Page 49
Relay and Timer Specifications
7.11 (9/32)
11 4 14 3
Five M3.5 x 0.315 Screws 4.06 (5/32)
12 2 3.0 Ø (1) (1/8) Use M3 Screws
84.1 (3-5/16) 5 (+) (A1)
39.5 (1-17/32) 35.5 (1-13/32)
1 (-) (A2)
4.06 (5/32) 15.6 (5/8)
29.9 (1-3/16)
7.11 (9/32)
21 6
2.03 (5/64) 22 7 24 5
Eight M3.5 x 0.315 Screws 12 2 14 4 3.0 Ø (1) (1/8) Use M3 Screws
84.1 (3-5/16) 8 (+) (A1) 4.06 (5/32)
1 (-) (A2) 15.6 (5/8)
54.1 (2-1/8)
Cat. No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
2.03 (5/64)
11 3
4.06 (5/32) 39.5 (1-17/32) 35.5 (1-13/32)
29.9 (1-3/16) 54.1 (2-1/8)
Cat. No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
49
Page 50
Relay and Timer Specifications
700-HL Terminal Block Relay • Relay and socket assembled interface modules for high density interposing or isolation applications • Screw terminal and spring-clamp bases • 6 A relay, choice of silver or gold contacts • 2 A solid-state relay, DC output • 2 A solid-state relay, AC output • SPDT (relay), 1 N.O. (solid-state) • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules • Unique leakage current suppression version to address industry concerns of nuisance coil turn-on or contact non-drop out when connecting to PLCs with leakage current • Available with hazardous location certification Standard built-in Features: • LED • Reverse Polarity Protection for DC Inputs • Coil Surge Protection(1) Cat. No. 700-HLT1Z24
Cat. No. 700-HLT2Z24
Cat. No. 700-HLS1Z24
Cat. No. 700-HLS11Z24
(3)
Specifications
Output Type
SPDT (1 C/O); Ith = 6A(2)
Recommended Tightening Torque
0.5 N• m max. (4.4 lb• in)
Wire Range
Screw Terminal: 0.14 mm2…2.5 mm2 (#26…#14 AWG), Spring Terminal: 0.2 mm2…2.5 mm2 (#24…#14 AWG)
Approvals
UL, cULus, cURus, ABS, CE
1 N.O. solid-state; Ith = 2 A, 24V DC or Ith = 2 A, 240V AC
(1) Diode surge protection provided. (2) For Gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-HLT1Z24 is required with gold plating, the new cat. no. is 700-HLT1Z24X. (3) Reverse polarity on the output terminals of the solid-state relay will result in the output being "ON" regardless of the state of the input voltage.
Input Voltage
Pkg. Qty.
Cat. No. Cat. No. (Spring Clamp (Screw Terminals) Terminals)
Cat. No. Pkg. Quantity (Screw Terminals) (DC Output)
Cat. No. (Spring Clamp Terminals) (DC Output)
Cat. No. (Screw Terminals) (AC Output)
12V DC
10
(2), - - - 10
(2)
10
(2)
700-HLS1Z24
700-HLS2Z24
700-HLS11Z24
48V DC
10
(2)
700-HLT2Z48
10
(2)
700-HLS1Z48
700-HLS2Z48
700-HLS11Z48
12V AC/DC
10
700-HLT1U12
700-HLT2U12, - - - 24V AC/DC
10
700-HLT1U24
700-HLT2U24, - - - 48V AC/DC
10
700-HLT1U48
700-HLT2U48, - - - 10
(2)
700-HLS1U1
700-HLS2U1
700-HLS11U1
700-HLS1U2
700-HLS2U2
700-HLS11U2, - 24V DC
110/125V AC/DC
10
700-HLT1Z12 700-HLT1Z24 700-HLT1Z48
700-HLT1U1
700-HLT2Z12 700-HLT2Z24
700-HLT2U1
220…240V AC/DC
10
700-HLT1U2
700-HLT2U2
10
(2)
240V AC
10
700-HLT1A2, - - 50
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 51
Relay and Timer Specifications
Cat. No. (Spring Clamp Terminals) (DC Output)
Cat. No. (Screw Terminals) (AC Output)
700-HLS1L1, 700-HLS11L1
700-HLS1L2, 700-HLS11L2
10
700-HLS1Z24-EX, - - 10, - - - 10
700-HLS1U1-EX, - Pkg. Quantity
Socket Input Voltage
Cat. No.
