Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 1 of 2

B-Series Switches: Pressure, Differential Pressure, Temperature, pages 1 to 8

Pages 1 to 8 of 16

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Ashcroft B424B

Page 1

YOUR PRESSURE AND TEMPERATURE SWITCH SOURCE

B-SERIES SWITCHES PRESSURE DIFFERENTIAL PRESSURE TEMPERATURE

A Halliburton Company

BULLETIN SW-10

Page 2

B-SERIES PRODUCT INFORMATlON

The Dresser Control Instrument Operation supplies highly reliable Ashcroft® switches and controls for industrial and process applications. We begin with rock-solid designs, matching the most appropriate technology with the safety and reliability requirements of the applications. The materials of construction are specified to Dresser’s exacting standards, and product is built to last in the toughest applications. Our modern, responsive manufacturing facility in Milford, Connecticut is supported by an extensive network of stocking distributors and factory sales offices located in virtually every part of the world. Special application assistance is always just a telephone call away. The Ashcroft B-Series switch line is designed to satisfy most switch requirements. Materials of construction have been selected for long life. A wide vari- ety of precision switch elements are available to meet every application requirement, including hermetically sealed contacts for added reliability and safety. The actuators we use have been proven in more than 20 years of service in the world’s plants and mills. Special designs are available for fire safety, NACE, limit control and other more stringent requirements. Simplicity and ease of use are stressed to improve reliability of the installation. B-Series switches have proven reliable in such harsh environments as: • Offshore oil rigs • Chemical and petrochemical plants • Pulp and paper mills • Steel mills • Power plants • Water and sewage-treatment plants • Other corrosive environments

Type 400 Enclosure UL and CSA listed instrument quality snap-action switch for reliable operation. Ratings up to 10A dc or 20A ac. Hermetically sealed switch also available.

Epoxy-coated aluminum enclosure for corrosion resistance. Meets NEMA 3, 4, 4X, 13 and IP66 requirements.

Accessible adjustment for convenient switch setting, includes vibrationresistant feature.

3

⁄4 NPT electrical connection for easy wiring. Neoprene gasket for sealing enclosure.

High proof pressure.

Standard pressure connection materials: Pressure psi ranges – 316 SS Differential psid ranges – Nickel-plated brass Pressure and differential I.W. ranges – Epoxy-coated carbon steel

2

Deadband limits for each switch.

Page 3

RECOMMENDED PRACTICE:

Applications include: pumps, compressors, washers, filters, degreasers, evaporators, recovery systems, food processing, ground support equipment, reverse osmosis systems, heat exchangers, hydraulic systems, lubrication systems, marine equipment, textile machinery, heating and air conditioning equipment.

All controls should be selected considering the media and ambient operating conditions. Improper application can be detrimental to the switch, cause failure and possibly personal injury or property damage.

Hermetically Sealed Switch We recommend hermetically sealed switch elements for improved reliability. The hermetically sealed switch provides uncompromising contact protection in harsh or corrosive environments. The Ashcroft 400 Series is also approved for installation in Division II hazardous areas when supplied with hermetically sealed contacts.

The information in this catalog is offered as a guide to assist in making the proper selection of Ashcroft controls. Features: • UL-recognized component, guide WSQ2, File E85076 • All-stainless steel welded construction

Additional information is available from Dresser Control Instrument Operations Sales. Offices are listed on the back cover.

Type 700 Enclosure UL and CSA listed instrument quality snap-action switch for reliable operation. Ratings up to 10A dc or 20A ac. Hermetically sealed switch also available. Dual (2 SPDT) shown.

Terminal block wiring standard on dual switches. Optional (XK3) on single switches.

Deadband limits for each switch. High proof pressure.

Epoxy-coated aluminum enclosure and cover for corrosion resistance. Class 1, Division 1 & 2, Groups B, C, D, Class 2, Division 1 & 2, Groups E, F, G, NEMA 7 & 9 and IP66. Buna-N 0-ring for sealing enclosure.

Two 3⁄4 NPT electrical conduit connections.

Standard 316 SS pressure connection. Optional 1⁄2 NPT shown.

Accessible adlustment is stainless steel for corrosion resistance, includes vibration-resistant feature.

