The text of a spec sheet · part 4 of 27
Relay and Timer Specifications, Bulletin Number 700: General Purpose Relays, pages 29 to 38
Pages 29 to 38 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 29
Relay and Timer Specifications
Specifications - 700-HD Relays Attribute
700-HD Electrical Ratings
Pilot Duty Rating
(1)
NEMA B300
Rated Thermal Current (Ith)
15 A(2) – 120V 15 A (2) – 240V,
Rated Insulation Voltage (Ui)
250V IEC-300V UL/CSA
Inductive
Contacts
Make
Hp
Break 2-Pole
3-Pole
2-Pole
3-Pole
120V AC
60 A
30 A
6A
3A
3/4
240V AC
30 A
15 A
3A
1.5 A
2
General-purpose
15 A, 240V AC
Resistive
15 A, 30V DC
Min. Low Energy Permissible Load
1000 mW (10V, 10 mA)
Permissible Coil Voltage Variation
80…110% of Nominal Voltage at 50 Hz 80…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Coil Consumption ±10%
AC Coils
50 Hz
60 Hz
Inrush
3.3VA
2.85VA
Sealed
2.2VA
1.9VA
DC Coils
1.3 W
Maximum Contact Resistance
50 MΩ 20% of Nominal V AC 10% of Nominal V DC
Must Dropout Voltage
Design Specification/Test Requirements Electrical Dielectric Withstand Voltage
Pole-to-Pole
2500V
Contact to Coil
4000V Mechanical
Degree of Protection (Open Type) IEC 529
IP 40
Mechanical lifecycles (AC/DC)
See Overview/Product Selection
Switching Frequency Operations
3600/HR > 10 x 106 / 30 x 106
Coil Voltages Operating Time
Pickup
20 ms
Dropout
4 ms
Maximum Operating Rate
4 Ops/s
Minimum Low Energy Permissible Load
1000 mN (10V, 10 mA) Environmental
Temperature Altitude
Operating
–40…+70 °C
Storage
–40…+100 °C 2000 m (6560 ft)
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
29
Page 30
Relay and Timer Specifications
Attribute
700-HD Construction
Insulating Material
Molded High Dielectric Material
Enclosure
Transparent Dust Cover
Contact Material
Silver Cad. Ox.
Terminal Markings
In accordance with EN50 0005
Certifications cURs Recognized (File No. E3125, Guide NLDX2/NLDX8), CSA Certified (File No. 229473), CE Marked, UR Certified
Standards
UL 508, CSA C22.2 No. 14, EN 61810-1
Cycles
Maximum Switching Current (A)
(1) See NEMA Ratings and Test Values on page 5 (2) 3-pole relays have a 20 A maximum total current rating for all three poles.
Voltage DC (V)
Load (kVA)
Contact life versus AC1 load at 600 cycles/h.
Breaking capacity for DC1 load at 600 cycles/h.
Reduction Factor
Load applied to one contact. A = for N.O. types B = other types
(Highly Resistive)
COS φ
(Inductive)
Load Reduction factor versus cos φ
30
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 31
Relay and Timer Specifications
Dimensions - 700-HD Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 35.9 (1.41)
63 (2.48)
68 (2.67)
38.2 (1.50) 700-HD Relay
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
31
Page 32
Relay and Timer Specifications
700-HF Square Base Relay • 12 A contact rating • DPDT, 4PDT • Plug-in quick connect/solder terminals • Options: LED, push-to-test manual override operator
Photo
Description
DPDT 2-pole 2 Form C AgCdO Contacts
Contact Rating
Wiring Diagrams U.S./Canada
International
12 A
700-HN116 700-HN262
Socket
700-HN116 700-HN262
4PDT 4-pole 4 Form C AgCdO Contact 12 A
Socket
700-HN139 700-HN264
700-HN139 700-HN264
(1) Pilot Light Option: Add suffix (-4) to the selected 700-HF Relay Cat. No. except for the 240V AC units, add (-4L). Manual Operator and LED Option: Add suffix (-3-4) to the selected 700-HF Relay Cat. No., except for the 240V AC units, add (-3-4L).
32
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Coil Voltage
Cat. No.(1)
6V AC
700-HF32A06
12V AC
700-HF32A12
24V AC
700-HF32A24
120V AC
700-HF32A1
240V AC
700-HF32A2
6V DC
700-HF32Z06
12V DC
700-HF32Z12
24V DC
700-HF32Z24
48V DC
700-HF32Z48
110V DC
700-HF32Z1
6V AC
700-HF34A06
12V AC
700-HF34A12
24V AC
700-HF34A24
120V AC
700-HF34A1
240V AC
700-HF34A2
6V DC
700-HF34Z06
12V DC
700-HF34Z12
24V DC
700-HF34Z24
48V DC
700-HF34Z48
110V DC
700-HF34Z1
Page 33
Relay and Timer Specifications
Accessories - 700-HF Relays Photo
Description
Pkg. Qty. Cat. No.
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with DPDT HF relays.
10
700-HN116
Screw Terminal Socket, Panel or DIN Rail Mounting, Guarded Terminal Construction 8-blade socket for use with DPDT 700-HF relays. The socket has the ability to use optional plug-in modules (Cat. No. 700-A_ _ accessories, LED, surge suppression, timing modules).
10
700-HN262
Screw Terminal Socket, Panel or DIN Rail Mounting, Guarded Terminal Construction 14-blade socket for use with 4PDT 700-HF relays.
10
700-HN139
Screw Terminal Socket, Panel or DIN Rail Mounting, Guarded Terminal Construction 14-blade socket for use with 4PDT 700-HF relays. The socket has coil and contact separation and the ability to use optional plug-in modules (Cat. No. 700-A_ _ accessories, LED, surge suppression, timing modules).
