Page 829

Section 16 Error and System Messages

Message

Description

CPU #2 EXEC WILL NOT START

CPU #2 is halted and will not start to execute its exec (9/290 only). Consult Allen-Bradley customer support services.

CPU #2 HARDWARE ERROR #2

The 68030 main processor has detected a bus error. Consult Allen-Bradley customer support services (9/290 only).

CPU #2 HARDWARE ERROR #3

The 68030 main processor has detected a spurious interrupt. Consult Allen-Bradley customer support services (9/290 only).

CPU #2 HARDWARE ERROR #4

The 68030 main processor has detected an illegal address. Consult Allen-Bradley customer support services (9/290 only).

CPU #2 HARDWARE ERROR #6

The 68030 main processor has detected a privilege violation. Consult Allen-Bradley customer support services (9/290 only).

CPU #2 HARDWARE ERROR #8

CPU #2 has detected an unassigned vector interrupt. Consult Allen-Bradley customer support services (9/290 only).

CPU #2 HARDWARE ERROR #9

CPU #2 has detected an illegal instruction. Consult Allen-Bradley Customer Support Services (9/290 only).

CPU #2 LOCAL RAM FAILED

The RAM memory supporting the 68030 I/O ring processor has failed (Z80 I/O ring processor on 9/240 only). Consult Allen-Bradley customer support services.

CPU #2 PROM HAS FAILED

The PROM memory supporting the 68030 (Z80 9/240 only) I/O ring processor has failed its checksum test. Consult Allen-Bradley customer support services.

CPU #2 RAM HAS FAILED

The RAM memory supporting the 68030 (Z80 9/240 only) I/O ring processor has failed. Consult Allen-Bradley customer support services.

CPU #2 WATCHDOG ERROR

The 68030 (Z80 9/240 only) I/O ring processor has failed. Consult Allen-Bradley customer support services.

CREATING BACKUP FILE - PLEASE WAIT

A backup file for the current utility is being created. The message will clear when the backup is complete.

CREATING TOOL OFFSET FILE - PLEASE WAIT

The tool offset table (or tables) is currently being backed-up. The control is generating an executable G10 program and entering it into the control’s program directory.

CREATING TOOL MGMT. FILE - PLEASE WAIT

The tool management tables are currently being backed-up. The control is generating an executable G10 program and entering it into the control’s program directory.

CSS RPM LIMIT AUXILIARY SPINDLE 2

The aux spindle 2 RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CSS RPM LIMIT AUXILIARY SPINDLE 3

The aux spindle 3 RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CSS RPM LIMIT FIRST SPINDLE

The spindle 1 RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CSS RPM LIMIT PRIMARY SPINDLE

The primary spindle RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CSS RPM LIMIT SECOND SPINDLE

The spindle 2 RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CSS RPM LIMIT THIRD SPINDLE

The spindle 3 RPM requested by CSS is greater than the maximum CSS RPM limit. This limit is set by the system installer in AMP or can be reduced by programming a G92 block.

CUR LOOP G/A CLOCK LOST

This error was generated by a servo amplifier error. It can usually be corrected by turning off power to the amplifier, and then back on.

CURRENT FEEDBACK ERROR

The servo module has detected faulty or missing current feedback from the digital servo motor. The most likely cause of this error is be a broken or disconnected wire.

CURSORING NOT ALLOWED

While assigning a {CUSTOM TOOL} in {RANDOM TOOL}, you cannot cursor to select another tool position.

16-9

Page 830

Section 16 Error and System Messages

Message

Description

CUTTER COMP./TTRC INTERFERENCE

The cutter radius is too large, reverse motion is required, or some other cutter compensation interference exists. Either an alternate tool or an alternate tool path must be programmed. Another option would be to disable cutter compensation error detection.

CYCLE ALREADY ACTIVE

An attempt was made to start a cycle while another cycle was currently executing.

CYLINDER RADIUS IS ZERO

The cylinder radius was not programmed in a virtual C cylindrical interpolation (G16.1) cycle.

CYLINDRICAL AXIS NOT PRESENT

Cylindrical interpolation was programmed without at least one cylindrical interpolation axes present (rotary, park, or feed axes).

