i2867 Controller Installation & Programming Guide: Output Connections

Pages 27 to 30 of 52, from i2867 Controller Installation & Programming Guide

The original document is the PDF (552 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2-867

Page 27

Output Connections The i2867 Controllers include 5 Form A Triac outputs that can be used separately or be configured into Form K Tri-state outputs (2-max) with a free triac output remaining. Any two consecutive Triac outputs can be configured as a Form K output. Examples would be (OUT1 and OUT 2), (OUT3 and OUT4), (OUT2 and OUT3) and (OUT4 and OUT5). The Controller also includes 2 analog outputs.

Note: When used with an Infinity network serviced by an SX8000 workstation, OUT 1 and OUT2 must be configured as a tri-state output. The SX8000 workstation assumes the i2867 is configured as an Infinet 1 TCX867 and therefore, these outputs cannot be used as separate triac outputs. Output terminations are located on a sixteen-position removable screw terminal connector along the right side of the module.

5 L

4

24V A 0.17 C A, 50/6 4VA 0HZ

3 SHL

2 D

1

-

+

INF IN PO ET RT

867

UN IN1 1

IN2 2

IVE INP RSAL UTS IN3 3

IN4 4

RET 5

Output Terminations i2867 Installation & Programming Guide

21

Page 28

The outputs are grouped in pairs of two connector terminals per channel. Each Triac digital output presents a normally open single pole set of contacts.

The diagram below indicates where each output number is located in the terminal block. The Triac outputs are labeled ‘Digital Outputs’. Connection

22

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10.

GND OUT 1 GND OUT 2 GND OUT 3 GND OUT 4 GND OUT 5

Form A Triac Output

11. 12. 13.

RET OUT 6 OUT 7

Analog Outputs (0-10V)

14. 15. 16.

RET IN 5 SPWR

Smart Sensor Bus Interface

Form A Triac Output Form A Triac Output Form A Triac Output Form A Triac Output

Andover Controls Corporation

Page 29

Digital Outputs (Form A Triacs) The i2867 includes five Form A Triac outputs. The following is a functional schematic representation of the connection:

These output contacts operate as a solid state relay. When the output is set to an ‘ON’ state, the contacts close allowing current to flow between the output terminals. To use the Form A output in your system, configure an output point with an Electrical Type of Digital. Output Rating: Output Accuracy: Output Protection:

0.5A, 24 VAC, (Cannot switch DC loads) 0.1 sec. for Pulse Width Modulation (PWM) control RC snubber on each output

Switching Loads with Triacs Although the Triac-based outputs provided with this unit appear as relay contacts in the schematics provided, they are actually solid-state switches that have limitations on the loads they can switch. AC vs. DC The first limitation is that they cannot be used with DC loads. A Triac switches AC only. Minimum Load Current The second limitation involves the minimum load current. In order for the Triac to switch it must have at least 30 ma of holding current from the load. If your load is less than 30 ma you can induce the required load by connecting a resistor across the load. Check the current draw specification on your field device, and if it does not meet this minimum, add a resistor in parallel with the device being driven sized to achieve the minimum loading. Use the following formulas to determine resistance and wattage: Resistance (ohms) =

Voltage Current

Power (Watts) =

2

(Voltage) Resistance i2867 Installation & Programming Guide

23

Page 30

Tri-State Output Adjacent outputs of the i2867 Controller module can be configured as Tri-state Triac outputs. The following is a schematic representation of a Tri-state output:

In this example, Output 1 is the Tri-state output. The second output in a Tri-state pair is not addressable as a separate output. It is an integral part of the Tri-state circuit for Output 1. Configure Output 1 with an Electrical Type of Tri-state.

Combining Form A Outputs as a Tri-State Output Adjacent output pairs: OUT1 and OUT2 OUT2 and OUT3 OUT3 and OUT4 OUT4 and OUT5 can be combined to form a standard Tri-state output. The outputs are electrically connected as shown in the schematic for the built-in Tri-state output. Configure the output point of the first point of a pair (i.e., OUT3 of the pair OUT3 and OUT4) with an Electrical Type of Tri-state. 24