Page 741

Section 15A Troubleshooting the Control

15A.5 Remote I/O Diagnostics

When the {REMOTE I/O} softkey is pressed (only available on systems with remote I/O) on the Main Diagnostics Menu screen, the Remote I/O monitor screen appears. This first screen displays only single transfer remote I/O words. “REMOTE I/O” appears at the top to identify the screen, along with the “SETUP MODE” message indicating that the control is in setup diagnostics mode. Figure 15A.13 shows an example of the Remote I/O screen. Figure 15A.13 Remote I/O Diagnostics Screen

REMOTE I/O - DISCRETE

0 1 2 3 4 5 6 7 OUT 0 1 2 3 4 5 6 7

ON=

SETUP MODE

IN

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

RIO BTRIO BT READ WRITE

The screen displays the eight input and eight output ports available. Following each port number are numbers 15 to 00 which correspond to the bit numbers for each I/O point on the port. If an input or output bit number is “ON”, it appears in inverse video. This is a real time display, response is limited only by delays in screen updates. The screen only shows the remote I/O words available on this system based on your rack size and starting address (as configured in AMP). Pressing the exit softkey (up arrow) at any time displays the Main Diagnostics Menu screen.

15A-31

Page 742

Section 15A Troubleshooting The Control

If block transfers are enabled (in AMP or using softkey) the first address in the rack (word 0 on above screen) will not be shown and the two RIO BT diagnostic softkeys appear. This first word is reserved for block transfer status information and can not be accessed by PAL. Pressing either the {RIO BT READ} or {RIO BT WRITE} softkeys displays the following screens: Figure 15A.14 Remote I/O Block Transfer Read Diagnostics Screen

REMOTE I/O - BLOCK TRANSFER READ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

ON =

HEX VALUE

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

1F93 1FF7 205B 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

NEXT PAGE

The block transfer write screen is similar to the above read screen. In addition to displaying the set bits of each word in reverse video, the right column of these screens display the hex equivalent value of the word. These screens display 16 words at a time of the total 64 block transfer words. Pressing the {NEXT PAGE} softkey displays the next 16 words. There are 32 block transfer read words and 32 block transfer write words.

15A-32

Page 743

Section 15A Troubleshooting the Control

For 9/230, 9/440 and 9/290 systems with the remote I/O option using revision 10.01 or later firmware, both single, block transfer, and pass through remote I/O should be available depending on your AMP, PAL or softkey selection. The remote I/O module on the 9/260 is a standalone module with its own I/O processor and firmware revision. The following table illustrates some common 9/260 Remote I/O configuration errors.

9/260 Remote I/O card Plugged into a 9/290

PAL flag $RMON Not set in first PAL scan

$RMON is set but block transfer is disabled in AMP

$RMON s set and block transfer is enabled in AMP

9/260 RIO card (01.01 or earlier) 9/Series Firmware prior to release 10.01

“FCM Revision Check Failure”displayed. Remote I/O is Disabled.

RIO Not Enabled

RIO is enabled for single transfers only. No block transfers or pass through.

N/A (AMP parameter did not exist)

9/260 RIO card (01.01 or earlier) 9/Series firmware that supports block transfers (10.01 or later)

“FCM Revision Check Failure”displayed. Remote I/O is Disabled.

“FCM Revision Check Failure”displayed. Remote I/O is Disabled.

RIO is enabled for single transfers only. No block transfers or pass through.

“FCM Revision Check Failure”displayed. Only single transfers enabled.

9/260 RIO card that supports block transfer (02.01 or later) 9/Series firmware that supports block transfers (10.01 or later)

“FCM Revision Check Failure”displayed. Remote I/O is Disabled.

Pass through enabled. RIO data unavailable to PAL logic.

RIO is enabled for single transfers. No block transfers. Pass through can be enabled using softkey.

Single transfers, block transfers, and pass through enabled. Softkey is not available.

15A-33

Page 744

Section 15A Troubleshooting The Control

15A.6 Fast I/O Diagnostics (9/260 and 9/290 Only)

When the {FAST I/O} softkey is pressed on the Main Diagnostics Menu screen, the Fast I/O screen appears. “FAST I/O” appears at the top to identify the screen, along with the “SETUP MODE” message indicating that the control is in setup diagnostics mode. Figure 15A.15 shows an example of the Fast I/O screen. Figure 15A.15 Fast I/O Diagnostics Screen

FAST I/O CN17F

IN OUT

SETUP MODE ON = 01 03 05 07 09 11 13 15

The screen shows connector CN17F, which is the Fast I/O connector number. It is followed by the four input terminals (01, 03, 05, and 07) and the four output terminals (09, 11, 13, and 15). If an input or output is “ON”, its terminal number appears in inverse video. This is a real time display, and its response is limited only by delays in screen updates. Pressing the exit softkey (up arrow) at any time displays the Main Diagnostics Menu screen.

