Page 21

Measuring Temperature (IN1 - IN4) All four of the i2867 inputs may be configured to sense temperature by configuring the controller’s inputs appropriately. This is done by setting the Electrical Type to either ACC Temp (DEG F) or ACC Temp (DEG C). Connect a resistive thermistor sensor to that input terminal. The following is a schematic representation of the connection:

IN x Thermistor RET

One lead connects to a numbered input terminal, the other to a return terminal. When the input point is configured as a temperature input, the controller utilizes a look-up table to convert from a voltage reading to a temperature reading in degrees Fahrenheit or Celsius. To measure temperature, the pull-up resistor switch associated with this input must be enabled.

Caution Never apply a voltage to a thermistor - doing so alters the thermistor’s accuracy and reliability. In fact, it’s a good idea to replace any thermistor that has had any sort of voltage applied to it.

Maximum Wire Runs for Thermistors To keep thermistor errors minimal, limit the length of wire runs to the maximum for the gauge wire you select. The following two pages include three tables that indicate the maximum length runs for wires of various gauges to keep errors within certain temperature limits when using thermistor elements.

i2867 Installation & Programming Guide

15

Page 22

Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 70 °F (21 °C) Gauge

1/2 °F (.28 °C) Error

1/4 °F (.14 °C) Error

1/10 °F (.06 °C) Error

#14 2.5 mm2

26,700 ft. 8150 m

13,300 ft. 4000 m

5,300 ft. 1600 m

#16 1.5 mm2

16,700 ft. 5120 m

8,300 ft. 2500 m

3,300 ft. 1000 m

#18 1.0 mm2

10,500 ft. 3200 m

5,200 ft. 1600 m

2,100 ft. 640 m

#20 0.5 mm2

6600 ft. 2000 m

3,300 ft. 1000 m

1,300 ft. 400 m

#22 0.35 mm2

4,100 ft. 1250 m

2,000 ft. 600 m

800 ft. 250 m

Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 100 °F (38 °C)

16

Gauge

1/2 °F (.28 °C) Error

1/4 °F (.14 °C) Error

1/10 °F (.06 °C) Error

#14 2.5 mm2

12,600 ft. 3800 m

6,300 ft. 1900 m

2,500 ft. 760 m

#16 1.5 mm2

7,900 ft. 2400 m

3,900 ft. 1200 m

1,500 ft. 450 m

#18 1.0 mm2

5,000 ft. 1500 m

2,500 ft. 760 m

1,000 ft. 300 m

#20 0.5 mm2

3,100 ft. 950 m

1,500 ft. 450 m

600 ft. 180 m

#22 0.35 mm2

1,900 ft. 580 m

900 ft. 275 m

300 ft. 90 m

Andover Controls Corporation

Page 23

Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 150 °F (65 °C) Gauge

1/2 °F (.28 °C) Error

1/4 °F (.14 °C) Error

1/10 °F (.06 °C) Error

#14 2.5 mm2

4,100 ft. 1250 m

2,000 ft. 600 m

800 ft. 240 m

#16 1.5 mm2

2,600 ft. 800 m

1,300 ft. 400 m

500 ft. 150 m

#18 1.0 mm2

1,600 ft. 500 m

800 ft. 240 m

300 ft. 90 m

#20 0.5 mm2

1,000 ft. 300 m

500 ft. 150 m

200 ft. 60 m

#22 0.35 mm2

600 ft. 180 m

300 ft. 90 m

100 ft. 30 m i2867 Installation & Programming Guide