The text of a manual · part 66 of 91

9/Series CNC Hardware Integration and Maintenance Manual, pages 651 to 660

Pages 651 to 660 of 898

The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 8500-1746I

Page 651

Section 13A Connecting 8520 Digital Drive Systems

Table 13A.H 1AX-D Servo Amplifier Jumper Settings (continued) J13

Short - Enable Axis Motor Open - Disable Axis Motor

J14

Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched

J15

Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used

Table 13A.I 2AX-D (2 axis) Servo Amplifier Jumper Settings Axis 1 - - CNA1

J1

J2

J3

J4

J7

J8

J9

J10

Axis 2 - - CNA2

J13

J14

J15

J16

J19

J20

J21

J22

Motor Rated Current 200%

300%

0.4

0.4

0.7

0.7

1.1

1.1

1.5

1.5

1.9

1.9

2.2

2.2

2.6

2.6

3.0

3.0

3.4

3.4

3.7

3.7

4.1

>AMP Limit

4.5

>AMP Limit

4.9

>AMP Limit

5.2

>AMP Limit

5.6

>AMP Limit

6.0

>AMP Limit

·

· ·

·

·

·

·

·

· · ·

·

· ·

·

·

·

· ·

· ·

·

·

·

· · ·

· ·

·

·

· ·

·

·

·

·

·

·

·

·

·

· ·

· · ·

· ·

·

·

· ·

·

·

·

·

·

·

·

·

·

· ·

“· ” Denotes jumper short

For 200% of motor rated current, the following jumpers are shorted: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 For 300% of motor rated current, the following jumpers are open: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24

13A-17

Page 652

Section 13A Connecting 8520 Digital Drive Systems

Table 13A.J 2AX-D Servo Amplifier Jumper Settings (continued) J25

Short - Enable Axis 1 Motor Open - Disable Axis 1 Motor

J26

Short - Enable Axis 2 Motor Open - Disable Axis 2 Motor

J27

Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched

J28

Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used

Table 13A.K 3AX-D (3 axis) Servo Amplifier Jumper Settings Axis 1 - - CNA1

J1

J2

J3

J4

J7

J8

J9

J10

Axis 2 - - CNA2

J13

J14

J15

J16

J19

J20

J21

J22

Axis 3 - - CNA3

J25

J26

J27

J28

J31

J32

J33

J34

Motor Rated Current 200%

300%

0.7

0.7

1.5

1.5

2.2

2.2

3.0

3.0

3.7

3.7

4.5

4.5

5.2

5.2

5.9

5.9

6.7

6.7

7.5

7.5

8.2

>AMP Limit

9.0

>AMP Limit

9.7

>AMP Limit

10.4

>AMP Limit

11.2

>AMP Limit

11.9

>AMP Limit

·

· ·

·

·

·

·

·

· · ·

·

· ·

·

·

·

· ·

· ·

·

·

·

· · ·

· ·

·

·

· ·

·

·

·

·

·

·

·

·

·

· ·

· · ·

· ·

·

·

· ·

·

·

·

·

·

·

·

·

·

· ·

“· ” Denotes jumper short

For 200% of motor rated current, the following jumpers are shorted: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 - AXIS 3: J29, J30, J35, J36

13A-18

Page 653

Section 13A Connecting 8520 Digital Drive Systems

For 300% of motor rated current, the following jumpers are open: - AXIS 1: J5, J6, J11, J12 AXIS 2: J17, J18, J23, J24 - AXIS 3: J29, J30, J35, J36 Table 13A.L 3AX-D Servo Amplifier Jumper Settings (continued) J37

Short - Enable Axis 1 Motor Open - Disable Axis 1 Motor

J38

Short - Enable Axis 2 Motor Open - Disable Axis 2 Motor

J39

Short - Enable Axis 3 Motor Open - Disable Axis 3 Motor

J40

Short - Bus Under Voltage FAULT not Latched Open - Bus Under Voltage FAULT Latched

J41

Short - Internal Shunt Resistor Used Open - External Shunt Resistor Used

13A.6 8520 Digital Servo Amplifier Shunt Specifications

When the servo amplifier is installed as recommended and E-STOP occurs, the control sets the velocity command to zero. If the axes are in motion at that time, they will coast to a stop rather than being rapidly decelerated as they would be under servo amplifier control. To improve axis stopping time when E-STOP occurs, the 8520 digital servo amplifier employs a dynamic brake. This brake is in the form of a power resistor that is shunted across the motor terminals. Power generated by the motor is dissipated through this resistor, thereby driving the motor to a rapid stop even though the 8520 digital servo amplifier is off. There are three shunt resistor options that can be used with the 8520 digital servo amplifiers. One involves using the internal shunt resistor supplied with the amplifiers, while the others require purchase and installation of an external shunt resistor. The following equations should be used to size a shunt resistor for the desired application. First, use these equations to solve for the peak power P, and the average power W. Then apply those values to the chart below to determine the appropriate shunt option. P = (.00054) (J) (N2)

