Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 8 of 27

Relay and Timer Specifications, Bulletin Number 700: General Purpose Relays, pages 69 to 78

Pages 69 to 78 of 250, from Relay and Timer Specifications, Bulletin Number 700

The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CFB620EJC

Page 69

Relay and Timer Specifications

Dimensions - 700-HP Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

29.0 (1.14)

12.4 (0.49)

25.0 (0.98)

700-HP Relay

5.2 (13/64)

12.5 (1/2)

6.2 (15/64)

50 (1-63/64)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

69

Page 70

Relay and Timer Specifications

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

21 6

11 3

24 5

14 4

22 7

12 2

17.5 (0.69)

60.9 (2.40) 17.5 (0.69)

Ø 3.2 (0.12) Use M3 Screws

78.6 (3.09)

8 (+) A1

1 (-) A2

4.0 (0.16) 15.8 (0.62)

Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

70

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

21.6 (0.85)

35.4 (1.39)

21.6 (0.85)

Page 71

Relay and Timer Specifications

700-HJ Magnetic Latching Relay • 10 A Contact Rating • SPDT • DPDT Single Coil • DPDT Dual Coil • Blade Style Quick Connect Terminals Photo

Description

SPDT 1-Pole 1 Form C AgCdO Contacts (Single Coil AC or DC)

Contact Rating

700-HN153

Sockets

DC(3)

Coil Voltage

Cat. No.

24V AC

700-HJ36A24

120V AC

700-HJ36A1

24V DC

700-HJ36Z24

24V AC

700-HJ32A24

120V AC

700-HJ32A1

240V AC

700-HJ32A2

12V DC

700-HJ32Z12

24V DC

700-HJ32Z24

24V DC

700-HJD32Z24

700-HN154

10 A

Sockets

DPDT 2-Pole 2 Form C AgCdO Contacts (Dual Coil(1)

AC(2)

10 A

Sockets

DPDT 2-Pole 2 Form C AgCdO Contacts (Single Coil AC or DC)

Wiring Diagrams

700-HN153

10 A

700-HN154

DC Only

700-HN153 or 700-HN154

(1) Available only in DC Coil with DPDT contacts. (2) AC Relays include internal diodes. (3) For DC operation, polarity must be observed.

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

71

Page 72

Relay and Timer Specifications

Accessories-700-HJ Relays Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Socket, Panel or DIN Rail Mounting. Guarded Terminal Construction 11-blade socket for use with 700-HB relays. This socket has coil and contact separation as well as the ability to use optional plug-in modules ( 700-A__ accessories, LED, surge suppression, timing modules).

10

700-HN153

Screw Terminal Base Socket, Panel or DIN Rail Mounting. Open Style Construction 11-blade for use with 700-HB relays.

10

700-HN154

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip For Cat. Nos. 700-HN153 and -HN154 Sockets with 700-HJ Relays Secures relay in socket. Order must be for 10 clips or multiples of 10.

10

700-HN159

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Socket and Retainer Clip Reference Relay Type 700-HJ

Socket Cat. No.

Retainer Clip Cat. No.

700-HN153

700-HN159

700-HN154

700-HN159

Specifications - 700-HJ Relays Attribute

700-HJ Electrical Ratings

Pilot Duty Rating, Rated Thermal Current (Ith)

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive

Contacts

120V AC 240V AC DC

Permissible Coil Voltage Variation

72

Make

Break

Hp

30 A 15 A

3A 1.5 A 24V DC, 10 A 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

1/4 1/3

Page 73

Relay and Timer Specifications

Specifications - 700-HJ Relays Single AC Coil AC Coils

Inrush Sealed

Coil Consumption ±10% DC Coils

Single DC Coil

Dual DC Coil

1.44 VA 1.44 VA, - - 1.2 W

12V 1.63 W 24V 1.67 W

Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole

1500V AC

Contact-to-Pole

1500V AC

Contact-to-Frame

1500V AC Mechanical

Open Type (Guarded Terminal Sockets)

Degree of Protection Mechanical Life Operations

10 x 106

Switching Frequency Operations

1800/HR

Coil Voltages Operating Time at Nominal Voltage at 20 °C

See Product Selection Pickup Dropout

25 ms 25 ms

Maximum Operating Rate, Environmental

Operating

–45…+50 °C (–49…+122 °F)

Storage

–45…+100 °C (–49…+212 °F)

Temperature

Altitude

2000 m (6560 ft.) Construction

Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets

Molded High Dielectric Material Transparent Dust Cover Silver Cad. Ox. In accordance with EN50 0005 11-Blade Socket Cat. No. 700-HN153 Cat. No. 700-HN154

Certifications

CSA Certified, File LR700026, UL Recognized, File E3125, Guide NLDX 2

Standards

UL 508, CSA 22.2 No. 14, EN/IEC 60947-4-1, -5-1

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

73

Page 74

Relay and Timer Specifications

Dimensions - 700-HJ Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

700-HJ Relay

Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in

Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)

5.2 (13/64)

6.2 (15/64)

50 (1-63/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

74

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 75

Relay and Timer Specifications

700-HG Power Relay • 40 A Contact Ratings • SPST-NO-DM, SPDT, DPST-NO, DPDT • Panel Mounted • Options: Magnetic Blowout for High DC Loads, Auxiliary Snap Action Switch • Screw Terminals #6-32 for Coil, #8-32 for Contacts Description

