pilot Duty Rating
(1)
NEMA C300, R300
Rated Thermal Current (Ith)
7 A and 10 A
Rated Insulation Voltage (Ui)
250V IEC – 300V UL/CSA 700-HC_4
Hp
700-HC22
Hp
Inductive 120V AC
15 A
1.5 A
1/8
15 A
1.5 A
1/3
240V AC
7.5 A
0.75 A
1/3
7.5 A
0.75 A
3/4
Contacts General-purpose
7 A, 277V AC
10 A, 277V AC
Resistive
7 A, 30V DC
10 A, 24V DC 100 mW (10V, 10 mA) - Silver Contacts 50 mW (5V, 10 mA, or 25V, 2 mA) - Gold Contacts
Min. Low Energy Permissible Load
Permissible Coil Voltage Variation
Pickup:
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
Must Dropout Voltage:
50 Hz Coil Consumption ±10%
AC Coils
20% of nom voltage at AC 10% of nom voltage at DC 60 Hz
Inrush
2.2VA
1.6VA
Sealed
1.3VA
1.1VA
DC Coils
1.0 W 20% of VA (AC)
Max. Allowable Leakage
10% of W (DC) Design Specification/Test Requirements Electrical Dielectric Withstand Voltage
Pole-to-Pole
2000V
Contact to Coil
2000V
Electrical Life (Cycles)
100 000 min Mechanical
Degree of Protection (Open Type) IEC 529
IP 20 (Guarded Terminal Sockets)
Mechanical lifecycles
20 x 106 (AC), 50 x 106 (DC)
Switching Frequency Operations
1800/HR
Coil Voltages Operating Time (ms)
See Product Selection Pickup
10
Dropout
3
Maximum Operating Rate
8 cycles/s Environmental
Temperature Altitude Insulating Material Enclosure Contact Material
Operating
–30…+55 °C (–22…+131 °F)
Storage
–55…+85 °C (–67…+185 °F) 2000 m (6560 ft) Molded High Dielectric Material Transparent Dust Cover AgNi (700-HC2), AgNi + 5 μm All (700-HC1)
Terminal Markings on Socket
In accordance with EN50 0005
Sockets
700-HN103, -HN128, -HN104
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), cULus Listed when used with 700- HN103, -HN104, and -HN128 sockets (File No. E14843, Guide NRNT/NRNT7), CE Marked, LR Certified
Standards
UL 508, CSA 22.2 No. 14, EN 61810-1
(1) See General Information on page 3
42
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 43
Relay and Timer Specifications
Dimensions, 700-HC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
37.2 (1.46)
36.7 (1.44)
5.6 (0.22)
6.1 (0.24) 20.7 (0.82)
27.7 (1.09)
20.7 (0.82)
27.7 (1.09)
700-HC Relay (Two-Pole)
700-HC Relay (Four-Pole) 27.0 (1.06)
60.9 (2.40) 21.5 (0.85)
76.0 (2.99)
35.6 (1.40) 3.2 (0.13) 18.9 (0.74) 34.9 (1.37)
32.0 (1.26) 35.5 (1.40) 2.5 (0.10)
Cat. No. 700-HN104
Single Wire: 0.2 mm2…2.5 mm2 (24 AWG…14 AWG), Double Wire: 0.2 …2.5 mm2 (24 AWG…14 AWG), Qty. 2 wires Wire Type: solid or stranded, copper only, Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
30.0 (1-3/16) 6.1 (15/64)
Panel Mounting
24.5 (31/32)
28.9 (1-9/64)
8
7
6
5
4
3
2
1
67.0 (2-5/8)
4.2 (5/32)
14 12
#4-40 M3
30.0 (1-11/64)
24.9 (57/64) 21.1 (53/64)
13 11
10
62.0 (2-15/64)
65.0 (2-9/16)
9
26.0 (1-1/64)
Cat. No. 700-HN103
Cat. No. 700-HN128
Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…14 AWG) Double Wire: 0.2…2 x 1.5 mm2 (24 AWG…16 AWG), Qty. 2 wires Wire Type: Solid or Stranded, Copper only Strip Length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)
Wire Size: 2 x 1.5 mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Toque: 0.8 N•m (7 lb•in
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
43
Page 44
Relay and Timer Specifications
700-HK Slim Line Relay • 8 A/16 A contact ratings • DPDT/SPDT • Plug-in blade-style terminals • Retainer clip with sockets • Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or timer module • Standard ON/OFF flag indicator • Relay faceplate accepts optional 1492 snap-in markers • Choice of standard silver/nickel contacts or silver/nickel with gold plated contacts • Maximum duty version available Photo
Description
SPDT 1-Pole 1 Form C AgNi Contacts
Contact Rating
Wiring Diagrams U.S./Canada
International
16 A
Input
700-HN121, 700-HN221, 700-HN223
Socket
DPDT 2-Pole 2 Form C AgNi Contacts
700-HN121, 700-HN221, 700-HN223
8A
Input
Socket
44
700-HN122, 700-HN222, 700-HN224
700-HN122, 700-HN222, 700-HN224
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Coil Voltage
Cat. No.