W = (.0000108) (J) (N2) (T)

13A-19

Page 654

Section 13A Connecting 8520 Digital Drive Systems

Where: - J = total motor and axis inertia measured at motor shaft, summed for all motors connected to the servo amplifier [Kg cm s2] - N = maximum motor speed [rpm] - T = desired deceleration time from maximum motor speed to stop [sec.] Important: These equations are for approximating shunt resistor requirements. They can produce worst case data that is unrealistic for most applications. For example, in most machine tool applications it is unlikely that all axes will ever be traveling simultaneously at their maximum speed. Factor the type of duty expected for your machine into these equations.

Shunt Resistor Selection Chart P < 1100

1100 £P < 1800

1800 £P

W < 180

Shunt Option #1

Shunt Option #2

1

180 £W < 540

Shunt Option #2

Shunt Option #2

1

540 £W < 810

Shunt Option #3

Shunt Option #3

1

810 £W

2

2

2

1 Not possible with current configuration. Move one or more motors to another servo amplifier, or reduce inertia, or reduce motor speed.

2

Not possible with current configuration. Move one or more motors to another servo amplifier, or reduce inertia, or reduce motor speed, or increase time from maximum speed to stop.

Table 13A.M lists the internal/external shunt resistor, contactor, and fuse specifications. Table 13A.M Internal/External Shunt Specifications Specifications Option #1

Option #2

Option #3

Shunt Location

Internal

External

External

Shunt Resistance

16 ohms

10 ohms

10 ohms

Shunt Continuous Rating

196 watts

600 watts

900 watts

Shunt Duty Cycle Limit (determined by servo amplifier jumper settings)

2 sec

5 sec

5 sec

Shunt Fuse Rating Shunt Contactor Size

13A-20

Shunt Options

15A/600V non-time delay 15A/600V or greater

Page 655

Section 13A Connecting 8520 Digital Drive Systems

After determining system shunt requirements, terminal block (BT2) on each of the 8520 digital amplifiers should be jumpered for either an internal shunt resistor or an external shunt resistor. Figure 13A.10 and Figure 13A.11 illustrate this procedure. Figure 13A.10 Shunt Resistor Connections for 2AX-D Servo Amplifiers Using Internal Shunt Resistor

Using External Shunt Resistor

Contacts (minimum 4 contacts in series)

External shunt Fuse resistor Contacts (minimum 4 contacts in series)

EXT EXT TB2 TB2

INT/ EXT

INT/ EXT

EXT

EXT

INT

INT To internal shunt resistor

To internal shunt resistor

11288-I

Figure 13A.11 Shunt Resistor Connections for 1AX-D and 3AX-D Servo Amplifiers Using External Shunt Resistor Using Internal Shunt Resistor

External shunt resistor

Contacts (minimum 4 contacts in series)

Fuse

Contacts (minimum 4 contacts in series)

Shunt EXT

TB2

Shunt EXT

TB2

Internal shunt resistor

Internal shunt resistor 11289-I

13A-21

Page 656

Section 13A Connecting 8520 Digital Drive Systems

Normally-closed contacts must be installed as shown in Figure 13A.10 and Figure 13A.11. These four contacts should be held open whenever the 8520 digital servo amplifier is energized and should be closed by the emergency stop circuitry. You must wire at least four contacts in series to safely break this connection. Allen-Bradley 100-A30ND3 contactors with added deck 195-FAD4 are recommended. Refer to a 1389 transformer manual for special requirements and additional information on the normally-closed contactor. Details on emergency stop wiring start on page 6-1. ATTENTION: The four normally closed contacts shown in Figure 13A.10 and Figure 13A.11 should not be used on machines with large non-counter balanced vertical axes. No contacts are required. Under a normal shut down, leaving these contacts out allows the drive to maintain torque for a longer period of time. This provides more time for holding brakes to set.