15A-34

Page 745

Section 15A Troubleshooting the Control

15A.7 Servo Diagnostic Displays

There are two sets of diagnostic screens that provide detailed information on the operation and status of the servo system. Axis monitor diagnostic screens 1394 Drive status screens The axis monitor screens are available on all 9/Series controls. The “1394 DRIVE” status screen described here is available only on 9/440 systems. Note that there are comparable screens for the 9/260 and 9/290 under the “RING I/O” monitor screens. To access these two types of servo system displays, make the following softkey selections : [SYSTEM SUPPORT] (softkey level 1) PRGRAM OFFSET MACRO MANAGE PARAM

QUICK CHECK

FRONT PANEL

SWITCH LANG

ERROR PASSMESAGE WORD

SYSTEM SUPORT then [MONITOR]. (softkey level 2) PRGRAM MANAGE

AMP

DEVICE MONISETUP TOR

TIME PARTS

Subsequent selections are detailed in the following sections .

15A.7.1 Axis Monitor Diagnostics

When the {AXIS MONTOR} softkey is pressed on the Main Diagnostics Menu screen, the Axis Monitor screen appears. “AXIS MONITOR” appears at the top to identify the screen, along with the “SETUP MODE” message indicating that the control is in setup diagnostics mode. (softkey level 3) RING I/O

REMOTE I/O

FAST I/O

AXIS SERIAL MONTOR I/O

15A-35

Page 746

Section 15A Troubleshooting The Control

(softkey level 3) SEARCH 1394 DATA SCOPE MONTOR DRIVE

Figure 15A.16 below is an example of the Axis Monitor I/O screen. Note this screen is slightly different if you select the slave servo of a split axis. Figure 15A.16 Axis Monitor Screen

AXIS MONITOR

X AXIS [ MM ]

0.0000 0.0000

FOLLOWING ERROR DISTANCE TO MARKER

HM DIST

SETUP MODE

0.0120

HM TOL

0

COMMANDED TORQUE

%

SPINDLE DAC COMMAND

0.075

IN-POSITION MARKER FOUND

0

X AXIS

Y AXIS

Z AXIS

S1

S2

When the Axis Monitor screen first appears, axis 1 data is displayed. Axes are displayed with the axis names assigned to them in AMP. Spindles are shown after all configured axes. Press the appropriate softkey at the bottom of the screen. Only servos that have been configured in AMP will have softkeys available. If the axis is an adaptive depth probe, only the following error and probe position is shown. The position display for an adaptive depth probe shows the probe position relative to the zero point established either through PAL or at power up. The following error display shows following error on the adaptive depth probe.

15A-36

Page 747

Section 15A Troubleshooting the Control

When the probe is not fired, the following error magnitude equals the probe deflection from the probes zero point. Once the probe is fired, the following error shows: - the actual following error for the adaptive depth probe axis if the probe is AMPed to close the position loop for another axis. - the probe deflection relative to the probes zero point if the probe is not AMPed to close the position loop for another axis. Important: The following error display is invalid for the block that initially fires the adaptive depth probe, and the block that pulls out of the hole releasing the adaptive depth probe. The distance to marker value for the spindle is updated in both open- and closed-loop spindle operation. The following error is updated only during closed-loop spindle operation. Information for spindle servos following error is valid only when the spindle is in one of these closed-loop modes: orient solid tapping virtual C The control does not cancel following error when a spindle transitions from closed-loop mode to open-loop mode. The axis units of INCH, MM or DEG are displayed after the axis name.

15A-37

Page 748

Section 15A Troubleshooting The Control

Beneath the servo name are several rows of servo data. This data is displayed: FOLLOWING ERROR

This indicates the following error in inches, millimeters or degrees.

DISTANCE TO MARKER

This indicates the distance from the current axis position to the nearest encoder marker in inches or millimeters. The display rolls over at 1/2 the distance between markers. At this rollover point, the display switches sign depending on the direction of rotation. At the actual marker, the display reads zero.