3

Page 4

PRESSURE AND DIFFERENTlAL PRESSURE SWITCHES

B-Series pressure, differential pressure and vacuum switches use two different actuators depending on setpoint requirements. For setpoints between 2 and 3000 psi, the simple, rugged diaphragmsealed piston actuator is used. This design features high reliability and choice of actuator seal materials for virtually every application. An optional welded design is also available for setpoints up to 1000 psi for maximum reliability. This design is available in

316 SS or Monel. Differential pressure models use a unique, dual diaphragmsealed piston design that features very high static operating pressures and small size. For setpoints between 4.5 and 150 inches of H2O, a large diaphragm is used for increased sensitivity in both pressure and differential pressure designs with good choice of materials of construction.

All standard models feature ±1 percent of range setpoint repeatability and a minimum of 400 percent of range proof pressures. These standard designs perform well in applications where shock and vibration could be a problem and may be used in conjunction with Ashcroft diaphragm seals in extreme services such as slurries or abrasive process fluids.

PRESSURE/VACUUM SWITCHES Overpressure Ratings Proof psi Burst psi

Nominal Range(1) Vacuum –30˝ Hg Compound –15˝ H2O/ 15˝ H2O –30˝ H2O/ 30˝ H2O –30˝ Hg/ 15 psi –30˝ Hg/ 30 psi –30˝ Hg/ 60 psi Pressure 10˝ H2O 30˝ H2O 60˝ H2O 100˝ H2O 150˝ H2O 15 psi 30 psi 60 psi 100 psi 200 psi 400 psi 600 psi 1000 psi 3000 psi

20, 26, 27

Approximate Deadband(2) Switch Element 21, 24, 31 50 22

32

–760mm Hg

-100 kPa

250

400

0.3-0.7

1.5-3.0

0.5-2.2

0.4-1.5

2.1-4.2

–375mm H2O/ 375mm H2O –760mm H2O/ 760mm H2O –760mm Hg/ 1.0 kg/cm2 –760mm Hg/ 2.0 kg/cm2 –760mm Hg/ 4.0 kg/cm2

–3.7 kPa/ 3.7 kPa –7.5 kPa/ 7.5 kPa –100 kPa/ 100 kPa –100 kPa/ 200 kPa –100 kPa/ 400 kPa

20

35

20

35

250

400

250

400

250

400

0.15-75/ 0.15-75 0.30-60/ 0.30-60 0.5-1.0/ 0.3-0.7 1.0-1.5/ 0.3-0.8 2.0-3.0/ 0.7-1.5

1.5-2.5/ 1.5-2.5 1.5-2.5/ 1.5-2.5 2.0-3.0/ 0.5-1.5 3.0-6.0/ 1.0-2.0 5.0-9.0/ 3.0-5.0

0.45-2.0/ 0.45-2.0 0.45-2.0/ 0.45-2.0 0.75-2.5/ 0 .5-1.0 1.2-4.5/ 0.7-1.5 2.5-7.0/ 1.1-4.0

0.5-1.2/ 0.5-1.2 0.5-1.5/ 0.5-1.5 0.7-1.8/ 0.7-1.4 1.4-2.4 0.4-1.3 2.8-4.5 1.0-2.3

2.1-3.5/ 2.1-3.5 2.1-3.5/ 2.1-3.5 2.8-4.2/ 0.7-2.1 4.2-8.4/ 1.4-2.8 7.0-12.0/ 4.2-7.0

250mm H2O 750mm H2O 1500mm H2O 2500mm H2O 3750mm H2O 1.0 kg/cm2 2.0 kg/cm2 4.0 kg/cm2 7.0 kg/cm2 14 kg/cm2 28 kg/cm2 42 kg/cm2 70 kg/cm2 210 kg/cm2

2.5 kPa 7.5 kPa 15 kPa 25 kPa 37 kPa 100 kPa 200 kPa 400 kPa 700 kPa 1400 kPa 2800 kPa 4200 kPa 7000 kPa 2100 kPa