Important: Jumpers on the 8520 digital servo amplifier circuit boards must be set for internal or external shunt resistor. These jumpers control the duty cycle (amount of continuous “on” time) for the shunt resistors. Important: The external shunt resistor should be mounted in an area where the heat it generates will not adversely affect other components of the control. Important: The shunt contacts should not be closed while 3-phase power is applied to the drive amplifier. The shunt circuitry is sized to dynamic braking of the axis when E-stop is applied and 3-phase power is removed from the amplifier.

13A.7 8520 Drive Power Distribution

ATTENTION: To guard against electrical shock hazards, never make connections or disconnections at the ac distribution network unless the main ac disconnect switch is open and locked. Figure 13A.1 shows how power is distributed from the supply to the transformer and amplifier.

13A-22

Page 657

Section 13A Connecting 8520 Digital Drive Systems

Figure 13A.1 Power Distribution from the Supply to the Transformer and Amplifier Disconnect Switch 3Æ 230V ac R S

Fuse 1

Contactors 2 C1

A-B 1389 transformer 3

8520 digital Servo Amplifier Dynamic Brake circuitry (shunt resistor, fuse, contactor).

C1 C1

T 3A 3A

Internal drive logic fuse

Customer transformer

Motor E

115V ac

Main power supply Fuse size based on customer needs

Refer to drives interface section.

System ready

Customer power supply (24V dc) 9/260 and 9/2904 P1 C1 E-Stop Status Relay Contact

E-Stop Function

1

Main power circuit fuse sizing is determined by the following equation: Fuse capacity (A) = (Tr) x 974.3 V Where: Tr = Transformer size calculated on page 13A-12 (in kW) V = minimum 3 phase input voltage (V ac)

2

Contactor sizing is such that its capacity is greater than that of the fuses.

3

Refer to section 4.2 to size the transformer. 4 May not be necessary on PS2 24V is part of the power supply.

11194-I

13A-23

Page 658

Section 13A Connecting 8520 Digital Drive Systems

13A.8 8500 Digital Servo Motors

The 8500 digital servo motors are used to drive the axes of the 8520 digital servo drive system. The 8500 digital servo motors have a feedback device mounted on them that provides position and velocity data to the servo module. A second feedback device can be mounted directly on the axis (such as a linear slide) to provide greater precision for positioning feedback. On these systems with multiple feedback devices, the motor mounted encoder is used for motor commutation and velocity feedback.

13A.8.1 8500 Digital Servo Motor Options

The control uses a digital velocity command scheme to improve motor performance and efficiency. This requires the use of servo motors designed for 8520 digital drive application. The 8520 digital servo drive system can be configured to handle various 8500 digital servo motors. Table 13A.N lists the 1000/2000 RPM servo motor options and their specifications. Table 13A.N 1000/2000 RPM 8500 Digital Servo Motor Options and Specifications 1000/2000 RPM 8500 Digital Servo Motor Options

Specifications

8500-A1C

8500-A2C

8500-B1C

8500-B2C

8500-B3C

Rated Output/Axis kW (HP)

0.3 (0.4)

0.6 (0.8)

1.2 (1.6)

2.0 (2.7)

3.0 (4.1)

Rated Torque kg. cm (lb . in)

29 (25)

58 (50)

117 (102)

195 (169)

290 (252) 1

Continuous Max. Torque kg. cm (lb . in)

30 (26)

60 (52)

120 (104)

220 (191)

330 (286)

Instantaneous Max. Torque kg. cm (lb . in)

87 (76) 2

174 (151) 2

351 (305) 2

390 (339) 2

703 (610) 2

Rated Current

Arms

3.0

5.8

11.7

18.8

26 1

Rated Revolution rpm

1000

Maximum Rated Revolution rpm

2000

Torque Constant kg. cm/A (lb . in/A)

10.3 (8.9)

10.6 (9.2)

10.4 (9.0)

10.9 (9.5)

11.8 (10.2)

Rotor Inertia (J)

g . cm . s2 (lb . in s2x10-3)

13.8 (12.0)

24.8 (21.5)

68.2 (59.2)

112 (97.2)

146 (126.7)

(GD2/4)

kg . cm2 (lb . in2)

13.5 (4.61)

24.3 (8.31)

66.8 (22.8)

110 (37.6)

143 (48.9)

Power Rate kW/s

6.1

13.3

19.7

33.2

57.0

Mechanical Time Constant ms

8.3

5.9

6.9

5.2

4.1

Electrical Time Constant ms

4.2

5.4

10.4

12.9

15.3

Number of Pole poles

Weight kg (lb)

32 (71)

43 (95)

8 10 (15)

15 (33)

24 (53)

1

The rated current available for the 8500-B3C digital servo motor is limited to 21 amps (rms) by the amplifiers maximum output rating. This limits the available rated torque to 232 kg.cm (203 lb.in).