12V AC/DC
700-TBR12
24V AC/DC
700-TBR24
48V AC/DC
700-TBR48
110/125V AC/DC 220…240V AC/DC
700-TBR60
Input Voltage
Pkg. Qty.
Cat. No. Cat. No. (Spring Clamp (Screw Terminals) Terminals)
Cat. No. Pkg. Quantity (Screw Terminals) (DC Output)
Built-in LCSC (leakage current suppression circuit) 120V AC and 125V DC(1)
10
(2)
700-HLT1L1, 10
(2)
Built-in LCSC (leakage current suppression circuit) 240V AC (1)
10
(2)
700-HLT1L2, 10
(2)
Hazardous Location Certification 24V DC
10
700-HLT1Z24-EX, Hazardous Location Certification 12V DC
10
700-HLT1Z12-EX
Hazardous Location Certification 110/125V AC/DC
10
700-HLT1U1-EX
(1) Leakage current suppression up to 2.2 mA off state current. (2) Electromechanical relay to solid-state relay interchangeability is possible.
Accessories - 700-HLT, -HLS Relays Photo
Description
Replacement Relays(1) Order must be for 20 relays or multiples of 20.
20
Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR DC output. Order multiples of 20.
24V DC
700-TBS24
20
48V DC, 110/125V AC/DC 220…240V AC/DC
700-TBS60
Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. Order multiples of 20.
20
24V DC
700-TBS124
Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. Order must be for 20 relays or multiples of 20.
20
48V DC 110/125V AC/DC 220…240V AC/DC
700-TBS160
Color 20-Way Jumper Can be cut to required length. Ith = 36 A max per 20-way jumper.
1
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Red
700-TBJ20R
Grey
700-TBJ20G
Blue
700-TBJ20B
51
Page 52
Relay and Timer Specifications
Photo
Description
Pkg. Quantity
Socket Input Voltage
Cat. No.
End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.
10
Black
700-HN177
100
Blank
1492-MC6X10
Snap-in Marker These snap-in markers have a 6 x 10 mm surface and snap into the ejection lever for the relay. For custom markers, contact your local Rockwell Automation sales office or Allen-Bradley distributor for more information.
(1) For gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X
Dimensions - 700-HL Relays
700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG )Wire Type: Solid or stranded, copper only.Strip Length: 9 mm (11/32
Cat. No. 199-DR1 DIN Mounting Rail Series B, Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Specifications - 700-HLT Relays Cat. No. 700-HLT… (Relay Output) Electrical Ratings Pilot Duty Rating
B 300, R 300
Rated Thermal Current (Ith)
1-Pole, 6 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive
Contacts
24V AC, 1-phase
30 A
5A
120V AC, 1-phase
30 A
3A
240V AC, 1-phase
15 A
Make, Break and Continuous V DC
1.0 A
120V DC
0.2 A
240V DC
0.1 A
12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts
Min. Permissible Contact Ratings
52
1.5 A 24V DC
AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O., and N.C. Contact
Inductive Load
Permissible Coil Voltage Variation
1-Pole
Pickup:
85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Must Dropout Voltage:
10% of Nominal Voltage at AC 5% of Nominal Voltage at DC
Page 53
Relay and Timer Specifications
Cat. No. 700-HLT… (Relay Output) Power Consumption ±10%
AC DC
0.3VA 0.2 W Design Specification / Test Requirements
Dielectric Withstand Voltage Input Voltage
Pole to Pole (VRMS)
1000V
Contact to Coil (VRMS)
4000V
12V AC/DC
24V AC/DC
48V AC/DC
120V AC/DC
240V AC/DC
120V LCSC
240V LCSC
1K
2K
6K
26 K
56 K
16 K
35 K
Impedance (Ohms)
Mechanical Degree of Protection
IP20
Mechanical Life Operations
1 x 107
Electrical Life Operations
6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.