CYLIND/VIRTUAL CONFIGURATION ERROR

An axis configuration error was detected by the control when cylindrical interpolation or end face milling was requested in a program block. Some examples would include: A cylindrical/virtual axis is named same as a real axis or is missing (for example on a lathe A, the cylindrical axis may have been named the same as a incremental axis name). A cylindrical/virtual axis is named the same as another programing command (for example a secondary auxiliary word, the angle word, etc...).

D D-WORD IS GREATER THAN TOOL DIA.

The programmed D-word value is greater than the tool diameter of the current tool.

D-WORD IS LESS THAN AMP THRESHOLD

The D-word has been programmed with a value that is too small.

D-WORD OUT OF RANGE

More than 1000 auto-dress operations were specified by the D-word in a grinder fixed cycle.

DAC MONITOR CIPC ON

This message comes up on power-up, after patch AMP has been modified to invoke DAC monitoring of the coarse incremental position command.

DAC MONITOR F. E. ON

The axis-following error is being output to the DAC output port for monitoring and debugging. Turning parameters 86 or 87 ON through patch AMP enables this output.

DAC MONITOR FV ON

This message comes up on power-up, after patch AMP has been modified to invoke DAC monitoring of the fine interpolated final velocity for each fine iteration (20ms).

DAC MONITOR INTEGRATOR ON

This message comes up on power-up, after patch AMP has been modified to invoke DAC monitoring of the velocity error integrator accum.

DAC MONITOR VEL ERROR ON

This message comes up on power-up, after patch AMP has been modified to invoke DAC monitoring of the velocity error.

DAC MONITOR VELOCITY ON

The axis velocity command is being output to the DAC output port for monitoring and debugging. Turning ON parameters 86 or 87 through patch AMP enables this output.

DATA MAY BE OUTPUT TO PRINTER ONLY

The information being output by the control is intended to go to a printer. Make sure that the output port that is selected is properly connected to a printer and try again.

DATA STARVED

The control is waiting for the next program block to set up. Typically, this is the result of the control executing a part program faster than it can be read from a peripheral device such as a tape reader. This error often occurs immediately after the execution of several very short, rapidly executed blocks. To prevent this error from reoccurring, it is recommended that the program be loaded into control memory or to a faster peripheral device.

DECIMAL POINT ERROR

A word or parameter has been programmed with more than one decimal point.

DECIMAL POINT NOT ALLOWED

A word or parameter has been programmed with a decimal point when it can legally exist only as an integer value . For example, the number of repetitions (L) must be an integer value programmed without a decimal point.

DEFAULT AMP LOADED

This indicates that the default AMP values stored in the control’s executive memory have been activated. AMP in RAM and AMP in Backup memory were either unavailable or corrupt. This message can also occur if the battery backup fails.

DEFAULTS LOADED

The default device set-up parameters were loaded into the current device.

DEPTH > PROGRAMMED ENDPOINT

This error occurs during a threading cycle when the depth of the cut exceeds the programmed final depth of thread.

16-10

Page 831

Section 16 Error and System Messages

Message

Description

DEPTH PROBE AXIS MUST BE LAST

Adaptive depth probe is not AMPed as the last axis in the system. It must be AMPed after all normal axis and after the deskew slave and before any spindles. Refer to your AMP reference manual for details.

DEPTH PROBE AXIS NOT AMPED

A G26 (adaptive depth probe) move was programmed but no adaptive depth probe axis has been specified in AMP. Refer to your 9/Series AMP reference manual.

DEPTH PROBE FB GEARING NOT 1:1

The AMP configured gear ratio for the logical axis used as a depth probe must be a one to one ratio. “Reset Teeth on Motor Gear for Pos. FB”and “Teeth on Lead Screw Gear for Pos. FB”.

DEPTH PROBE TRAVEL LIMIT

The adaptive depth probe has moved to its AMPed travel limit. Note the value entered in AMP is the adaptive depth probe deflection from the PAL determined probe zero point. It may not be the actual total probe deflection.

