The text of a manual · part 6 of 9
i2867 Controller Installation & Programming Guide, pages 24 to 26
Pages 24 to 26 of 52: Measuring DC Voltages (IN1 - IN4); Sensing Contact Closures (Digital) IN1 – IN5; Counting Pulsing Signals or Contact Closures
The original document is the PDF (552 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls i2-867
Page 24
Measuring DC Voltages (IN1 - IN4) All four inputs may be configured to sense DC voltage by setting the Electrical Type to Voltage and connecting the input terminals to a DC voltage source within the range of the module’s input specifications. The following is a schematic representation of the connection:
IN x
+ V -
RET
The plus lead connects to the numbered input terminal, the other to a return terminal. To measure voltage, the pull-up resistor switch associated with this input must be disabled.
Voltage Input Specifications
Voltage Range Resolution Accuracy Input Impedance Filtering Calibration
18
0 to 5.115 V 0.005 V +/–0.015 V 10KΩ referenced to 5.120 V Corner Frequency at 30 Hz, – 20db/decade Permanent (factory)
Andover Controls Corporation
Page 25
Sensing Contact Closures (Digital) IN1 – IN5 Digital input points are designed to allow the monitoring of contact closures across an input (contact wired between the input and return). All five inputs can be configured as Digital Inputs.
IN x Contact Closure RET
To sense a digital input or contact closure, configure an input point with an Electrical Type of Digital. To sense contact closures, the pull-up resistor switch associated with this input must be enabled.
Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, readings are reversed: ‘On’ will occur when the contact is open, and ‘Off’ occurs when the contact is closed.
i2867 Installation & Programming Guide
19
Page 26
Counting Pulsing Signals or Contact Closures Counter inputs are designed to allow the monitoring of digital pulse trains or contact closures across an input just like digital inputs, but they accumulate a total of those closures and act like a counter. All four inputs can be configured as Counter Inputs. Interfacing is similar to a digital input, however, you set the Electrical Type attribute to Counter instead. To count signals or contact closures, the pull-up resistor switch associated with this input must be enabled. When using an input as a counter, you must take into account the frequency of the input signal being counted. Universal inputs do not allow for very high speed contact counting. This module allows counting up to a maximum of 4 Hz or 4 contact closures per second.
Minimum Pulse Width The high period of the signal must be at least 125 milliseconds. The low period of the signal must be at least 125 milliseconds.
20
Andover Controls Corporation