Page 751
Section 15A Troubleshooting the Control
Faults Axis Module
CNC display: Error Message Description
GRND FLT
Axix Module PowerFault (0:1,2,3,4)
OVER CRNT
BUS FLT
OVER TEMP 1
The axis module hardware has faulted from a short duration over current condition. If the output current exceeds a fixed level (Over 200% of axis module rating for the 10 and 15 Kw modules and Over 300% for the 2, 3 and 5 Kw modules) this fault will appear. Typical causes are a shorted lead, motor malfunction, or malfunctioning power IGBTs. Axis Module OverCurrent (0:1,2,3,4) This axis module of your 1394 system has been requested to provide too much current over an extended time period. This is typically caused by: Accel/Decel command from the CNC is requiring peak current for an excessive amount of time, the machine friction or inertial/viscous load is excessive, the motor has been improperly sized, a short circuit exists across the drive output terminals, logic supply circuits have malfunctioned, or AC input is incorrectly wired. Axis Module Buss Voltage Loss (0:1,2,3,4) The DC bus supply to the axis module was lost or has fallen below 275VDC. Check slider connections/termination strip or there could be a blown link fuse. This condidtion also occurs in a systemE- stop state. Axis Module OverTemp (0:1,2,3,4) The 1394 axis module contains a thermal sensor which senses the internal ambient temperature. Causes could be: that the cabinet ambient temperature is above the 70 degree C rating. The machine duty cycle requires an RMS current exceeding the continuous rating of the axis module. The airflow access to the 1394 is limited or blocked.
Faults System Module
CNC Display error message Description
BUSS VOLTAGE ____
HIGH : System Module Over Voltage (0) The 1394 system module bus voltage exceeds the maximum operating voltage. The DC power bus is continuously monitored. If it exceeds a preset level (810 Vdc), an over voltage fault is sensed and the axis modules are disabled. This can be caused by an under sized shunt requirement, shunt regulator fuse has blown, the shunt regulator transistor has malfunctioned, the power driver board is malfunctioning and incorrectly sensing the bus voltage, the CNC acc/dec rate is incorrectly set, the input line voltage is excessive, the system inertia is too high causing excessive energy to be returned to the power supply bus, or a vertical axis with insufficient counterbalancing is overdriving the servomotor and causing excessive energy to be returned to the power supply bus. LOW : System Module Under Voltage The 1394 system module voltage does not meet the minimum operating voltage. The DC power buss shall activate the under voltage limit when the bus drops to 275 VDC or less. It will clear at 300 Vdc. Typical causes include low voltage on the three phase input. If any Phase is missing, the “PhaseLoss”message will take priority.
BUSS VOLTAGE ____
VALUE : Displays the value of the DC buss voltage in DC volts. Nominal normal voltage is 600 V
15A-41
Page 752
Section 15A Troubleshooting The Control
TEMPERATURE System Module Over Temperature 1
The 1394 contains a thermal sensor which senses the internal ambient temperature. Causes could be that : The cabinet ambient temperature is above the 70 deg C rating. The machine duty cycle requires an RMS current exceeding the continuous rating of the controller. The airflow access to the 1394 is limited or blocked. An axis module or a system module FAN has failed.
PHASE LOSS system Module Phase Loss (0) The 1394 system module has detected a loss of one of the input power phases. The three- phase input line is monitored and a fault will be issued when a phase loss is detected. Typical causes include, one, two or all three of the input line fuses have opened, contactor malfunction, or incorrect wiring.
GROUND FAULT
System Module Ground Fault (0)
SHUNT TIMEOUT **
System Module Shunt timeout (0)
The 1394 system module has detected a ground fault. The system generates a ground fault when there is an imbalance in the DC bus of greater than 50 A. This drive error can be caused by incorrect wiring (verify motor and ground wiring), motor malfunction, or an axis module IGBT malfunction, or a short to ground The shunt resistor has timed out due to an amount of regeneration energy produced by the motor exceeding the limit of the shunt resistor by more than 5%. You may require a properly sized shunt, modification of the duty cycle of the application, or the addition of an external shunt for additional capacity.