DEPTH PROBE NOT SUPPORTED

A depth probe axis has been AMPed on an axis located on a servo card or a 9/230 that does not support the adaptive depth feature. (analog servo rev < rev 0.10 or 3 axis 9/260 9/290 digital servo cards)

DESKEW OPTION NOT INSTALLED

If the AMPed name specifying the deskew slave servo is not zero, or the AMPed name specifying the deskew master servo is not zero, and the option flag for deskew is zero, then the system is held in E-Stop.

DEVICE ALREADY OPENED

An attempt was made to open a device for download or upload from ports A or B when the device was already opened.

DEVICE NOT OPENED YET

The ready signal was not received when attempting to send data to or communicate with a peripheral device connected to communication ports A or B.

DIAMETER AXIS MISCONFIGURED

An invalid axis has been configured as the diameter axis.

DIRECTORY CHANGED TO MAIN DIRECTORY

When a password is entered that does not have access to the protectable part program directory and the protectable part program directory is currently selected, the control changes the selected directory to the main directory.

DISP SELECT NOT ALLOWED

You can not use the display select functions while the online PAL search monitor utility is active. Leave the search monitor utility before you try to select a display.

DIVIDE BY ZERO ERROR

A system software error has occurred. Consult Allen-Bradley customer support services.

(DO) NUMBER ALREADY USED

When executing a program, an attempt was made to activate a DO loop that has the same loop identifier (DO 1, 2, or 3) as an already active loop in the program. Provided they are not nested loops, the same loop identifier can be used more than once in a program .

(DO) RANGES INTERSECT

DO loops are improperly nested. A DO loop that is nested within another DO loop does not have an END command before the original DO loop END occurs.

DRESS CANCEL DEFERRED TO G40

The in- process dresser cannot be canceled (made inactive) while dresser/wheel radius compensation is active. If an attempt to cancel the in- process dresser is made, the control will postpone the request until dresser/wheel radius compensation is canceled with a G40 (note that M02, M30, and M99 can also cancel compensation).

DRESSER AXIS NOT ALLOWED

An attempt was made to program the dresser axis when the over the wheel dresser feature has been activated through PAL. You cannot program the dresser axis when the over the wheel dresser feature is active.

DRESSER FLANGE LIMIT REACHED

While dressing the grinding wheel the wheel size reached the entered flange limit. You should stop dressing the wheel before damage to the wheel flange occurs.

DRESSER MINIMUM LIMIT REACHED

The current dressing operation would dress the grinding wheel below the minimum wheel diameter as specified on the dresser status screen. This dressing operation will not be performed.

DRESSER MISCONFIGURED

One of the AMP parameters for the dresser axis has not been configured properly. Either the dresser axis, the vertical axis, or some other axis name is not a valid axis in the system. You must re-configure your AMP. Refer to your AMP manual for details.

16-11

Page 832

Section 16 Error and System Messages

Message

Description

DRESSER MIS-POSITIONED

Wheel re-enable was requested with IPD active and wheel is more than 4 inch-programming counts (hard-code amount) away from its previously active absolute position. Wheel dressing does not start.

DRESSER NOT INITIALIZED

This error is generated if an attempt is made to activate the in- process dresser before the dresser has been initialized through a wheel calibration operation.

DRESSER NOT/MIS CONFIGURED

The grinder over-the-wheel dresser feature issues this message when a wheel is initialized and the dresser parameters in AMP have been misconfigured. This message is issued when the dresser axis, dresser vertical axis, or dresser other axis has not been selected, or has been AMPed to have common axes, or has been AMPed to be a non-existent axis name.

DRESSER WARNING LIMIT REACHED

The axis specified as the dresser axis has been dressed smaller than the dresser warning limit value as specified on the dresser status page.

DRILL AXIS CONFIGURATION ERROR

The drilling axis is not a currently configured machine axis. On dual processing controls this message may result when the drilling axis is in another process. The drilling axis must be a configured axis in the current process and should not be the slave of a dual axis (drill axis should be the master axis for dual group). On machines with dual axes, this message can mean the axis configured in AMP as the fixed-drilling axis is a slave axis. The drill axis should be the master axis.

DUAL AXES MASTER&SLAVE PROCESS NOT SAME

When configuring a dual axis on a dual processing system, configure AMP so all axes in the dual axis group are in the same source process even if the dual axis group is shared.