20 20 20 20 20 500 500 500 1000 1000 2400 2400 12000 12000

35 35 35 35 35 1500 1500 1500 3000 3000 3000 3000 18000 18000

0.2-0.5 0.3-0.6 0.5-1.3 0.6-1.6 1.0-2.5 0.1-0.35 0.1-0.50 0.3-1.0 0.5-1.7 1-3 4-7.5 4-11 7-30 15-60

1.0-2.0 1.5-2.5 1.5-3.5 2.5-5.5 4.5-8.5 0.5-1.5 0.5-1.5 1.0-3.5 1.5-5.0 5-13 5-24 9-30 30-110 80-235

0.35-1.5 0.45-2.0 0.9-2.5 1.1-4.0 1.7-6.5 0.2-1.0 0.3-1.0 0.7-2.5 1.1-3.5 2-9 5.5-15 7-20 18-70 37-160

0.4-1.0 0.5-2.0 0.7-3.0 1.0-4.0 2.0-6.0 0.4-1.0 0.4-1.0 0.6-2.0 1.0-4.5 3.0-7.5 4.0-11.0 5.0-23.0 15-80 30.0-230

1.4-2.8 2.1-3.5 2.1-5.0 3.5-7.7 6.0-12.0 0.7-2.1 0.7-2.1 1.4-5.0 2.1-7.0 7.0-18.2 7.0-33.6 12.6-42 42-154 112-329

PRESSURE/VACUUM SWITCHES

30˝ H2O 60˝ H2O 100˝ H2O 150˝ H2O 15 psid 30 psid 60 psid 100 psid 200 psid 400 psid 600 psid

Nominal Range(1) 750mm H2O 1500mm H2O 2500mm H2O 3750mm H2O 1.0 kg/cm2 2.0 kg/cm2 4.0 kg/cm2 7.0 kg/cm2 14.0 kg/cm2 28.0 kg/cm2 42 0 kg/cm2

7.5 kPa 15 kPa 25 kPa 37 kPa 100 kPa 200 kPa 400 kPa 700 kPa 1400 kPa 2800 kPa 4200 kPa

Pressure Ratings Static Working Pressure Proof psi 5.4 21.6 5.4 21.6 5.4 21.6 5.4 21.6 500 2000 500 2000 500 2000 1000 4000 1000 4000 1000 8000 2000 8000

Approximate Deadband(2) Switch Element 20, 26, 27 0.3-0.6 0.5-1.3 0.6-1.6 1.0-2.5 0.5-1.0 1.0-2.0 2.0-4.0 4.0-10.0 5.0-15.0 10.0-20.0 20.0-40.0

21, 24, 31 1.5-2.5 1.5-3.5 2.5-5.5 4.5-8.5 2.0-5.0 2.0-5.0 3.0-6.0 11.0-20.0 12.0-40.0 20.0-60.0 80.0-150.0

50 0.45-2.0 0.9-2.5 1.1-4.0 1.8-6.5 0.7-3.5 1.5-3.5 3.0-4.5 7.0-15.0 10.0-26.0 15.0-40.0 30.0-115.0

22 32 0.5-2.0 2.1-3.5 0.7-3.0 2.1-5.0 1.0-4.0 3.5-7.7 2.0-6.0 6.3-12.0 0.7-1.4 2.8-7.0 1.4-2.8 2.8-7.0 2.8-5.6 4.2-8.5 6.0-14.0 16.0-28.0 7.0-21.0 17.0-56.0 14.0-28.0 28.0-84.0 30.0-56.0 112.0-210.0

Values shown are for zero static working pressure.

NOTES: 1 Switches may generally be set between 15% and 100% of nominal range on increasing pressure. Consult factory for applications where setpoints must be lower.

4

2 All deadbands are given in English units as shown in the nominal range column. Deadbands shown are for switches with Buna N diaphragm. Approximate deadbands for optional diaphragms:

Viton: Multiply Buna N value by 1.4 Teflon: Multiply Buna N value by 1.2 Stainless Steel: Multiply Buna N value by 1.7 Monel: Multiply Buna N value by 1.7 Dual Switch Element: Multiply single switch element value by 1.6 for approximate deadband.

