Page 651
Section 13A Connecting 8520 Digital Drive Systems
Table 13A.H 1AX-D Servo Amplifier Jumper Settings (continued) J13
Short - Enable Axis Motor Open - Disable Axis Motor
J14
Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched
J15
Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used
Table 13A.I 2AX-D (2 axis) Servo Amplifier Jumper Settings Axis 1 - - CNA1
J1
J2
J3
J4
J7
J8
J9
J10
Axis 2 - - CNA2
J13
J14
J15
J16
J19
J20
J21
J22
Motor Rated Current 200%
300%
0.4
0.4
0.7
0.7
1.1
1.1
1.5
1.5
1.9
1.9
2.2
2.2
2.6
2.6
3.0
3.0
3.4
3.4
3.7
3.7
4.1
>AMP Limit
4.5
>AMP Limit
4.9
>AMP Limit
5.2
>AMP Limit
5.6
>AMP Limit
6.0
>AMP Limit
·
· ·
·
·
·
·
·
· · ·
·
· ·
·
·
·
· ·
· ·
·
·
·
· · ·
· ·
·
·
· ·
·
·
·
·
·
·
·
·
·
· ·
· · ·
· ·
·
·
· ·
·
·
·
·
·
·
·
·
·
· ·
“· ” Denotes jumper short
For 200% of motor rated current, the following jumpers are shorted: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 For 300% of motor rated current, the following jumpers are open: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24
13A-17
Page 652
Section 13A Connecting 8520 Digital Drive Systems
Table 13A.J 2AX-D Servo Amplifier Jumper Settings (continued) J25
Short - Enable Axis 1 Motor Open - Disable Axis 1 Motor
J26
Short - Enable Axis 2 Motor Open - Disable Axis 2 Motor
J27
Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched
J28
Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used
Table 13A.K 3AX-D (3 axis) Servo Amplifier Jumper Settings Axis 1 - - CNA1
J1
J2
J3
J4
J7
J8
J9
J10
Axis 2 - - CNA2
J13
J14
J15
J16
J19
J20
J21
J22
Axis 3 - - CNA3
J25
J26
J27
J28
J31
J32
J33
J34
Motor Rated Current 200%
300%
0.7
0.7
1.5
1.5
2.2
2.2
3.0
3.0
3.7
3.7
4.5
4.5
5.2
5.2
5.9
5.9
6.7
6.7
7.5
7.5
8.2
>AMP Limit
9.0
>AMP Limit
9.7
>AMP Limit
10.4
>AMP Limit
11.2
>AMP Limit
11.9
>AMP Limit
·
· ·
·
·
·
·
·
· · ·
·
· ·
·
·
·
· ·
· ·
·
·
·
· · ·
· ·
·
·
· ·
·
·
·
·
·
·
·
·
·
· ·
· · ·
· ·
·
·
· ·
·
·
·
·
·
·
·
·
·
· ·
“· ” Denotes jumper short
For 200% of motor rated current, the following jumpers are shorted: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 - AXIS 3: J29, J30, J35, J36
13A-18
Page 653
Section 13A Connecting 8520 Digital Drive Systems
For 300% of motor rated current, the following jumpers are open: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 - AXIS 3: J29, J30, J35, J36 Table 13A.L 3AX-D Servo Amplifier Jumper Settings (continued) J37
Short - Enable Axis 1 Motor Open - Disable Axis 1 Motor
J38
Short - Enable Axis 2 Motor Open - Disable Axis 2 Motor
J39
Short - Enable Axis 3 Motor Open - Disable Axis 3 Motor
J40
Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched
J41
Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used
13A.6 8520 Digital Servo Amplifier Shunt Specifications
When the servo amplifier is installed as recommended and E-STOP occurs, the control sets the velocity command to zero. If the axes are in motion at that time, they will coast to a stop rather than being rapidly decelerated as they would be under servo amplifier control. To improve axis stopping time when E-STOP occurs, the 8520 digital servo amplifier employs a dynamic brake. This brake is in the form of a power resistor that is shunted across the motor terminals. Power generated by the motor is dissipated through this resistor, thereby driving the motor to a rapid stop even though the 8520 digital servo amplifier is off. There are three shunt resistor options that can be used with the 8520 digital servo amplifiers. One involves using the internal shunt resistor supplied with the amplifiers, while the others require purchase and installation of an external shunt resistor. The following equations should be used to size a shunt resistor for the desired application. First, use these equations to solve for the peak power P, and the average power W. Then apply those values to the chart below to determine the appropriate shunt option. P = (.00054) (J) (N2)
W = (.0000108) (J) (N2) (T)
13A-19
Page 654
Section 13A Connecting 8520 Digital Drive Systems
Where: - J = total motor and axis inertia measured at motor shaft, summed for all motors connected to the servo amplifier [Kg cm s2] - N = maximum motor speed [rpm] - T = desired deceleration time from maximum motor speed to stop [sec.] Important: These equations are for approximating shunt resistor requirements. They can produce worst case data that is unrealistic for most applications. For example, in most machine tool applications it is unlikely that all axes will ever be traveling simultaneously at their maximum speed. Factor the type of duty expected for your machine into these equations.