DUAL AXES PARK LOGIC CANNOT CHANGE

An attempt was made, using dual axes, to change the current park status. At this point, the request will not be allowed.

DUAL GROUP AXES MUST HAVE SAME ROLLOVER

All rotary axes in a dual axes group must have the same rollover value. These rollover values are set in AMP.

DUAL LATHE-MUST USE PROCESS 1,2

Dual lathe must have the active processes be the first 2 available in AMP; 3 or 4 should not be configured as an active process.

DUAL MASTER&SLAVE RAD/DIAM CONFIG ERR

The slave of a dual group has been defined as a diameter axis. The OEM must define the master to be a diameter axis and the system will change the slave to be a diameter axis. When the group is decoupled the slave will continue to take on the master’s rad/diam traits.

DUAL PLANE CONFIGURATION ERROR

In AMP you have defined a plane with an axis and a master and a slave in the wrong order. For example: If the system has 4 axes YXZU and ZU are duals, if an AMPed plane is ZX, then UX can not be and AMPed plane. It must be XU (refer to your AMP reference manual for details).

DUAL SLAVE OR SPLIT AXIS NOT ALLOWED

Neither a dual slave, nor a split axis (deskew axis) may be programmed in a G24, G25, or G26 block.

DUALS CANNOT CHANGE OFFSETS IN CIRCULAR

An attempt was made, using dual axes, to account for an offset change in a circular move. Dual offset changes can only be made in linear blocks.

DUALS ONLY ALLOWING SINGLE AXIS HOME

An attempt was made to home multiple axes in a dual group when PAL only allows one axis at a time to be homed. PAL can be changed to allow homing of multiple axes in a dual group.

DUALPORT PTO TEST FAILED

The Dualport failed the diagnostic test and the bootstrapping operation is skipped. Consult Allen-Bradley customer support services.

DUPLICATE 1394 SLOT

The 1394 rack ID and slot number AMP entries are the same for two or more servos. Each axis module in a 1394 rack must have an individual address.

DUPLICATE 7300 PATTERN NAME

An attempt was made to enter a 7300 pattern name that already exists.

DUPLICATE DUAL MASTER NAMES

Both dual master axes names have the same letter.

DUPLICATE I/O RING DEVICE

Two or more of the same type of device on the I/O ring have the same device address switch setting.

DUPLICATE PROGRAM

An attempt was made to rename a program in control memory using the same program name (or number) of another program already in memory.

DUPLICATE PROGRAM NAME

An attempt was made to store or copy a program in control memory using the same program name (or number) of another program already in memory.

16-12

Page 833

Section 16 Error and System Messages

Message DWELL VALUE NOT PROGRAMMED

Description A G04 Dwell or a parameter requesting a dwell at hole bottom in a fixed drilling cycle was programmed with no value assigned to the length of the dwell.

E (E) AND (F) IN SAME BLOCK

In a G32 block (Lathe A) or G33 block (Lathe B & C), both leads were programmed in the same block.

EMPTY PROGRAM WAS DELETED FROM DIRECTORY

The current program being edited was saved and contained no program blocks. This program was deleted from the control’s program directory.

ENCODER QUADRATURE FAULT

An error has been detected in the encoder feedback signals. Likely causes are excessive noise, inadequate shielding, poor grounding, or encoder hardware failure.

END OF FILE

When transferring a file over the serial port, the control has reached the last block in the program.

END OF PROGRAM

When displaying a part program on the CRT, the control has reached the last block in the program.

END OF PROGRAM REACHED

When performing one of the program search features, the control has reached the last block in the program.

ENTER ALL REQUIRED PROMPT DATA

An attempt was made to create a transfer line part program from the quick view screen without entering all the required quick view screen prompt data. Optional data is shown in reverse video.

ENTRY OUT OF RANGE

A parameter value was entered that is larger or smaller than the usable range determined in AMP or allowed on the system.

ERASE PROMPT

The operator has data on the input line (line 2 of the CRT) that must be cleared or entered so that a new prompt can be displayed on the input line.

ERROR ACCESSING PROGRAM

A major software error was generated by the control’s internal software when editing the program; the program should be deleted. If the error persists, contact Allen-Bradley customer service support.