HM DIST

This value is the distance to the marker calculated when the axis stopped after the home switch went false, during the last home operation. Value is in this axis’s programming units. If the axis does not requrie homing , or if a “switchless”home was executed on this axis, a value of 0.0 will be displayed. Only visable for servo AXES.

HM TOL

This is a static display of the value set in AMP to detect a home tolerence error. A value in the “HM DIST” larger than this limit indicates that an error has occured.

COMMANDED TORQUE

This is the torque output being commanded to the motor for the axis being monitored. It is expressed as a percentage of rated torque (0 to 300%) defined in AMP as the torque limit for that axis. The sign indicates the direction of commanded torque. This value is also available in PAL. Refer to $TORQ.

SPINDLE DAC COMMAND

This is an integer number reflecting the digital output to the DAC. The same value is displayed for every axis (except the split axis slave servo). Only visable for “spindls”. This value is calculated as follows: [Voltage at Max for Gear n ][ Commanded RPM ] x 4096

_____________________________________________________________ [ Maximum Spindle Speed - Gear n ] x 10

[Voltage at Max for Gear n ] and [ Maximum Spindle Speed - Gear n ] are AMP parameters. SKEW

Skew data is only displayed on the axis screen of a split axis slave servo. The value shown here as skew indicates the difference in following error between the split axis master servo and the split axis slave servo.

The status of the following error and the distance from marker/null are displayed in the lower right corner of the screen. It is displayed as one of the following: IN-POSITION

The absolute value of the following error is less than the value of the INPOSITION BAND parameter.

< FEEDRATE SUPPRESSION

The absolute value of the following error is greater than the value of the INPOSITION BAND parameter, but is less than the value of the FEEDRATE SUPPRESSION POINT parameter.

> FEEDRATE SUPPRESSION

The absolute value of the following error is greater than the value of the FEEDRATE SUPPRESSION POINT parameter.

EXCESS ERROR

The absolute value of the following error is greater than the value of the EXCESS ERROR parameter.

The status of the distance from marker/null is displayed as either:

15A-38

Page 749

Section 15A Troubleshooting the Control

MARKER NOT FOUND

The axis has not yet encountered an encoder marker/null.

MARKER FOUND

The axis has encountered an encoder marker/null since last reset or power up.

The status of the distance from marker/null is reset whenever there is a loss of feedback or power to the control. These are real time displays, response is limited only by delays in screen updates. Pressing the exit softkey (up arrow) at any time displays the Main Diagnostics Menu screen. When you use the Axis Monitor screen during solid tapping, the position loop type, gain, and acceleration ramp of the AMPed tapping axis matches that of the spindle. This may result in a monitored following-error magnitude for these two axes that is different while in solid-tapping mode. When they are not in solid tapping mode the monitored following-error magnitude for these axes is the same.

15A.7.2 1394 Drives Diagnostics Screen

If you are starting up a 9/440 system, the following screen is available to help you determine what servo faults, if any , exist on your system prior to attempting to run the machine. Select the [1394 DRIVE] softkey under the [MONITOR] section of the [SYSTEM SUPPORT] softkey. (softkey level 3) RING I/O

REMOTE I/O

FAST I/O

AXIS SERIAL MONTOR I/O

(softkey level 3) DATA SEARCH 1394 SCOPE MONTOR DRIVE

15A-39

Page 750

Section 15A Troubleshooting The Control

Figure 15A.17 1394 Drive Diagnostics Screen System Module Faults

1394 DRIVES SYSTEM MODULE STATUS BUS VOLTAGE (Low/hi/OK) ___v TEMPERATURE (ok FLT) PHASE LOSS (OK/FLT GROUND FAULT(OK/FLT)

1394-0-0 SME0 SHUNT TIMEOUT (OK/flT) OVERCURRENT (OK-FLT) PRECHARGE (OK/FLT) SHUNT UTIL XX % REGEN UTIL XX %

AXIS MODULE STATUS

Axis Module Slot Number

GRND FLT

OVER CRNT

BUS FLT

OVER TEMP slot 1

OK/FLT

OK/FLT

OK/FLT

OK/FLT

Slot 2

OK/FLT

OK/FLT

OK/FLT

OK/FLT slot 3

OK/FLT

OK/FLT

OK/FLT

OK/FLT slot 4

OK/FLT

OK/FLT

OK/FLT

OK/FLT

The following table lists the axis module and system module faults that can be shown on this screen and gives a description of each. Note that those items designated with a “**” in this table are only shown if the smart power (or Series C ) 9/440 hardware is being used in your system. On all other systems these areas of the screen are left blank.

15A-40