SPST-NO-DM 1 Form X AgCdO Contacts

SPDT 1-pole 1 Form C AgCdO Contacts

DPST-NO 2-pole 2 Form A AgCdO Contacts

DPDT 2-pole 2 Form C AgCdO Contacts

Contact Ratings

Wiring Diagrams

40 A (A600)

40 A (A600)

40 A (A600)

40 A (A600)

Coil Voltage

Cat. No.(1)

24V AC

700-HG45A24

120V AC

700-HG45A1

240V AC

700-HG45A2

277V AC

700-HG45A27

480V AC

700-HG45A4

12V DC

700-HG45Z12

24V DC

700-HG45Z24

48V DC

700-HG45Z48

110V DC

700-HG45Z1

24V AC

700-HG46A24

120V AC

700-HG46A1

240V AC

700-HG46A2

12V DC

700-HG46Z12

24V DC

700-HG46Z24

48V DC

700-HG46Z48

110V DC

700-HG46Z1

24V AC

700-HG47A24

120V AC

700-HG47A1

240V AC

700-HG47A2

480V AC

700-HG47A4

12V DC

700-HG47Z12

24V DC

700-HG47Z24

48V DC

700-HG47Z48

110V DC

700-HG47Z1

24V AC

700-HG42A24

120V AC

700-HG42A1

240V AC

700-HG42A2

277 AC

700-HG42A27

12V DC

700-HG42Z12

24V DC

700-HG42Z24

48V DC

700-HG42Z48

110V DC

700-HG42Z1

220V DC

700-HG42Z2

250V DC

700-HG42Z25

(1) Auxiliary Snap Switch Option: Add suffix (-5) to the selected 700-HG relay Cat. No., except for the 220V DC add (-5L). Magnetic Blowout Option: Add suffix (-6) to the selected 700-HG relay Cat. No. (suppresses the arc when switching DC loads – ratings listed below).

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

75

Page 76

Relay and Timer Specifications

Accessories - 700-HG Relays Photo

Description

Pkg. Qty.

Cat. No.

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Type 1 Enclosure For use with any of the listed relays. Knockouts for 1/2 in. and 3/4 in. conduit connections. The enclosure exceeds the minimum clearances required by U.S. standards, resulting in generous wiring spaces.

1

700-HN120

Auxiliary Snap Action Switch Contact

Material

Rating

Dielectric Withstand V (1 Min.)

SPDT (1 Form C)

Silver Cad. Ox.

10 A at 120 or 240 Resistive

1500V AC RMS Contact to Frame

76

Rockwell Automation Publication 700-TD552C-EN-P - October 2018

Page 77

Relay and Timer Specifications

Specifications - 700-HG Relays Attribute

700-HG

Electrical Ratings Pilot Duty Rating (1)

A600

Rated Thermal Current (Ith)

40 A

Rated Insulation Voltage (Ui)

600V UL Contact Ratings: AC Ratings SPST-NO-DM Inductive

Volts

Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT Resistive Make/Break and Continuous

Make

Break

Continuous

120

60 A

6A

10 A

40 A

240

30 A

3A

10 A

40 A

480V

15 A

1.5 A

10 A

12 A

600V

12 A

1.2 A

10 A

10 A

Inductive HP

2

2

Volts

Resistive Make/Break and Continuous Continuous

Make

Break

120

60 A

6A

10 A

40 A

240

30 A

3A

10 A

40 A

480

15 A

1.5 A

10 A

5A

600

15 A

1.2 A

10 A

5A

HP (2)

1 - 1/2

1 - 1/2

DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous Est Drop 125V 1.2...3 A SPST - NO DM

SPDT, DPST - NO and DPDT

110V

20 A

10 A

220V

8A

4A

325V

4A

2A

500V

2A, DC Ratings: With Magnetic Blowouts:

Make, Break, and Continuous

80...100% of Nominal Voltage at 50 Hz Permissible Coil Voltage Variation

85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC 50 HZ

Coil Consumption ±10%

AC Coils

60 HZ

Inrush

13 VA

16 VA

Sealed

10 VA

11 VA

DC Coils

2.0 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole

2200V AC

Contact to Pole

2200V

Contact to Frame

2200V AC Mechanical

Degree of Protection

Open Type

Mechanical Life Operations

5 x 106

Switching Frequency Operations

1600/Hr

Coil Voltage

See Overview/Product Selection

Operating Time at Nominal Voltage at Pickup 20 °C Dropout

40 ms 35 ms

Maximum Operating Rate, Rockwell Automation Publication 700-TD552C-EN-P - October 2018

77

Page 78

Relay and Timer Specifications

Specifications - 700-HG Relays Environmental Temperature

Operating

30...+55 °C (-22...+149 °F)

Storage

-30...+65 °C (-22...+149 °F)

Altitude

2000 m (6560 ft.) Construction

Insulating Material Enclosure Contact Material

Molded Thermo Setting Plastic, Silver Cadmium Oxide

Terminal Markings on Socket, Sockets, Certifications

CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked

Standards

UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1

(1) NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. (2) For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.

78

Rockwell Automation Publication 700-TD552C-EN-P - October 2018