ERROR FOUND

A QuickCheck syntax check operation has found an error in the currently displayed program block. This is the block after the block containing the block-completed symbol “@”. Press <CYCLE START> to continue the program check.

ERROR IN CIRCLE DATA

This error can occur when digitizing a circular block, typically the result of entering positions that cannot be correctly connected with an arc.

ERROR LOOKING FOR (END) COMMAND

The control has found a paramacro END command that does not match one of the active paramacro DO loop ranges.

ERROR TRANSFERRING PAL TO CPU #2

An error occurred while PAL was being transferred to the I/O CPU at power-up. PAL is transferred to the I/O CPU at power-up on a 9/290. Consult Allen-Bradley customer support services.

EXACTLY 2 DIGITS MUST FOLLOW DECIMAL PT

You have used incorrect search string syntax in the PAL search monitor utility.

EXCESS FOLLOWING ERROR

The following error for an axis exceeds the allowable value as defined in AMP. Most likely cause is AMP servo related parameters are set too stringently for the hardware. Also caused by axis runaway.

EXCESS SKEW ON

The calculated skew is larger than the AMPed maximum allowable skew.

EXEC BOOTSTRAP FAILED

The bootstraper failed to respond within the specified time for any code segment. Consult Allen-Bradley customer support services.

EXPRESSION INCOMPLETE

A syntax problem has been found in a paramacro expression. The control is unable to correctly evaluate the expression as entered.

EXTRA DATA IN INTERRUPT MACRO BLK

An attempt was made to program extra data (such as a G-code) in the M-code block that activates or deactivates an interrupt program. No extra commands can be programmed in this block.

16-13

Page 834

Section 16 Error and System Messages

Message

Description

EXTRA DATA IN QPP BLOCK

The QuickPath Plus block has been programmed with too many parameters. For example, you cannot program a G13 block with both axis data and an angle word or with an L or A word in the block.

EXTRA I/O RING DEVICE

An I/O device that has not been defined in the I/O assignment file is physically present on the I/O ring.

EXTRA KEYBOARD OR HPG ON I/O RING

The control detected a keyboard or HPG on the 9/Series fiber optic ring that was not configured as a ring device. The I/O ring will still function and the control will NOT be held in E-Stop. You may also use the keyboard or HPG by selecting it as the active device via the corresponding PAL flags. You should configure the keyboard or HPG with the I/O assigner utility (See your 9/Series PAL reference manual for details).

F FCM DUALPORT RAM FAILURE

The FCM detected an error in dualport RAM.

FCM FLASH RAM FAILURE

The FCM detected an error in flash RAM.

FCM LOCAL RAM FAILURE

The FCM detected an error in local RAM at power-up or during the runtime diagnostics.

FCM PLUG CONFIGURE FAILED

The FCM card failed to configure correctly.

FCM PLUG FAULT

The plug on the FCM detected an error.

FCM PLUG NEGOTIATE FAILED

The FCM firmware could not communicate with the plug.

FCM POWER UP SEQUENCE FAILURE

Power-up failed. Try again. If error appears again, contact your Allen-Bradley sales representative.

FCM REVISION CHECK FAILURE

Revision on module is out-of-date. Contact Allen-Bradley sales representative to get latest revision of the module’s firmware.

FCM ROM FAILURE

The FCM detected an error in ROM during runtime diagnostics.

FCM SHADOW RAM FAILURE

The FCM detected an error in shadow RAM.

FCM SPURIOUS INTERRUPT

A spurious interrupt occurred on the FCM card.

FCM VRTX ERROR

A call from VRTX from the FCM card firmware returned an error.

FCM WATCHDOG

The watchdog on the FCM card timed out.

FDBK NOT AVAILABLE ON 4TH AXIS OF BOARD

An attempt was made to receive feedback from the axis that is configured as the fourth axis on a servo board. You can only receive feedback from the first three axes on a servo board.

FEEDBACK DISCONNECTED

The control has detected a loss of feedback from the encoder. The most likely cause of this error would be a broken or disconnected wire. Axis homing will be required after the error condition is corrected.