6V AC
700-HK36A06
12V AC
700-HK36A12
24V AC
700-HK36A24
120V AC
700-HK36A1
240V AC
700-HK36A2
6V DC
700-HK36Z06
12V DC
700-HK36Z12
24V DC
700-HK36Z24
48V DC
700-HK36Z48
110V DC
700-HK36Z1
6V AC
700-HK32A06
12V AC
700-HK32A12
24V AC
700-HK32A24
120V AC
700-HK32A1
240V AC
700-HK32A2
6V DC
700-HK32Z06
12V DC
700-HK32Z12
24V DC
700-HK32Z24
48V DC
700-HK32Z48
110V DC
700-HK32Z1
Page 45
Relay and Timer Specifications
Accessories- 700-HK Relays Photo
Description
Pkg. Qty.
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1-pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.
10
700-HN121
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 16 A rating for use with 1-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.
10
700-HN221
Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket for use with 1-pole, 700-HK relays.
10
700-HN223
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 5 A rating for use with 2-pole, 700-HK relays. Accepts forked lug conductors. This socket includes a retainer clip.
10
700-HN122
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 8 A rating for use with 2-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.
10
700-HN222
Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole 700-HK relays.
10
700-HN224
Flange Mount Adapter Used for panel-mounting bulletin 700-HK relays. Order must be for 10 adapters or multiples of 10.
10
700-HN226
35 mm Rail Mount Adapter Mounts bulletin 700-HK relays to a 35 mm rail. Order must be for 10 adapters or multiples of 10.
10
700-HN227
Socket Retainer Clip and Ejection Lever For use with 700-HN22, -HN222, -HN223, and -HN224 sockets. Orders must be for 10 clips or multiples of 10.
10
700-HN229
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
45
Page 46
Relay and Timer Specifications
Specifications- 700-HK Relays Attribute
700-HK Electrical Ratings
Rated Thermal Current (Ith)
1-Pole, 1 CO, SPDT, 16 A
2-Pole, 2 CO, DPDT, 8 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA 120V AC
AC-15, 6.2 A B300 Pilot Duty, 3 A A300 (700-HKM_) 1/3 Hp (0.24 kW) 1-phase
120V AC
AC-15, 2.9 A B300 Pilot Duty, 3.0 A 1/4 Hp (0.18 kW), 1-phase
240V AC
AC-15, 3.1 A B300 Pilot Duty, 1.5 A A300(700-HKM_) 3/4 Hp (0.55 kW), 1-phase
240V AC
AC-15, 1.4 A B300 Pilot Duty, 1.5 A 1/2 Hp (0.37 kW), 1-phase
230V AC
0.55 kW, 1-phase
230V AC
0.37 kW, 1-phase
24V DC
DC-13, 5.0 A
24V DC
DC-13, 3.0 A
125V DC
DC-13, 0.2 A / R300 Pilot Duty, 0.22 A
125V DC
DC-13, 0.2 A / R300 Pilot Duty, 0.22 A
250V DC
DC-13, 0.1 A / R300 Pilot Duty, 0.11 A
5 A, 250V AC
DC-13, 0.1 A / R300 Pilot Duty, 0.11 A
230V AC
AC-1, 16 A
230V AC
AC-1, 8 A
277V AC
16 A, General Use
277V AC
8 A, General Use
30V DC
DC-1, 12 A / 10 A, Resistive
30V DC
DC-1, 6 A / 6 A, Resistive
Inductive V AC
Contacts Inductive V DC
Resistive Make, Break , and Continuous Min. Permissible Contact Ratings
Permissible Coil Voltage Variation
Pickup: holding Voltage: Must Dropout Voltage:
300 mW (5V/60 mA or 60V/5 mA) for AgNi Contacts (700-HK3_) 50 mW (5V/10 mA or 25V/2 mA) for AgNi + Gold Contacts (700-HKX_) 500 mW (100V/5 mA or 5V/100 mA) for AgSnO2 Contacts (700-HKM_) 80…110% of Nominal Voltage at 50/60 Hz, 73...110% of Nominal Voltage at DC 80% of Nominal V AC at 50/60 Hz, 40% of Nominal V DC 20% of Nominal V AC at 50/60 Hz, 10% Nominal V DC
Power Consumption
1.2V A (V AC Coils), 0.5 W (V DC Coils)
Coil Voltages
See Overview/Product Selection Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole to Pole (VRMS) Contact to Coil (VRMS)
2000V AC 4000V AC Mechanical
Degree of Protection
IP 20 (guarded terminal sockets), RT II, Flux-proof (Relay) 10 x 106
Mechanical Life Operations 230V AC, 16 A Resistive: 100 000 min. 277V AC, 16 A Resistive: 30 000 min. 30V DC, 10 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min. A300 (700-HKM_): 100,000 min.