Shunt Resistor Selection Chart P < 1100
1100 £P < 1800
1800 £P
W < 180
Shunt Option #1
Shunt Option #2
1
180 £W < 540
Shunt Option #2
Shunt Option #2
1
540 £W < 810
Shunt Option #3
Shunt Option #3
1
810 £W
2
2
2
1 Not possible with current configuration. Move one or more motors to another servo amplifier, or reduce inertia, or reduce motor speed.
2
Not possible with current configuration. Move one or more motors to another servo amplifier, or reduce inertia, or reduce motor speed, or increase time from maximum speed to stop.
Table 13A.M lists the internal/external shunt resistor, contactor, and fuse specifications. Table 13A.M Internal/External Shunt Specifications Specifications Option #1
Option #2
Option #3
Shunt Location
Internal
External
External
Shunt Resistance
16 ohms
10 ohms
10 ohms
Shunt Continuous Rating
196 watts
600 watts
900 watts
Shunt Duty Cycle Limit (determined by servo amplifier jumper settings)
2 sec
5 sec
5 sec
Shunt Fuse Rating Shunt Contactor Size
13A-20
Shunt Options
15A/600V non-time delay 15A/600V or greater
Page 655
Section 13A Connecting 8520 Digital Drive Systems
After determining system shunt requirements, terminal block (BT2) on each of the 8520 digital amplifiers should be jumpered for either an internal shunt resistor or an external shunt resistor. Figure 13A.10 and Figure 13A.11 illustrate this procedure. Figure 13A.10 Shunt Resistor Connections for 2AX-D Servo Amplifiers Using Internal Shunt Resistor
Using External Shunt Resistor
Contacts (minimum 4 contacts in series)
External shunt Fuse resistor Contacts (minimum 4 contacts in series)
EXT EXT TB2 TB2
INT/ EXT
INT/ EXT
EXT
EXT
INT
INT To internal shunt resistor
To internal shunt resistor
11288-I
Figure 13A.11 Shunt Resistor Connections for 1AX-D and 3AX-D Servo Amplifiers Using External Shunt Resistor Using Internal Shunt Resistor
External shunt resistor
Contacts (minimum 4 contacts in series)
Fuse
Contacts (minimum 4 contacts in series)
Shunt EXT
TB2
Shunt EXT
TB2
Internal shunt resistor
Internal shunt resistor 11289-I
13A-21
Page 656
Section 13A Connecting 8520 Digital Drive Systems
Normally-closed contacts must be installed as shown in Figure 13A.10 and Figure 13A.11. These four contacts should be held open whenever the 8520 digital servo amplifier is energized and should be closed by the emergency stop circuitry. You must wire at least four contacts in series to safely break this connection. Allen-Bradley 100-A30ND3 contactors with added deck 195-FAD4 are recommended. Refer to a 1389 transformer manual for special requirements and additional information on the normally-closed contactor. Details on emergency stop wiring start on page 6-1. ATTENTION: The four normally closed contacts shown in Figure 13A.10 and Figure 13A.11 should not be used on machines with large non-counter balanced vertical axes. No contacts are required. Under a normal shut down, leaving these contacts out allows the drive to maintain torque for a longer period of time. This provides more time for holding brakes to set.
Important: Jumpers on the 8520 digital servo amplifier circuit boards must be set for internal or external shunt resistor. These jumpers control the duty cycle (amount of continuous “on” time) for the shunt resistors. Important: The external shunt resistor should be mounted in an area where the heat it generates will not adversely affect other components of the control. Important: The shunt contacts should not be closed while 3-phase power is applied to the drive amplifier. The shunt circuitry is sized to dynamic braking of the axis when E-stop is applied and 3-phase power is removed from the amplifier.