FEEDBACK OPTION NOT INSTALLED

A PTO check determines the legal number of axes.

FEED AXIS DATA NOT PROGRAMMED

Feed axis data required during a grinder fixed cycle was not programmed.

FEED AXIS MOTION NOT ALLOWED

During Virtual C programming, no axis motion is allowed on the axis specified as the feed axis in AMP.

FEED TO HARDSTOP PROGRAMMING ERROR

No axis, or more than one axis, was programmed in a G24 block. Or the programmed axis integrand was not programmed in the block.

FILE CANNOT BE CONVERTED TO EIA FORMAT

The file requested to be output to a device has characters that cannot be converted to EIA.

FILE DOWNLOAD COMPLETE

Status message that means the download has completed.

FILE DOWNLOAD ERROR

Check file download and file download configuration screens to make sure all fields are entered correctly.

FILE DOWNLOAD IN PROGRESS

This status message means a file is being downloaded.

FIXED CYCLE ALREADY ACTIVE

You cannot program a fixed cycle with a fixed cycle already active.

FIXED CYCLE PROGRAMMING ERROR

A fixed cycle has been programmed incorrectly. Verify that the correct parameters have been used and that parameters restricted to integer or positive values are programmed as such.

16-14

Page 835

Section 16 Error and System Messages

Message

Description

FLASH IN USE - TRY AGAIN LATER

Only one task is allowed to write flash at a time. If a second task requests a flash write, you will see this message.

FLASH SIMMS ARE NOT INSTALLED

Install the flash SIMMs into the 9/Series mother board. Flash SIMMs must be installed. If a repaired system is being installed, you should have saved your flash SIMMs for re-installation before making the return.

FLASH SIMMS CONTAIN INVALID DATA

Flash SIMMs have become corrupted probably from a communication error during a system update. Retry the system executive update utility. If the situation persists, contact Allen- Bradley support.

FLASH SIMMS U10 AND U14 ARE EMPTY OR MISSING

Make sure your flash SIMMs are installed in the correct tracks. Refer to the 9/Series integration and maintenance manual section covering your processor for details on flash installation. Remove and reseat flash SIMMs.

FLASH SIMM U10 IS EMPTY OR MISSING

Make sure your flash SIMMs are installed in the correct tracks. If they appear to be installed correctly, remove and reseat SIMMs. If problem persists, contact Allen- Bradley support service.

FLASH SIMM U14 IS EMPTY OR MISSING

Make sure your flash SIMMs are installed in the correct tracks. If they appear to be installed correctly, remove and reseat SIMMs. If problem persists, contact Allen- Bradley support service.

FLASH WRITE ERROR

A problem occurred while writing to flash, for example bad flash, no flash, or no voltage.

FOREGROUND OVERLAP

The foreground tasks did not complete execution within the 20-millisecond period allocated. Foreground tasks include PAL foreground, axis interpolation, servo interface, and I/O ring scanning. Correct by reducing PAL foreground program size or removing some devices from the I/O ring. G

G10 NOT ALLOWED DURING CYCLE

G10 code is not allowed to be used during the cycle. Cancel the fixed cycle.

G24 NOT ALLOWED

G24 is not allowed when any automatic G coded cycle is active (such as G81).

G24 PLANE INCOMPATIBILITY

The hard stop axis may not be in the active part rotation plane.

G25 NOT ALLOWED

G25 is not allowed when any automatic G coded cycle is active (such as G81).

G25 PLANE INCOMPATIBILITY

The adaptive feed axis may not be in the active part rotation plane.

G26 NOT ALLOWED

G26 (adaptive depth probe) can not be programmed when another modal group is active (such as a G81 fixed cycle).

G26 PLANE INCOMPATIBILITY

A conflict between a plane dependent feature and a G26 (depth probe). For example if part rotation is active and a G26 is programmed on an axis in the part rotation plane this error is generated. Refer to the 9/Series users manual section on G26 for details on incompatible planar features.

G28 BLOCK DOES NOT PRECEDE G29 BLOCK

A G29 block was programmed before a G28 block. During 7300 tape compatibility mode, the first automatic threading block must contain a G28 code; the next block must contain a G29 code.