Page 5

ORDER INFORMATION

B-SERIES PRESSURE AND DIFFERENTIAL PRESSURE SWITCH MODEL NUMBER: To specify the exact switch desired, select entries from appropriate tables as shown in example below. 1

2

3

4

5

B 4

2 0

B

X P K

600 PSI

1 – ENCLOSURE

2 – SWITCH ELEMENT SELECTION

Pressure switch, type 400, watertight enclosure meets NEMA 3, 4, 4X, 13 and IP66 requirements. Pressure switch, type 700, explosion-proof enclosure meets Div. 1 & 2, NEMA 7, 9 and IP66 requirements. Differential pressure switch, type 400, watertight enclosure meets NEMA 3, 4, 4X, 13 and IP66 requirements. Differential pressure switch, type 700, explosionproof enclosure meets Div. 1 & 2, NEMA 7, 9 and IP66 requirements.

B4 B7

D4

D7

Range Process Temperature Limits °F(9) 0 to 150 20 to 300 0 to 150 0 to 300 0 to 300

Vac. 0-600 1000 ˝ H2O psi psi • • • • • • • • • • • • •

4 – OPTIONS Use table from page 9

5 – RANGE Select from table on page 4

NOTES: 1 Standard switch. 2 Not available with psid ranges. 3 Dual switches are 2 SPDT snap-action switches, not independently adjustable. 4 Not available with type 400 enclosure. 5 Not available with type 700 enclosure. 6 Estimated dc. rating, 2.5A, 28 Vdc (not UL listed). 7 Estimated dc rating, 0.4A, 120 Vdc (not UL listed). 8 Available on pressure only. 9 Ambient operating temperature limits –20 to 150°F, all styles, setpoint shift of ±1% of range per 50°F temperature change is normal.

23 24(1)

25(2) 26(7) 27 28(5)

3 – ACTUATOR SEAL Code and Material B – Buna-N V – Viton T – Teflon S – 316L(8) P – Monel(8)

Order Code 20(7) 21 22(6)

3000 psi • •

29(5) 31 32 42 50 61(7) 62(7) 63 64

65 67(4,6) 68(4) 71(4)

Switch Elements UL/CSA Listed SPDT Narrow deadband ac 15A, 125/250 Vac Ammonia service 5A, 125/250 Vac Hermetically sealed switch, 5A, 125/250 Vac narrow deadband Heavy duty ac 22A, 125/250 Vac General purpose 15A, 125/250/480 Vac 1⁄2A, 125 Vdc 1⁄4A, 250 Vdc; 6A, 30 Vdc Heavy duty dc 10A, 125 Vac or dc, 1⁄8 HP, 125 Vac or dc Sealed environment proof 15A, 125/250 Vac High temperature 300°F 15A, 125/250 Vac Manual reset trip on 15A, 125/250 Vac increasing Manual reset trip on 15A, 125/250 Vac decreasing Low level (gold) contacts 1A, 125 Vac Hermetically sealed switch, 11A, 125/250 Vac general purpose 5A, 30 Vdc Hermetically sealed switch, 1A, 125 Vac gold contacts Variable deadband 15A, 125/250 Vac UL/CSA Listed Dual (2 SPDT) Dual narrow deadband 15A, 125/250 Vac Dual sealed environment 15A, 125/250 Vac proof Dual high temp. 300°F 15A, 125/250 Vac Dual general purpose 15A, 125/250/480 Vac 1⁄2A, 125 Vdc 1⁄4A, 250 Vdc Dual ammonia service 5A, 125/250 Vac Dual hermetically sealed 5A, 125/250 Vac switch, narrow deadband Dual hermetically sealed 11A, 125/250 Vac switch, general purpose 5A, 30 Vdc Dual hermetically sealed 1A, 125 Vac switch, gold contacts

5

Page 6

TEMPERATURE SWITCHES

B-Series temperature switches feature a SAMA Class II vapor pressure thermal system. This system provides quick, accurate response to process temperature changes with negligible ambient temperature effects. This is inherent in the design due to the precise relationship that exists between temperature and pressure according to the vapor pressure laws. A wide selection of sensing bulb and armored capillary lengths is available. The vapor pressure system design features small bulb sizes, making installation easy and cost-effective. All models feature ±1.0% percent of span setpoint repeatability with very high overtemperature ratings. These standard designs perform well in applications where shock and vibration could be a problem and should be used with Ashcroft thermowells for bulb protection and ease of installation and maintenance.