2

These values will vary depending on the amplifier selected to operate these motors. You may need to recalculate these values based on your amplifier selection.

Important: 8500 digital servo motor mounting dimensions start on page 13B-1.

13A-24

Page 659

Section 13A Connecting 8520 Digital Drive Systems

Table 13A.O lists the 1500/2500 RPM 8500 digital servo motor options and their specifications. Table 13A.O 1500/2500 RPM 8500 Digital Servo Motor Options and Specifications Specifications

1500/2500 RPM 8500 Digital Servo Motor Options 8500-A1D

8500-A2D

8500-A3D

8500-B1D

8500-B2D

Rated Output/Axis kW (HP)

0.45 (0.6)

0.85 (1.2)

1.3 (1.8)

1.8 (2.4)

2.9 (3.9)

Rated Torque kg. cm (lb . in)

29 (25)

55 (48)

85 (74)

117 (102)

190 (165)

Continuous Max. Torque kg. cm (lb . in)

30 (26)

60 (52)

90 (72)

120 (104)

230 (200)

Instantaneous Max. Torque kg. cm (lb . in)

87 (76) 1

165 (143) 1

255 (221) 1

234 (203) 1

380 (330) 1

Rated Current

Arms

3.8

6.2

9.7

15

20

Rated Revolution rpm

1500

Maximum Rated Revolution rpm

2500

Torque Constant kg. cm/A (lb . in/A)

8.2 (7.1)

9.4 (8.2)

9.4 (8.2)

8.4 (7.3)

10.0 (8.7)

Rotor Inertia (J)

g . cm . s2 (lb . in s2x10-3)

13.8 (12.0)

24.8 (21.5)

37.4 (32.5)

68.2 (59.2)

112 (97.2)

(GD2/4)

kg . cm2 (lb . in2)

13.5 (4.61)

24.3 (8.31)

36.7 (12.5)

66.8 (22.8)

110 (37.6)

Power Rate kW/s

6.0

12

18.9

19.7

31.5

Mechanical Time Constant ms

8.3

5.7

4.7

6.8

5.1

Electrical Time Constant ms

4.2

5.5

6.4

10.4

13.0

Number of Pole poles

Weight kg (lb)

24 (53)

32 (71)

1

8 10 (22)

15 (33)

21 (46)

These values will vary depending on the amplifier selected to operate these motors. You may need to recalculate these values based on your amplifier selection.

Important: 8500 digital servo motor mounting dimensions start on page 13B-1.

13A-25

Page 660

Section 13A Connecting 8520 Digital Drive Systems

Table 13A.P lists the general motor specifications that apply to all of the previously listed 8500 digital servo motors. Table 13A.P 8500 Digital Servo Motor General Specifications Item

Specification

Ambient Temperature

0°C to +40°C

Ambient Humidity

20-80% (No Dew Condensation)

Brake Voltage

90V dc

Brake Holding Torque

A Series - 90 Kg - cm 16.2 watts B Series - 360 Kg - cm 31 watts

Drive Method

Direct Drive

Enclosure

Totally-enclosed, Self-Cooled (Equivalent to IP-55 Rating)

Excitation Method

Permanent Ferrite Magnet

Isolation Voltage

1500 V ac, 1 min.

Insulation Resistance

500 V dc, 10M Ohms or more

Mounting

Flange Mounted

Oil Seal

Nitril Rubber 1

Thermostat

N.C.

- Opens at 155°C ±5°C - Closes at 110°C ±20°C

1 Oil sealed motors should be operated under the following conditions:

· Optimum oil level should be below the oil seal lip · Oil should be splashed to oil seal

All 8500 digital servo motors listed are equipped with thermal overload switches. These are normally closed switches that open when the motor temperature exceeds a safe limit. The system installer has two choices for implementing these safety switches. They can be wired directly into the E-STOP string, or they can cause an input to PAL through an I/O device. Wiring these switches directly into the E-STOP string provides an immediate and very reliable response to over-temperature conditions. The disadvantage in doing this is that the drives will be shut down no matter where the machine is in an operation and cannot be restarted until the over-temperature condition is resolved. If the over-temperature switches are wired as inputs to PAL, the PAL program can be written to handle the situation in a controlled manner. PAL can be programmed to allow the completion of an operation, or to move the axes to a safe position before shutting down the machine.

13A-26