G29 BLOCK DOES NOT FOLLOW G28 BLOCK

A G28 block was programmed without a following G29 block. During 7300 tape compatibility mode, the first automatic threading block must contain a G28 code; the next block must contain a G29 code.

G40 NOT ALLOWED IN CIRCULAR

An exit move from cutter compensation or TTRC was attempted in a circular block (G02 or G03). An exit move (programmed with a G40) must generate a linear move.

G53 NOT ALLOWED IN G91 MODE

An attempt was made to make an incremental move in the machine (absolute) coordinate system. Only absolute moves (G90) are permitted in the machine coordinate system.

G53 NOT ALLOWED IN INCREMENTAL MODE

A G53 move to absolute position was requested while in incremental mode.

G53 ON AN UNHOMED AXES

An attempt to program a move in the machine (absolute) coordinate system was made before the axis was homed. It is necessary to home the axes to establish the location of the machine coordinate system.

16-15

Page 836

Section 16 Error and System Messages

Message

Description

G91 MODE NOT ALLOWED IN QPP

Since QuickPath Plus is generally used to program blocks without knowing the intersection of the blocks, it is impossible to calculate a location for the end-point of the block when the move is incremental. QuickPath Plus must be programmed in absolute mode (G90).

(G-CODE) TABLE ERROR

There has been an internal software fault relative to the G-code table. Consult Allen-Bradley Customer Support Services.

(GOTO) SEQ. NUMBER NOT FOUND

The sequence number (N word) called by a GOTO command does not exist in the currently executing program.

GRAPHICS ACTIVE IN ANOTHER PROCESS

Graphics can only be active in one process at a time. You must turn graphics off in one process before you can activate them in another process.

H HARD STOP ACTIVATION ERROR

An attempt was made to (G24) hard stop an axis while a different axis was already holding against a hard stop.

HARD STOP AND/OR ADAPTIVE DATA CONFLICT

An attempt was made to create a transfer line part program from the quick view screen entering data for both hard stop (G24) and adaptive depth features (G26). You can select only one of these features.

HARD STOP AXIS NOT ALLOWED IN INTERRUPT

An axis which is still hard-stopped due to a previous G24 block may not be moved by any block inside an interrupt macro program.

HARD STOP DETECTION ERROR

A hard stop (G24) was detected outside of the programmed hard stop region. Or a hard stop was not detected before the hard stop axis reached its endpoint.

HARD STOP DIRECTION ERROR

The axis currently holding against a hard stop (G24) was programmed with a move further into the hard stop. You must program the move away from the hard stop in the direction opposite to the direction used to place the axis at the hard stop.

HARD STOP EXCESS ERROR

The hard stop axis (G24) was moving too fast when it encountered the hard stop. You must reduce the axis feedrate before contacting the hard stop.

HARDWARE ERROR #1

The 68030 (68000 on 9/240 only) main processor received an interrupt of unknown origin on level 6. Consult Allen-Bradley customer support services.

HARDWARE ERROR #2

The 68030 (68000 on 9/240 only) main processor has detected a bus error. Consult Allen-Bradley customer support services.

HARDWARE ERROR #3

The 68030 (68000 on 9/240 only) main processor has detected a spurious interrupt. Consult Allen-Bradley customer support services.

HARDWARE ERROR #4

The 68030 (68000 on 9/240 only) main processor has detected an illegal address. Consult Allen-Bradley customer support services.

HARDWARE ERROR #5

The PAL program residing in RAM memory has failed a checksum test. Attempt to download your PAL program to the control again. If the error remains, consult Allen-Bradley customer support services.

HARDWARE ERROR #6

The 68030 (68000 on 9/240 only) main processor has detected a privilege violation. Consult Allen-Bradley customer support services.

HARDWARE ERROR #7

The AMP data in Backup memory has failed a checksum test. Attempt to download your AMP program to the control again and again try to store it in Backup memory. If the error remains, consult Allen-Bradley customer support services.

HARDWARE ERROR #10

The servo processor RAM diagnostic test has failed. Consult Allen-Bradley customer support services.

HARDWARE ERROR #12

The servo communications timing diagnostic test between the main processor and the servo processor has failed. Consult Allen-Bradley customer support services.