13A.7 8520 Drive Power Distribution
ATTENTION: To guard against electrical shock hazards, never make connections or disconnections at the ac distribution network unless the main ac disconnect switch is open and locked. Figure 13A.1 shows how power is distributed from the supply to the transformer and amplifier.
13A-22
Page 657
Section 13A Connecting 8520 Digital Drive Systems
Figure 13A.1 Power Distribution from the Supply to the Transformer and Amplifier Disconnect Switch 3Æ 230V ac R S
Fuse 1
Contactors 2 C1
A-B 1389 transformer 3
8520 digital Servo Amplifier Dynamic Brake circuitry (shunt resistor, fuse, contactor).
C1 C1
T 3A 3A
Internal drive logic fuse
Customer transformer
Motor E
115V ac
Main power supply Fuse size based on customer needs
Refer to drives interface section.
System ready
Customer power supply (24V dc) 9/260 and 9/2904 P1 C1 E-Stop Status Relay Contact
E-Stop Function
1
Main power circuit fuse sizing is determined by the following equation: Fuse capacity (A) = (Tr) x 974.3 V Where: Tr = Transformer size calculated on page 13A-12 (in kW) V = minimum 3 phase input voltage (V ac)
2
Contactor sizing is such that its capacity is greater than that of the fuses.
3
Refer to section 4.2 to size the transformer. 4 May not be necessary on PS2 24V is part of the power supply.
11194-I
13A-23
Page 658
Section 13A Connecting 8520 Digital Drive Systems
13A.8 8500 Digital Servo Motors
The 8500 digital servo motors are used to drive the axes of the 8520 digital servo drive system. The 8500 digital servo motors have a feedback device mounted on them that provides position and velocity data to the servo module. A second feedback device can be mounted directly on the axis (such as a linear slide) to provide greater precision for positioning feedback. On these systems with multiple feedback devices, the motor mounted encoder is used for motor commutation and velocity feedback.
13A.8.1 8500 Digital Servo Motor Options
The control uses a digital velocity command scheme to improve motor performance and efficiency. This requires the use of servo motors designed for 8520 digital drive application. The 8520 digital servo drive system can be configured to handle various 8500 digital servo motors. Table 13A.N lists the 1000/2000 RPM servo motor options and their specifications. Table 13A.N 1000/2000 RPM 8500 Digital Servo Motor Options and Specifications 1000/2000 RPM 8500 Digital Servo Motor Options
Specifications
8500-A1C
8500-A2C
8500-B1C
8500-B2C
8500-B3C
Rated Output/Axis kW (HP)
0.3 (0.4)
0.6 (0.8)
1.2 (1.6)
2.0 (2.7)
3.0 (4.1)
Rated Torque kg. cm (lb . in)
29 (25)
58 (50)
117 (102)
195 (169)
290 (252) 1
Continuous Max. Torque kg. cm (lb . in)
30 (26)
60 (52)
120 (104)
220 (191)
330 (286)
Instantaneous Max. Torque kg. cm (lb . in)
87 (76) 2
174 (151) 2
351 (305) 2
390 (339) 2
703 (610) 2
Rated Current
Arms
3.0
5.8
11.7
18.8
26 1
Rated Revolution rpm
1000
Maximum Rated Revolution rpm
2000
Torque Constant kg. cm/A (lb . in/A)
10.3 (8.9)
10.6 (9.2)
10.4 (9.0)
10.9 (9.5)
11.8 (10.2)
Rotor Inertia (J)
g . cm . s2 (lb . in s2x10-3)
13.8 (12.0)
24.8 (21.5)
68.2 (59.2)
112 (97.2)
146 (126.7)
(GD2/4)
kg . cm2 (lb . in2)
13.5 (4.61)
24.3 (8.31)
66.8 (22.8)
110 (37.6)
143 (48.9)
Power Rate kW/s
6.1
13.3
19.7
33.2
57.0
Mechanical Time Constant ms
8.3
5.9
6.9
5.2
4.1
Electrical Time Constant ms
4.2
5.4
10.4
12.9
15.3
Number of Pole poles
Weight kg (lb)
32 (71)
43 (95)
8 10 (15)
15 (33)
24 (53)
1
The rated current available for the 8500-B3C digital servo motor is limited to 21 amps (rms) by the amplifiers maximum output rating. This limits the available rated torque to 232 kg.cm (203 lb.in).