Electrical Lifecycles
Mechanical: 18,000 cycles/hr. Electrical: 900 cycles/hr.
Switching Frequency Operating Time at Nominal Voltage at 20 °C (ms)
230V AC, 8 A Resistive: 100 000 min. 277V AC, 8 A Resistive: 30 000 min. 30V DC, 6 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min.
Pickup
15 ms
Dropout
5 ms
Vibration
Operational Non-Operational
10…2000 Hz, 0.76 mm (0.03 in.) 2.5 G 10…2000 Hz, 0.76 mm (0.03 in.) 5.0 G
Shock
Operational Non-Operational
15 G 50 G Environmental
Temperature
Operating Storage
–40…+70 °C (–40…+158 °F) –40…+85 °C (–40…+185 °F)
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket
46
Molded High Dielectric Material Transparent Dust Cover 700-HK3_: Silver nickel (AgNi); 700-HKX_: Silver Nickel + Gold Plating (AgNi + Au); 700-HKM_: Silver Tin Oxide(AgSnO2) In accordance with EN 50005
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 47
Relay and Timer Specifications
Attribute
700-HK
Sockets
1-Pole
2-Pole
Screw Terminal
700-HN121 (10 A @ 70 °C) 700-HN221 (16 A @ 50 °C, 12 A @ 70 °C)
700-HN122 (2 x 5 A @ 70 °C) 700-HN222 (2 x 8 A @ 70 °C)
Spring Clamp
700-HN223 (15 A @ 40 °C with 2 conductors per terminal) (10 A @ 70 °C with 1 conductor per terminal)
700-HN224 (2 x 8 A@ 70 °C)
Approvals Certifications
CSA Certified, File 75088, UL Recognized, File E3125 Guide NLDX2/NLCX8, cULus Listed with Allen-Bradley sockets (File No. 3125 Guide NLDX/NLDX7), CE Marked
Standards
EN61810-1, CSA 22.2 No. 14, UL 508
Dimensions- 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 12.4 (1/2)
12.4 (1/2)
29.0 (1-9/64)
32.8 (1-19/64)
29.0 (1-9/64)
32.8 (1-19/64)
30.1 (1-3/16)
6.5 (1/4)
6.5 (1/4)
2.5 (3/32) 4.75 (3/16) A1 5
0.5 (1/32) COM 11 4
A2 NC 22 NO 24 1 5 7 COM 21 6
NC 12 NO 14 2 3 Cat. No. 700-HK36_ (SPDT) NO 14 4
NC 12 2
0.5 (1/32)
COM 11 3 NO 14 A1 NC 12 4 2 8
A2 1
COM 11 3
30.1 (1-3/16)
Cat. No. 700-HK32_ (DPDT) COM 11 NO 14 NC 12 3 4 2
A1 8
A1 8 15.8 (5/8)
15.8 (5/8) COM 21 6
NO 24 5
NC 22 7 Cat. No. 700-HN224
A2 1
COM 21 NO 24 NC 22 6 5 7
A2 1 Cat. No. 700-HN222
COM 11 4
NO 14 3
NC 12 2
A1 5
COM 11 NO 14 NC 12 4 3 2
A1 5
15.8 (5/8)
15.8 (5/8)
A2 1
A2 1 Cat. No. 700-HN221
Cat. No. 700-HN223
64.9 (2-9/16)
44.7 (1-3/4)
32.5 22.6 (1-9/32) (57/64)
35.3 (1-25/64)
34.7 (1-3/8) 95.6 (3-49/64)
35.4 (1-13/32) 82.85 (3-17/64)
Cat. No. 700-HN223, 700-HN224 Wire Size: 0.2 mm2...1.5 mm2 (#24 AWG....#14 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in)
Cat. No. 700-HN221, 700-HN222 Wire Size: 0.2 mm2...2.5 mm2 (#24 AWG....#12 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in), Torque: 0.8Nm (7.0 lb.-in.)
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
47
Page 48
Relay and Timer Specifications
Dimensions - 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 46.0 (1-13/16) 14.4 (37/64)
3.6 (9/64)
14.4 (37/64)
38.0 (1-1/2)
46.9 (1-27/32)
42.4 (1-43/64)
36.6 (1-11/16)
39.8 (1-37/64)
18.1 (23/32)
2.0 (5/64)
34.8 (1-3/8) Cat. No. 700-HN227
Cat. No. 700-HN226
6.2 (15/64)
50 (1-63/64)
1.0 (0.04)
12.5 (1/2)
27.0 (1.06)
35.0 (1.38)
5.2 (13/64)
7.5 (0.30)
1000 (39-3/8) Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes Cat. No. 199-DR1 DIN Mounting Rail Series B
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
Cat. No.