HARDWARE ERROR #13

The main processor was not ready in time to send data to the servo processor. Consult Allen-Bradley customer support services.

HARDWARE ERROR #14

The servo processor sent an invalid error code to the main processor. Consult Allen-Bradley customer support services.

16-16

Page 837

Section 16 Error and System Messages

Message

Description

HARDWARE ERROR #15

The servo communications data echo diagnostic test between the main processor and the servo processor has failed. Consult Allen-Bradley customer support services.

HARDWARE OVERTRAVEL (+)

The indicated axis has reached a travel limit in the positive direction.

HARDWARE OVERTRAVEL (-)

The indicated axis has reached a travel limit in the negative direction.

HIPERFACE COMMUNICATION ERROR

A serial communications error (e.g., CHECKSUM, TIMEOUT) was detected within the SINCOS device during power- up. If this error occurs at PTO, check your feedback device to make sure it is not disconnected.

HIPERFACE PASSWORD FAILURE

During the SINCOS device’s alignment procedure, the logic used to set the passwords detects an incorrect password. A section of the code will repeatedly attempt various combinations of each of the passwords to correct the error condition.

HOME TOLERANCE EXCEEDED

This error condition occurs when the homing operation of the indicated axis is aborted due to the condition of the axis stopping off of the home switch in excess of 3/8 of an electrical cycle of the feedback device away from a null marker. If this problem persists you may need to adjust either the home switch position, or the home switch trip dog, or the feedback position. This may also require you to adjust the AMP Home Calibration parameter for this axis.

HOME REQUEST ON A PARKED AXIS

An attempt was made, while using dual axes, to do a homing operation on a parked axis.

HOMING NOT COMPLETED

An attempt was made to execute a programmed axis move before the axes have been homed. Axes must be homed before they can be moved through part program or MDI commands.

I I/O RING COMMUNICATIONS ERROR

A communication error has occurred in the fiber optic I/O ring. This is usually caused by a broken or disconnected fiber optic cable.

I/O RING NOISE WHILE IDLE

An illegal character was detected by an optical receiver while the I/O ring should have been idle. The system will try to reset itself. If it cannot reset itself, the system enters E-Stop.

I/O RING NOT CONFIGURED

The control cannot run the I/O ring if it was not configured and downloaded from ODS or resident in the PAL PROMs.

I/O RING TIME-OUT

A very large foreground PAL program, combined with a large number of I/O ring devices, has created timing problems for I/O ring communications. Reduce PAL program size by deleting unnecessary rungs and optimize the execution of others.

ILLEGAL (/) VALUE

A block delete slash value greater than /9 was programmed. There are only 9 block deletes available.

ILLEGAL (G) CODE

An illegal G-code value has been programmed.

ILLEGAL (M) CODE

An illegal M-code value has been programmed.

ILLEGAL ANGLE VALUE

A QuickPath Plus block has defined the angle of the next block incorrectly. There is no possible path that connects the two tool paths to the programmed end-point using the entered angle.

ILLEGAL APPLICATION COMMAND FROM TEACH

A non-recognized SD1-type packet was received in a CMD=61 DF1 packet from the teach pendant interface. Allowable SD1s are 1 - 5.

ILLEGAL AXIS DATA FORMAT

Digitized axis data does not fit within the allowable AMPed axis format. For example, if an axis inch format is set at 2.3 and a digitized position is recorded as 121.0, an error will be generated. The axis display will also show “__.___”.

ILLEGAL CHARACTER

An undefined character was entered in a program block and could not be executed. Certain characters cannot be recognized while in certain modes. Also verify that you are using the correct axis and integrand names as assigned in AMP.

ILLEGAL CODE DURING G41/G42

An illegal code was encountered during G41/G42 programming.

ILLEGAL CODE DURING VIRTUAL C

An illegal code was encountered during Virtual C programming.

ILLEGAL CODES IN RANDOM TOOL BLOCK

An invalid parameter was entered in a G10.1L20 block that loads data into the Random Tool table. P, Q, R, and O are the allowable parameters.

ILLEGAL COMMAND FROM ODS

A command was received from ODS that was not recognized by the control.

16-17