2
These values will vary depending on the amplifier selected to operate these motors. You may need to recalculate these values based on your amplifier selection.
Important: 8500 digital servo motor mounting dimensions start on page 13B-1.
13A-24
Page 659
Section 13A Connecting 8520 Digital Drive Systems
Table 13A.O lists the 1500/2500 RPM 8500 digital servo motor options and their specifications. Table 13A.O 1500/2500 RPM 8500 Digital Servo Motor Options and Specifications Specifications
1500/2500 RPM 8500 Digital Servo Motor Options 8500-A1D
8500-A2D
8500-A3D
8500-B1D
8500-B2D
Rated Output/Axis kW (HP)
0.45 (0.6)
0.85 (1.2)
1.3 (1.8)
1.8 (2.4)
2.9 (3.9)
Rated Torque kg. cm (lb . in)
29 (25)
55 (48)
85 (74)
117 (102)
190 (165)
Continuous Max. Torque kg. cm (lb . in)
30 (26)
60 (52)
90 (72)
120 (104)
230 (200)
Instantaneous Max. Torque kg. cm (lb . in)
87 (76) 1
165 (143) 1
255 (221) 1
234 (203) 1
380 (330) 1
Rated Current
Arms
3.8
6.2
9.7
15
20
Rated Revolution rpm
1500
Maximum Rated Revolution rpm
2500
Torque Constant kg. cm/A (lb . in/A)
8.2 (7.1)
9.4 (8.2)
9.4 (8.2)
8.4 (7.3)
10.0 (8.7)
Rotor Inertia (J)
g . cm . s2 (lb . in s2x10-3)
13.8 (12.0)
24.8 (21.5)
37.4 (32.5)
68.2 (59.2)
112 (97.2)
(GD2/4)
kg . cm2 (lb . in2)
13.5 (4.61)
24.3 (8.31)
36.7 (12.5)
66.8 (22.8)
110 (37.6)
Power Rate kW/s
6.0
12
18.9
19.7
31.5
Mechanical Time Constant ms
8.3
5.7
4.7
6.8
5.1
Electrical Time Constant ms
4.2
5.5
6.4
10.4
13.0
Number of Pole poles
Weight kg (lb)
24 (53)
32 (71)
1
8 10 (22)
15 (33)
21 (46)
These values will vary depending on the amplifier selected to operate these motors. You may need to recalculate these values based on your amplifier selection.
Important: 8500 digital servo motor mounting dimensions start on page 13B-1.
13A-25
Page 660
Section 13A Connecting 8520 Digital Drive Systems
Table 13A.P lists the general motor specifications that apply to all of the previously listed 8500 digital servo motors. Table 13A.P 8500 Digital Servo Motor General Specifications Item
Specification
Ambient Temperature
0°C to +40°C
Ambient Humidity
20-80% (No Dew Condensation)
Brake Voltage
90V dc
Brake Holding Torque
A Series - 90 Kg - cm 16.2 watts B Series - 360 Kg - cm 31 watts
Drive Method
Direct Drive
Enclosure
Totally-enclosed, Self-Cooled (Equivalent to IP-55 Rating)
Excitation Method
Permanent Ferrite Magnet
Isolation Voltage
1500 V ac, 1 min.
Insulation Resistance
500 V dc, 10M Ohms or more
Mounting
Flange Mounted
Oil Seal
Nitril Rubber 1
Thermostat
N.C.
- Opens at 155°C ±5°C - Closes at 110°C ±20°C
1 Oil sealed motors should be operated under the following conditions:
· Optimum oil level should be below the oil seal lip · Oil should be splashed to oil seal
All 8500 digital servo motors listed are equipped with thermal overload switches. These are normally closed switches that open when the motor temperature exceeds a safe limit. The system installer has two choices for implementing these safety switches. They can be wired directly into the E-STOP string, or they can cause an input to PAL through an I/O device. Wiring these switches directly into the E-STOP string provides an immediate and very reliable response to over-temperature conditions. The disadvantage in doing this is that the drives will be shut down no matter where the machine is in an operation and cannot be restarted until the over-temperature condition is resolved. If the over-temperature switches are wired as inputs to PAL, the PAL program can be written to handle the situation in a controlled manner. PAL can be programmed to allow the completion of an operation, or to move the axes to a safe position before shutting down the machine.
13A-26