STANDARD TEMPERATURE RANGE SELECTION Maximum Temperature

Nominal Range(1)

Approximate Deadband(1) Switch Element

°F

°C

°F

20, 26, 27

21, 24, 31

50

22

32

–40 to 60 0 to 100 75 to 205 150 to 260 235 to 375 350 to 525(3) 500 to 750(2)

–40 to 160 –20 to 400 20 to 95 65 to 125 110 to 190 175 to 275 260 to 400

400 400 400 400 500 700 900

1.0-2.0 1.5-3.0 1.5-3.5 1.5-3.0 1.5-3.5 2.0-4.5 4.0-8.0

3.0-8.0 5.0-12.0 8.0-16.0 5.0-12.0 5.0-12.0 8.0-16.0 16.0-30.0

1.5-5.5 2.2-8.5 2.5-12.0 2.2-8.5 2.5-8.5 3.2-12.0 7.2-24.0

1.4-6.0 1.5-7.5 2.0-9.0 2.0-9.0 2.0-9.0 2.5-10.0 5.0-23.0

8.0-16.0 9.0-20.0 10.0-24.0 10.0-24.0 10.0-24.0 15.0-34.0 30.0-50.0

NOTES: 1 All deadbands given in °F. 2 Available with remote mount thermal systems only. 3 Not available with 23⁄4˝ stem.

4 Dual switch element multiply single switch element value by 1.6 for approximate deadband. 5 Set and reset points must fall within the adjustable range.

THERMOWELLS Thermowells must be used on any application where the bulb of the temperature switch may be exposed to pressure, corrosive fluids or high velocity. Additionally, the use of a thermowell permits instrument interchange or calibration check without disturbing or closing down the process. Ashcroft temperature switches have bulb diameters to match 3⁄8˝ nominal bore thermowells Is. The bulbs have a sensitive portion length of 2˝ which can be used with 21⁄2˝ “U” dimensioned thermowells or longer. For maximum accuracy a thermowells “U” dimension should be selected to permit complete immersion of the sensitive portion plus 1˝ when measuring the temperature of liquids; an extra 3˝ should be allowed when measuring the temperature of gases.

Thermowell bushings should be used with remote mount temperature switches. We recommend the standard 3˝ bulb and code 69 Series bushings for use with any thermowell “U” dimension. A split rubber grommet allows easy installation and “S” dimension adjustment. INSTRUMENT (SWITCH) CONNECTION

To order a thermowell, refer to Price Sheet TH/PS-1 for complete information.

1/2" NPT

Bushing slides along capillary

69 series (XBX) bushing

Process connection

“S”

“S” U˝

3˝

6

Page 7

ORDER INFORMATION

B-SERIES TEMPERATURE SWITCH MODEL NUMBER: To specify the exact switch desired, select entries from appropriate tables as shown in example below. 1

2

T 4

2 0

3

4

T 0 5 030 X N H 150° to 260°F 3 – THERMAL SYSTEM SELECTION

1 – ENCLOSURE T4 T7

Temperature switch, type 400, watertight enclosure meets NEMA 3, 4, 4X, 13 and IP66 requirements. Temperature switch, type 700, explosion-proof enclosure meets Div. 1 & 2, NEMA 7, 9 and IP66 requirements.

2 – SWITCH ELEMENT SELECTION Order Code 20(7) 21 22(6) 23 24(1)