10
700-HN264
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays and Cat. Nos. 700-HN116, 700-HN262 Sockets with 700-HF DPDT Relays§ Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700-HN114
Retainer Clip for Cat. Nos. 700-HN139 and -HN264 Sockets with 700-HF 4PDT Relays§ Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700-HN266
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
33
Page 34
Relay and Timer Specifications
Accessories - 700-HF Relays Photo
Description
Pkg. Qty. Cat. No.
Diode with LED Surge Suppressor Voltage Range: 6…24V DC used with sockets that accept plug-in accessory modules.
10
700-ADL1
Diode with LED Surge Suppressor Voltage Range: 28…60V DC used with sockets that accept plug-in accessory modules.
10
700-ADL2
Diode with LED Surge Suppressor Voltage Range: 110…220V DC used with sockets that accept plug-in accessory modules.
10
700-ADL3
Varistor with LED Surge Suppressor Voltage Range: 6…24V AC used with sockets that accept plug-in accessory modules.
10
700-AV1R
Varistor with LED Surge Suppressor Voltage Range: 110…240V AC used with sockets that accept plug-in accessory modules.
10
700-AV3R
RC Surge Suppressor Voltage Range: 6…24V AC/DC used with sockets that accept plug-in accessory modules.
10
700-AR1
RC Surge Suppressor Voltage Range: 110…240V AC/DC used with sockets that accept plug-in accessory modules.
10
700-AR2
Timing Module On-Delay or One-Shot selectable voltage range: 12…24V AC/DC used with sockets that accept plug-in accessory modules.
700-AT3
Timing Module On-Delay or One-Shot selectable voltage range: 110…125V AC used with sockets that accept plug-in accessory modules.
700-AT3A1 1
Timing Module On-Delay or One-Shot selectable voltage range: 230…240V AC used with sockets that accept plug-in accessory modules.
Socket, and Retainer Clip Reference Relay Type
Cat. No. Socket
Cat. No. Retainer Clip
700-HF32
700-HN116 700-HN262
700-HN114
700-HF34
700-HN139 700-HN264
700-HN266
34
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
700-AT3A2
Page 35
Relay and Timer Specifications
Specifications- 700-HF Relays Electrical Ratings
700-HF 2 Pole
700-HF 4 Pole AC 15 @ 700 VA
Inductive V AC
230V AC
AC-1 @ 3000 VA 1 Hp @ 240V AC
120V AC
1/2 Hp @ 120V AC
DC-1
0.5 A @ 110V DC
AC
12 A @ 250 V AC (per pole)
DC
12 A @ 30 V DC (per pole)
Contacts
12 A @ 30V DC VDC
0.25 A @ 220V DC Resistive Operating Range
AC
80...110% nom voltage
DC Rated Power Holding Voltage Must Drop Out Voltage
80...110% nom voltage
85...110% nom voltage
AC (50 Hz)
1.5 VA
2 VA
DC
1W
1.3 W
AC
80% nom voltage
DC
60% nom voltage
AC
20% nom voltage
DC
10% nom voltage
Insulation Voltage
250V AC Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole
2500V AC
Contact to Pole
2500V AC
Mechanical Degree of Protection
Open Type (Sockets) 20 x 106
Mechanical Life Operations Switching Frequency Operations
3600/hr
Coil Voltages Operating Time at nom voltage at 20 °C
See Product Selection Pickup
8 ms
10 ms
Dropout
3 ms
4 ms
Maximum Operating Rate
4 Ops/s
Vibration
15 G
Shock
15 G Environmental
Temperature
Operating
–40…+70 °C (–40…+268 °F)
Storage
–50…+80 °C (–89…+176 °F)
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Molded High-Dielectric Material Transparent Dust Cover Silver Cad. Oxide In accordance with EN50 0005 8-Blade Socket (DPDT) Cat. No. 700-HN116 & 700-HN262, 14-Blade Socket (4PDT) Cat. No. 700-HN139 & 700-HN264
Certifications
CSA Certified (File No. 229473), UL Recognized (File No. E3125, Guide NLDX2/NLDX8), CE Marked, UL Listed when used with sockets shown above, (File No. E3125, Guide NLDX/NLDX 7), LR Certified, RINA Certified, IMQ Certified
Standards
UL 508, CSA 22.2 No. 14, EN-61810-1
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
35
Page 36
Relay and Timer Specifications
Dimensions -700-HF Relays Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
700-HF Relay (DPDT)
700-HF (4PDT)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
36
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 37
Relay and Timer Specifications
Dimensions - 700-HF Relays Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 700-HN116 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2.5 mm2 (14 … 20 AWG), Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb·in)
Cat. No. 700-HN262 Wire Size: Solid - 1x6/ 2 x 2.5 mm2 1x10 / 2 x 14 AWG Stranded - 1x4 / 2x2.5 mm2 1x12 / 2x14 AWG Length: 9 mm (3/8 in.) - Torque: 0.8 N∙m (7 lb. ∙ in.) 300V AC, 12 A, 50 °C
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
37
Page 38
Relay and Timer Specifications
Cat. No. 700-HN139 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2.5 mm2 (14 … 20 AWG), Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb·in)
Cat. No. 700-HN264 Wire Size: Solid - 1x6/ 2 x 2.5 mm2 1x10 / 2x14 AWG Stranded - 1x4 / 2x2.5 mm2 1x12 / 2x14 AWG Length: 9 mm (3/8 in.) - Torque: 0.8 N∙m (7 lb. ∙ in.) 300V AC, 10 A, 70 °C
38
Rockwell Automation Publication 700-TD552C-EN-P - October 2018