Page 17
Infinet Network Connection The i2867 controllers include an interface to the Andover Controls proprietary Infinet network. Connection to the Infinet allows multiple controllers to communicate and be controlled by a larger ‘host’ controller. Connection to the Infinet requires access to an Infinet network cable. This cable consists of two wires and a shield. Infinet connections are done at the Power/Communications connector. To wire the Controller to the Infinet, follow the steps below: 1. Trim the outer jacket of the Infinet cable to reveal the internal wires. 2. Strip the insulation from the white* wire and loosen the screw at position 1. 3. Insert the stripped end of the white* wire into the pin 1 position (‘+’ receptacle) of the terminal block. Tighten the screw. 4. Strip the insulation from the black* wire and loosen the screw at position 2. 5. Insert the stripped end of the black* wire into the pin 2 position (‘-’ receptacle) of the terminal block. Tighten the screw. 6. Insert the shield wire into the pin 3 position (‘SHLD’ receptacle) of the terminal block. Tighten the screw.
* Wire colors are included for clarity. The colors of your cable may vary. However, make sure that all Infinet connections are consistent on their connections.
1 2
3
4 5
Shield
Black (-)
White (+)
i2867 Installation & Programming Guide
11
Page 18
Input Connections Universal Inputs The i2867 Controller includes Andover Controls Universal Inputs that are unique in that they are software configurable to handle any one of a number of input types: Thermistor Voltage Digital/Counter
Input Wiring The actual input terminations are located on the bottom of the module. Connection is via a removable five-connection screw terminal plug. The signals within that connector are as follows:
PIN 1
Function IN1
2
IN2
3
IN3
4
IN4
5
RET (Common Return for all Inputs)
1 2
3 4
5
The inputs are labeled IN1 through IN4 and are followed by a connection labeled RET for the input signal return. Although there is only one return terminal (RET) supplied, it is recommended that a separate return wire be used for each input. All return wires should be crimped into one connection to the RET terminal.
12
Andover Controls Corporation
Page 19
Wiring Concerns Do not remotely ground any part of the sensor wiring. Remote grounds connected to the i2867 return terminal could make the controller operate incorrectly or damage the equipment. The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. It is recommended that you run input wiring in a conduit separate from AC power or output wiring and avoid long wiring runs. For reliable input operation, follow these input wiring guidelines: •
Never lay wires across the surface of the printed circuit board.
•
Wires should never be within 1 in. or 25 mm of any component on the printed circuit board.
•
Use shielded input wire.
•
Terminate the shield of the input wires at one end of the run only, preferably at the end where your controller is located.
•
Be careful when stripping wire not to drop small pieces of wire inside the cabinet.
•
Don’t run your input wiring in the same conduit with AC power.
•
Don’t run your input wiring in the same conduit with your output wiring.
Caution Do not externally ground any input connected to the Controller. This may damage the unit. Signal return terminals are not connected to Earth Ground.
Input Pull-up Resistor Selection The i2867 inputs may be configured to include internal pull-up resistors. In some measuring instances it is desirable that there be no pull-up resistor. Instead of physically removing or cutting the resistor off the printed circuit board, the input module includes a pull-up resistor selection switch. When the switch is placed in the ‘enabled’ or ON position, the pull-up resistor is connected to the input line. When the switch is moved to the ‘disabled’ or OFF position, the pull-up resistor is removed from the circuit. The following is a schematic representation of the switch and its associated pull-up:
VREF 10K Switch shown in ‘disabled’ position INPUT i2867 Installation & Programming Guide
13
Page 20
Input Pull-up Resistor Switch Location The i2867 pull-up selection switch is located inside the plastic case, behind the status panel. You must remove the front of the case to access the location. To remove the front of the case, locate the small plastic tabs that hold the case halves together. Depress the tab on both sides and lift the case back as shown:
While tabs are depressed, lift case backwards
Depress tabs on both sides
Once you have accessed the board, the switch can be found as shown on the following diagram:
DISABLED
1
2
3
ENABLED
4
PULL-UP RESISTOR ENABLE SWITCH
14