OVER CURRENT **
System Module Current Limit (0)
PRE CHARGE **
System Module Pre- Charge (0)
SHUNT UTIL ** value
Shunt resistor utilization percentage. This is a display of the amount of heat (current) that the shunt resistor has absorbed. A value approaching 100% indicates that the shunt resistor is saturated and will not be able to sustain further dynamic use.
REGEN UTIL ** value
Regeneration unit utilization percentage. This is a display of the amount of heat (current) dissipation that the regeneration electronics have absorbed. A value approaching 100% indicates that the regen electronics are becoming saturated and will not be able to sustain further dynamic use.
The system module has reached the limit of its current capabilities. The total motoring and regeneration current produced has exceeded the current capability of the system module by 5% or more. You may need to reduce the acc /dec profiles or increase the size of the system module. The DC bus voltage did not rise to operating levels (285 V) within .5 sec after 3 phase power was applied to the system. This can occur if : a short is detected on the DC bus . An axis is enabled before the pre- charge check is complete, or if torque is commanded before full bus voltage is present.
1 Over Temperature Indicators are for the system module and axis modules only. They do not reflect any motor over temperatures that may occur. Motor thermal switches (if available) should be wired into the E-STOP string.
15A-42
Page 753
Section 15A Troubleshooting the Control
15A.8 Serial I/O Diagnostics
When the {SERIAL I/O} softkey is pressed on the Main Diagnostics Menu screen, the Serial I/O diagnostics screen appears. “SERIAL I/O” appears on the top line of the screen, along with the “SETUP MODE” message indicating that the control is in setup diagnostics mode. Important: If ports A and B are both currently communicating with a peripheral, pressing the {SERIAL I/O} softkey displays the message “BOTH PORTS ARE BUSY” on the operator panel CRT. This softkey is disabled until the ports are no longer communicating. Figure 15A.18 below shows a typical Serial I/O screen. Figure 15A.18 Serial I/O Diagnostics Screen
SERIAL I/O SERIAL PORT: DEVICE: PORT TYPE BAUD RATE: PROTOCOL: PARITY: STOP BITS: DATA LENGTH: TIMEOUT: OUTPUT CODE;
SETUP MODE A ALLEN-BRADLEY 1770-SB RS232C 1200 LEVEL 2 NONE 1 8 15 SEC N/A
RECV RECV XMIT XMIT PORT A PORT B PORT A PORT B
Important: If port B is configured for ODS communication, the {RECV PORT B} and {XMIT PORT B} softkeys are not be displayed. This prevents the user from using port B when the control is communicating with ODS. When any of the 4 (or 2) softkeys displayed on the Serial I/O diagnostics screen is pressed, a screen similar to that in Figure 15A.19 is displayed:
15A-43
Page 754
Section 15A Troubleshooting The Control
Figure 15A.19 Serial I/O Diagnostics Screen
SERIAL I/O SERIAL PORT: DEVICE: PORT TYPE BAUD RATE: PROTOCOL: PARITY: STOP BITS:
START
SETUP MODE A ALLEN-BRADLEY 1770-SB RS232C PIN INP 1200 LEVEL 2 4 RTS NONE 5 1 6
STOP
OUT
CTS DSR
REPEAT SINGLE XMIT XMIT
The serial I/O parameters shown will vary for each peripheral device. If the parameters displayed for a specific peripheral device do not match the default parameters for that device, the message “PARAMETERS DO NOT MATCH THE DEFAULTS” are displayed on the screen. If the protocol parameter is set to LEVEL_1, RAW, or DF1, pressing the {START} softkey will highlight the CTS output signal. Pressing the {STOP} softkey changes the CTS output signal back to normal display. If the protocol parameter is set to LEVEL_2 and the control is receiving data, pressing the {START} softkey displays DC1 on the screen. Pressing the {STOP} softkey displays DC3. If the protocol parameter is set to LEVEL_2 and the control is transmitting data, pressing the {START} softkey displays DC2 on the screen. Pressing the {STOP} softkey displays DC4. Important: For more information on protocol, refer to page 8-9. When the {REPEAT XMIT} softkey is pressed, the control highlights this softkey and transmits a string of characters that corresponds to last key pressed on the operator panel keyboard. Pressing any of the softkeys stops transmission.
