i2867 Controller Installation & Programming Guide, pages 7 to 11

Pages 7 to 11 of 52: Introduction; i2867 Module Characteristics; Mechanical Installation

The original document is the PDF (552 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2-867

Page 7

TCX 865 5 L

4

24V AC 0.17A , 4V 50/60H A Z

3 SHLD

2 1

-

+

INFI NE PO T RT

867

IN1

UN IVER INPU SAL TS

IN2

IN3

1

IN4

2 3

4

RET 5

This manual describes the installation, and use of the i2867 Terminal Control Unit. This compact terminal control unit provides low-cost DDC control of package units, VAV boxes, unit ventilators, and other terminal unit applications with its versatile mix of inputs, outputs, plus an interface to Andover Controls' Smart Sensor Bus. The i2867 features combinations of universal inputs, Analog, Form A, and Tri-state outputs for flexible control configurations. The Infinet’s true peer-to-peer communications protocol provides the Infinity i2867 with the ability to instantly communicate with an Infinity network controller such as the Continuum NetController, as well as the entire network of Andover Infinet field controllers. Up to 254 i2867 controllers can be networked to one network controller.

i2867 Installation & Programming Guide

1

Page 8

i2867 Module Characteristics The following lists the features included in the i2867 Controller Module: •

4 Universal Inputs

•

1 Temperature Input/ Smart Sensor Bus Interface

•

5 Form A Triac Outputs

• •

2 Analog Outputs (0-10V) 24VAC input power

•

Infinet Interface

If You Are Upgrading From the TCX 867 The i2867 includes many advantages over the TCX867 and a few differences. The Triac output section of the i2867 is designed to provide low side switching. Before replacing a TCX867 with this product make sure that your outputs are wired as shown on page 23 of this manual. If you are interfacing a Sensor Plus peripheral to the i2867, follow the directions given in the Sensor Plus documentation (version C or higher) to detect the activation of the override button. Do not use the procedure recommended for use with the TCX867.

Controller Limitations Using SX8000 Based Systems Plain English Programs Creating a program in the i2867 using the terminal interface that sets the digitalfilter attribute of a voltage input will save successfully into the SX database, however, it cannot be edited and saved. This is because the TCX867 Infinet I controller did not include the ability to use this attribute. Outputs When you configure this controller using the SX8000 workstation, the TCX867 controller is selected. Although these controllers are similar in their input and output configurations, the TCX 867 used outputs 1 and 2 as a hardwired tri-state output while the i2867 includes the ability to separately address outputs 1 and 2. An error will occur if you try to configure output 1 or 2 as anything but a tri-state. Flash Memory Backup The i2867 includes the ability to save the current configuration to on-board flash memory. This new capability includes several new system variables and operating modes. The SX8000, being an older software implementation, did not include any capability to handle these new features automatically like the CyberStation can. Therefore there are limitations when using the flash system in an SX8000 environment. Refer to the Operation/Programming section for specific instructions.

2

Andover Controls Corporation

Page 9

Mechanical Installation The i2867 Controller module is mounted directly to a panel using screws. Mounting hardware is included as an integral part of the case design.

Note: This equipment is intended for field installation within the enclosure of another product. The i2867 module plastic case is illustrated below:

5 L

4

24VA 0.17AC , 50/604VA HZ

3 SHLD

2 1

-

+

INFI N PO ET RT

867

UN IN1 1

IN2 2

IVER INPU SAL TS IN3 3

IN4 4

RET 5

The reset switch and various status indicators may be accessed by lifting the hinged door to the module as shown.

Status Indicators

Connections to controlled/sensed equipment i2867 Installation & Programming Guide

3

Page 10

On the back of the module are locking mounting extensions. The design allows the module to be mounted directly to a panel using them as a bracket. A stand-off is molded into the locking extension. To mount the module, pull both extensions out until they click (locked position). Insert a screw through the standoff as shown below:

Locking Extension

Panel Mounting

4

Andover Controls Corporation

Page 11

Overall Dimensions The overall dimensions of the i2867 module are as shown:

i2867 Installation & Programming Guide

5