Page 12
Power Connection The i2867 Controller is operated via an individual external 24 Volt AC source. An internal power converter creates the necessary DC voltages to supply the microprocessor circuitry. Should the AC source be interrupted during operation, backup power for the internal controller state memory is provided by a coin-style 3 Volt Lithium battery. This battery can maintain back-up status for five years' worth of accumulated power failures and has a typical shelf life of at least ten years.
Battery Connection & Replacement To access the battery holder, the module cover must be removed and the electronics access cover must be removed. The cover is secured via two force fitting plastic tabs. To remove the access cover after the main cover is opened, gently pry the cover outward using your thumb and forefinger while lifting the cover. As shown below:
While tabs are depressed, lift case backwards
Depress tabs on both sides
6
Andover Controls Corporation
Page 13
Once the access cover is removed the printed circuit board is accessible. The following illustrates the location of the battery holder in relation to the board:
BATTERY
During shipment, an insulating plastic tab is inserted under the clip on the battery to prevent it from draining prior to installation. To activate the battery, this tab must be removed. Should it become necessary to replace the battery, the battery is placed in a coinstyle holder. The battery used in the i2867 is a type CR 1225, 48 mAhr 3.0 V primary Lithium battery. CAUTION There is danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent type recommended above. Dispose of used batteries according to manufacturer’s instructions.
i2867 Installation & Programming Guide
7
Page 14
24VAC Connection The i2867 controller is powered by an external 24 VAC source. This power supply is connected via two terminals located on the Power/Communications connector. The unit should receive power from its own independent, 24 VAC +10% -15%, 50 or 60 Hz, 10 VA, un-switched circuit. The Power/Communications connector is located on the top of the module case (as viewed from the front) and consists of five pins. The signals within that connector are as follows:
PIN 5
5 4
3 2
1
Function 24 VAC 5
4
L
(Earth GND)
3
Infinet Shield
2
Infinet -
1
Infinet +
4
24VA 0.17 C A, 50/6 4VA 0HZ
3 SHLD
2
INF
TCX
--
1
+
INPFOINET IN R PO TET RT
+
867 867
UN IN1 1
IN2 2
IVE INP RSAL UTS IN3 3
IN4 4
RET 5
Connect 24VAC as shown below: 24 VAC Step-Down Transformer
Optional 39V Varistor for extremely noisy environments
X1
AC Line Power X2 Optional Varistor choose a voltage rating appropriate to the input voltage applied. i.e 130V or 250V White or Green
Black
5 4 3 2 1 i2867
8
Andover Controls Corporation
Page 15
The 24 VAC connection consists of both terminals from the secondary of a power-line to 24 VAC transformer. Connection to the Controller is through push-on quick-disconnect screw type connector that is supplied with the Controller. The ground wire at the transformer should not exceed 12” in length and it must be connected to a good earth ground. The screw that connects the ground wire with earth ground shall have a green colored head that is hexagonal, slotted or both. Powering Multiple i2867 Controllers Unless all the i2867 controllers you intend to power are resident in the same cabinet, it is imperative that you use a separate transformer for each controller. When you attempt to power multiple remotely located controllers from a single power source the voltage drop caused by the current draw per controller (realize that the actuator may be using power from the controller as well) results in marginal operation and in most cases prevents proper communications between controllers. Warning Make sure that 24 VAC is not connected to the power cable while you are wiring the controller, or you could receive an electrical shock that is life-threatening.
i2867 Installation & Programming Guide
9
Page 16
Building Ground Requirements Be sure that all equipment from Andover Controls is grounded to true Earth ground. True Earth ground protects the equipment from transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented without a properly grounded installation. An example of a sub-standard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the Earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of the equipment.
Inspecting the Ground Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not follow the code and often have substandard electrical grounds. Check your ground as follows: Inspect the building power distribution panel for Earth-ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: Does not exist. Is connected to a corroded or galvanized pipe. Is connected using a small gauge wire (less than 14 AWG). Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel.
Lightning Protection Although metal oxide varistors are built into the board to protect against power line transients, this protection is not sufficient to protect against lightning. Lightning arresters are required at each point where Infinet cables enter or exit a building. The following lightning arrester is recommended: Andover Controls # 01-2100-299, Two pair gas tube lightning arrester 10
Andover Controls Corporation