15A-44
Page 755
Section 15A Troubleshooting the Control
When the {SINGLE XMIT} softkey is pressed, the control highlights this softkey and transmits the character that corresponds to last key pressed on the operator panel keyboard. Pressing any of the softkeys stops transmission.
15A.9 Data Scope Monitor
Use the data scope monitor feature to debug communications. To access the data scope monitor screen, shown in Figure 15A.20: 1.
Press the [SYSTEM SUPORT] softkey: (softkey level 1)
2.
PRGRAM OFFSET MACRO MANAGE PARAM
PRGRAM SYSTEM CHECK SUPORT
FRONT PANEL
SWITCH LANG
ERROR PASSMESAGE WORD
Press the [MONITOR] softkey: (softkey level 2)
3.
PRGRAM AMP PARAM
DEVICE MONISETUP TOR
PTOM SI/OEM
SYSTEM TIMING
TIME PARTS
Press the [DATA SCOPE] softkey. (softkey level 3) RING I/O
REMOTE FAST I/O I/O
AXIS SERIAL MONITOR I/O
DATA SCOPE
4.
Press either [PORT A] or [PORT B] depending on what port your device is connected to. (softkey level 4) PORT A PORT B
15A-45
Page 756
Section 15A Troubleshooting The Control
Figure 15A.20 Data Scope Monitor for Communication Diagnostics Default AMP Loaded
Data transmitted appears in standard video.
Transmit
E-Stop Serial Port: B
Receive
Data received appears in reversed video.
This is a 80-column screen.
FREEZE
UN FREEZE
CLEAR
Important: The keyboard is inactive during a PAL download; therefore, you cannot stop or freeze data on the screen while downloading PAL. Communication data is shown in hexadecimal form with two characters used for each communication byte. Data is continually overwritten in the display area. The position on the screen where the next data byte will be written is indicated by a blinking, block cursor. You have these softkey choices: FREEZE -- only the data scope display is frozen; no interruption of communication occurs. This means that while the display is in “freeze,” communication data is lost. UNFREEZE -- begins display of real time communication data from the current cursor position. CLEAR -- erases the displayed data and positions the cursor to the upper left of the display area; no data is lost.
END OF SECTION
15A-46
Page 757
Section
15B
Replacement Procedures
15B.0 Section Overview
This section covers replacement procedures for the components in your system. It also contains the procedure for updating your executive software. For Information on:
See Page:
Updating the Executive Firmware
15B-2
Replacing the Lithium Battery (8520-LIBAT)
15B-8
Replacing the CPU Board on the 9/260 and 9/290
15B-10
Replacing the Motherboard on the 9/260 and 9/290
15B-13
Replacing the Processor Board on the 9/230
15B-15
Replacing the Main Power Supply on the 9/260 and 9/290
15B-22
Replacing the Main Power Supply on the 9/230
15B-23
Replacing the Monochrome CRT
15B-25
Replacing the Color CRT
15B-25
Replacing the Keyboard Assembly for the Monochrome Operator Panel
15B-26
Replacing the Keyboard Assembly for the Color Operator Panel
15B-27
Replacing the I/O Interface for the Keyboard
15B-27
Replacing the Fuse in the Monochrome CRT
15B-29
Replacing the Fuse in the Color CRT
15B-30
Replacing the Power Supply for Monochrome Operator Panel
15B-31
Replacing the Power Supply for Color Operator Panel
15B-31
Replacing the Rotary MTB Panel
15B-32
Replacing the Push-Button MTB Panel
15B-33
Replacing the Push-Button Light Bulbs
15B-34
Replacing the Hand Pulse Generator and Interface Board
15B-36
Replacing the Battery Backup for Absolute Encoders on the Digital Servo Module
15B-37
Replacing the Digital Servo Module
15B-38
Replacing the Digital Servo Amplifier
15B-40
Replacing the Logic Board on the Digital Servo Amplifier
15B-41
Replacing the Power Section on the Digital Servo Amplifier
15B-42
Replacing the Optional Feedback Module
15B-43
Replacing the Analog Servo Module (9/260 and 9/290)
15B-44
Replacing an Analog Servo Amplifier
15B-46
Replacing the Rotary MTB Panel I/O Module
15B-47
Replacing the Push-Button MTB Panel I/O Module
15B-49
Replacing Digital I/O
15B-50
Replacing the Power Fuse on Digital I/O and Analog I/O
15B-52