Switching Frequency Operations (no-load)
10 cycles/sec
Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)
See Overview/Product Selection Pickup
7 ms
Dropout
3 ms
Maximum Operating Rate (full load = 6 A)
6 cycles/min. Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode
Coil Surge Protection
Environmental Temperature
Operating
–40…+55 °C
Storage
–40…100 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High Dielectric Material
Enclosure
Relay IP67
Contact Material
Silver Tin Ox, AgSnO2 or Silver with Gold Plating, AgSnO2 + Au
Terminal Markings on Socket
In accordance with EN50 0005
Certifications cULus Listed (File No. E3125, E14843 Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked, ABS (American Bureau of Shipping)
Standards
EN 61810-1, CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C
Hazardous Location Approvals
UL Listed (UL 60079-15)
700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
CSA Certified (1) (CAN/CSA E60079-15)
700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
Cat. No. 700-HLS… (Solid-state Output) Electrical Rated Thermal Current (Ith)
2 A (DC output)
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
2 A (AC output)
53
Page 54
Relay and Timer Specifications
Cat. No. 700-HLS… (Solid-state Output)
Control Circuit
Min. Control Voltage
80% nominal voltage
Maximum Control Voltage
110% nominal voltage
Control Current
9 mA ±10% (24V) 4 mA ±10% (120/240V)
Release Voltage
0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)
Min. Control Circuit Resistance Load Voltage Range
Outputs
2500 ohms (24V), 12k ohms (120V), 24k ohms (240V)
0…24V DC
24…240V AC
Max. Repetitive Blocking Voltage
33V
600V
Max. Switching Current (inductive/ resistive)
2 A DC
1 A AC
<120 mV DC
<1V AC
On State Voltage Drop @ Max. Switching Current
Power Consumption ±10%
3200 ohms (24V), 16k ohms (120V), 32k ohms (240V)
Leakage Current max. 100 μA (@U = 24V)
AC
0.6VA(120V), 1VA(240V)
DC
0.2 W
0.3 W
Design Specification/Test Requirements Dielectric Withstand Voltage
Pole to Pole (VRMS)
2500V
Contact to Coil (VRMS)
2500V
Input Voltage
24V DC
48V DC
120V AC/DC
240V AC/DC
120V LCSC
240V LCSC
Impedance (Ohms)
2K
9K
26 K
58 K
16 K
35 K
Mechanical Degree of Protection
IP20
Input Voltages Operating Time at Nominal Voltage at 20 °C (ms)
See Overview/Product Selection Turn on Time
30 μs (DC only input voltage), 7 ms (AC/DC input voltage)
Drop Out Time
350 μs (DC only input voltage), 10 ms (AC/DC input voltage)
Maximum Operating Rate
300 Hz Environmental
Temperature
Operating
–20…+55 °C
Storage
–40…70 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High-Dielectric Material
Enclosure
Relay IP67
Terminal Markings on Socket
In accordance with EN50 0005
Certifications cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)
Standards
UL 508, CSA C22.2 No. 14, EN 61810-1 Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C
Hazardous Location Approvals
UL Listed (UL 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
CSA Certified (1) (CAN/CSA 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
54
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 55
Relay and Timer Specifications
Dimensions - 700-HLT, -HLS Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
76.0 (2.99)
88.0 (3.46)
76.0 (2.99)
93.0 (3.66)
6.2 (0.24)
6.2 (0.24)
700-HLT / -HLS Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.)
700-HLT / -HLS Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…#14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x #16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)
Dimensions - 700-HLT, -HLS Relay Accessories 6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
Pkg. Qty.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb)
10/pkg
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb)
5/pkg
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
55
Page 56
Relay and Timer Specifications
700-HL 2-pole Terminal Block Relay • Relay and socket assembled interface modules for high density interposing or isolation applications • Screw terminal and spring-clamp bases • 10 A relay, choice of silver or gold contacts • DPDT (relay) • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules
Output Type
DPDT (2 C/O); Ith = 10 A
Recommended Tightening Torque
0.6 N•m max. (5.3 lb•in.)
Wire Range
Screw Terminal: 0.2…2.5 mm2 (#24…14 AWG), Spring Terminal: 0.2…2.5 mm2 (#24…14 AWG)
Approvals cULus, cURus, CE
Input Voltages
Pkg. Quantity
Cat. No.(1) (Screw Terminals)
Cat. No.(Spring Clamp Terminals)
12V DC
10
700-HLT12Z12
700-HLT22Z12
24V DC
10
700-HLT12Z24
700-HLT22Z24
48V DC
10
700-HLT12Z48
700-HLT22Z48
24V AC/DC
10
700-HLT12U24
700-HLT22U24
110/125V AC/DC
10
700-HLT12U1
700-HLT22U1
220…240V AC/DC
10
700-HLT12U2
700-HLT22U2
(1)
For Gold-plated contacts: Add the letter "X" at the end of the catalog number. Example: Cat. No. 700-HLT12Z24 with gold plated contacts is Cat. No. 700-HLT12Z24X. The following relays are available with the gold-plated contact option: 700-HLT_2Z24, 700-HLT_2U24, 700-HLT_2U1, and 700-HLT_2U2. Not available on 12V and 48V DC products.