Replacing the High Density I/O
15B-53
Replacing the Analog I/O
15B-54
15B-1
Page 758
Section 15B Replacement Procedures
15B.1 Updating the Executive Firmware
Replacing the Removable Operator Panel (ROP) Interface Module
15B-55
Replacing the ROP Module in the Removable Operator Panel Interface Assembly
15B-56
Replacing the Removable Operator Panel CRT or Keyboard Assemblies
15B-57
Replacing the 9/440 System Module or CNC Assembly
15B-58
Replacing the 9/440 E- Stop String Fuse
15B-60
As we release new versions of executive software for your control, you will have to install the new software. For the 9/230, 9/260 or 9/290 the executive software updates come to you on 3 1/2-inch floppy disks. You can install the executive software update on an: Allen-Bradley T35, T45, T47, T50, or T60 with MS-DOS 3.3 or greater installed IBM XT/AT personal computer or 100% compatible with MS-DOS 3.3 or greater installed When you install the update, it uses an external drive for the update, and an internal drive for a scratch directory. The update requires about 2 MB of disk space. In this procedure, all variables that are entered by the control during installation are in italic. Important: Installing the executive firmware can delete all battery backed up memory, AMP, and PAL. Make sure you have all necessary information backed up before you re-install the executive software.
15B-2
Page 759
Section 15B Replacement Procedures
To install the executive software follow this procedure: 1.
At the external drive prompt, insert the disk labeled A into your external drive and type update source: destination: <dir> where: source = source drive destination = destination drive dir = optional directory name that will be created on destination drive: For example when you type: update a:d:
This screen appears: * * *
******************* Update Utility Revision 2.0 Allen-Bradley Company, 1992
* * *
*******************
This utility will update the executive software on your 9/230, 9/260 or 9/290 CNC.
It will use drive “a:” as the source of the update, and drive “d:” for a scratch directory, “$update$”, which will be removed upon completion of the utility. A description of the update process can be found in the file “a:\read.me”. If you have not already reviewed this file, you should consider doing so before proceeding. Continue (y/n)?
2.
If you answer the prompt with an N you return to the DOS prompt. If you answer with a Y, this screen appears: 2Mb bytes of disk space are needed. Drive d: has 2736128 bytes available. This is enough to continue... The system will now be copied from drive a: to the scratch directory d:\$update$. You will periodically be requested to change floppy disks as the entire set is copied to the hard disk Strike any key when ready....
15B-3
Page 760
Section 15B Replacement Procedures
3.
When you press a key, this screen appears: Copying... Insert backup diskette 01 in drive A: Strike any key when ready
4.
Insert the next disk and strike a key when the update prompts you to do so. If you have additional disks in your update package, repeat this step for those disks. The screen may display more files being read by the computer than shown here. When prompted, strike any key. Copying... Insert backup diskette 01 in drive A: Strike any key when ready *** Files were backed up 12-31-1999 *** *** Resstoring file from drive A: Diskette: 01 \SYS0201.ZIP
5.
PC Screen
When you press a key, these screens appear. When decompression is complete, power down the control and connect the RS-232 cable as instructed on the screen. Control Screen
Copying is complete. The system file was compressed on floppy disk to conserve storage space, and minimize the number of required disks.
Informative Messages Connected to Host
It must now be decompressed. Decompressing is complete In order to download the system updates, the CNC and PC must first be connected. Power down the CNC. Connect the RS-232 cable from CNC port B to PC port COM1. Then restart the CNC. Press a key when ready...
15B-4
Error Messages