Accessories - 700-HL Relays (2- pole) Photo
Description
Replacement Relays Order must be for 20 relays or multiples of 20.
Pkg. Qty.
20
Socket Input Voltage/Color
Cat. No.
12V DC
700-TBR212
24V AC/DC
700-TBR224
48V DC
700-TBR248
110/125V AC/DC, 220…240V AC/DC
700-TBR2110
Red
700-TBJ08R
Grey
700-TBJ08G
Blue
700-TBJ08B
8-Way Jumper Can be cut to required length. Ith = 10 A max per 8-way jumper.
1
End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.
10
Black
700-HN177
Snap-in Marker(1) These snap-in markers have a 6 x 12 mm surface and snap into the ejection lever for the relay.
100
Blank
1492-MS6X12
(1) For custom markers, contact your local Rockwell Automation sales office or Allen-Bradley distributor for more information.
56
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 57
Relay and Timer Specifications
Specifications - 700-HL Relays (2-Pole) Cat. No. 700-HLT…2-Pole (Relay Output) Electrical Ratings
Pilot Duty Rating
B 300, R 300
Rated Thermal Current (Ith)
2-Pole, 10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA
Inductive V AC UL
Contacts
Inductive V DC
Resistive Make, Break, and Continuous
120V AC
AC-15, 3.0A B 300, 3.0 A
1/4 HP (186 W), 1-phase
240V AC
AC-15, 3.0 A B 300, 1.5 A
1/2 HP (373 W), 1-phase
24V DC
DC-13, 2.0 A
125V DC
DC-13, 0.3 A
250V DC
DC-13, 0.2 A
250V AC
10 A
24V DC
10 A
250V DC
0.28 A
Min. Permissible Contact Ratings
12V, 10 mA (120 mW) for Silver Contacts, 5V, 1 mA (50 mW) for Gold Contacts
Permissible Coil Voltage Variation
85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Pickup:
Must Dropout Voltage:
10% of Nominal Voltage at AC 5% of Nominal Voltage at DC
Design Specification/Test Requirements
Dielectric Withstand Voltage
Input Voltage
1000V
Contact to Coil (VRMS)
5000V
Adjacent Contacts (VRMS)
2500V
12V AC/DC
24V AC/DC
48V DC
120V AC/DC
240V AC/DC
1K
2K
3K
34 K
72 K
AC
N/A
0.5V A
N/A
0.4V A
0.8V A
DC
0.4 W
0.5 W
0.8 W
0.5 W
0.7 W
Impedance (Ohms) Power Consumption ±10%
Pole to Pole (VRMS)
Mechanical
Degree of Protection
IP20
Mechanical Life Operations
3 x 107
Electrical Life Operations
250V AC/24V DC, 8 A Resistive: 100 000 min. 24V DC, 10 A Resistive: 6000 min. 250V DC, 0.28 A Resistive: 6000 min. 250V AC, 10 A Resistive: 30 000 min.
Switching Frequency Operations (no-load)
1200 cycles/sec
Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms) Maximum Operating Rate (full load = 6 A)
See Overview/Product Selection Pickup typical 10 ms
Dropout typical 10 ms 6 cycles/min.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
57
Page 58
Relay and Timer Specifications
Cat. No. 700-HLT…2-Pole (Relay Output) Environmental
Temperature
Operating
–40…+60 °C
Storage
–40…+100 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High-Dielectric Material
Enclosure
Relay RT II, flux-proof, pollution degree 2 installation environment
Contact Material
AgNi 90/10 or AgNi 90/10 + Au
Terminal Markings on Socket
In accordance with EN50 0005
Certifications cULus Listed (File No. E3125, Guide NRNT/NRNT7), CE Marked
Standards
UL 508, CSA C22.2 No. 14, EN 61810-1
Dimensions - 700-HL (2-pole) Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 92.8 (3.65)
87.7 (3.45)
14 (0.55)
14 (0.55)
75 (2.95)
75 (2.95)
Bulletin 700-HL Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)
Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in)
97.8 (3.85)
Bulletin 700-TBJ08_ 8-Way Jumper
58
Rockwell Automation Publication 700-TD552C-EN-P - October 2018