25(2) 26(7) 27 28(5) 29(5) 31 32 50 61(7) 62(7) 63 64

65 67(4,6) 68(4) 71

6

5

Switch Elements UL/CSA Listed SPDT Narrow deadband ac 15A, 125/250 Vac Ammonia service 5A, 125/250 Vac Hermetically sealed switch, 5A, 125/250 Vac narrow deadband Heavy duty ac 22A, 125/250 Vac General purpose 15A, 125/250/480 Vac 1 ⁄2A, 125 Vdc 1 ⁄4A, 250 Vdc; 6A, 30 Vdc Heavy duty dc 10A, 125 Vac or dc, 1 ⁄8 HP, 125 Vac or dc Sealed environment proof 15A, 125/250 Vac High temperature 300°F 15A, 125/250 Vac Manual reset trip on 15A, 125/250 Vac increasing Manual reset trip on 15A, 125/250 Vac decreasing Low level (gold) contacts 1A, 125 Vac Hermetically sealed switch, 11A, 125/250 Vac general purpose 5A, 30 Vdc Variable deadband 15A, 125/250 Vac UL/CSA Listed Dual (2 SPDT) Dual narrow deadband 15A, 125/250 Vac Dual sealed environment 15A, 125/250 Vac proof Dual high temp. 300°F 15A, 125/250 Vac Dual general purpose 15A, 125/250/480 Vac 1 ⁄2A, 125 Vdc 1 ⁄4A, 250 Vdc Dual ammonia service 5A, 125/250 Vac Dual hermetically sealed 5A, 125/250 Vac switch, narrow deadband Dual hermetically sealed 11A, 125/250 Vac switch, general purpose 5A, 30 Vdc Dual hermetically sealed 1A, 125 Vac switch, gold contacts

Direct Mount System Material 3l6 SS Remote Mount Order Code System Material Line Length T05 316 SS 5´ T10 316 SS 10´ T15 316 SS 15´ T20 316 SS 20´ T25 316 SS 25´ Order Code TS

Style Rigid Style(9) Capillary with 302 SS Spring Armor

4 – BULB LENGTH SELECTION

5 – OPTIONS

Direct Mount

Use table on page 9

Order Code 027(8) 040 060 090 120 030(9)

Minimum “S” Thermowell Dimension “U” Dimension 23⁄4˝ – 4˝ 21⁄2˝ 6˝ 41⁄2˝ 9˝ 71⁄2˝ 12˝ 101⁄2˝ Remote Mount 3˝ 21⁄2˝

6 – STANDARD TEMPERATURE RANGE SELECTION Adjustable Range °F °C –40 to 600 –40 to 160 0 to 100 –40 to 400 75 to 205 20 to 95 150 to 260 65 to 125 235 to 375 110 to 190 350 to 525 175 to 275 500 to 750 260 to 400

NOTES: 1 Standard switch. 2 Available with remote mount thermal systems only. 3 Dual switches are 2 SPDT snap-action switches, not independently adjustable. 4 Not available with type 400 enclosure. 5 Not available with type 700 enclosure.

6 Estimated dc rating, 2.5A, 28 Vdc (not UL listed). 7 Estimated dc rating, 0.4A, 120 Vdc (not UL listed). 8 Not available on 350 to 525°F. 9 Consult factory on remote mount for bulb lengths other than 3.̋

7

Page 8

OPTIONAL FEATURES AND ACCESSORIES

XG9 – FIRE-SAFE WELDED ACTUATOR Standard features: • 3000 psi burst pressure unrestrained at room temperature • long service life • all welded – no O-rings • built-in over range protection • superior corrosion resistant materials • interchangeable with current Ashcroft pressure switch actuators • 15 psi to 600 psi ranges available

XG6 – U.L. LISTED LIMIT CONROL SWITCH Standard features: • setpoint indicating scale • adjusting nut stop • secondary chamber with vent • optional pilot light for FM requirements

XG8 – U.L. LISTED STEAM LIMIT CONTROL SWITCH Standard features: • 316 stainless steel welded diaphragm • setpoint indicating scale • adjusting nut stop

DIAPHRAGM SEALS

8

The Ashcroft pressure switch actuator is designed to satisfy most medium range pressure switch applications. It has only two wetted parts; pressure port and diaphragm. No O-rings are required because all joints are welded.

The Ashcroft medium pressure gas and oil limit control switch is designed for use with air, LP gas, natural gas, #1 and #2 fuel oil and #6 oil preheated to 240°F. This limit control is an adjustable pressure operated switch with a secondary chamber to prevent fuel from entering the switch enclosure in the unlikely event that the diaphragm develops a leak. The control shuts down a fuel pump in high or low pressure conditions.

The Ashcroft steam limit control switch is designed for use on boilers equipped with electrically operated burners. The limit control is an adjustable pressure operated switch set to stop burner operation when the recommended safe boiler working pressure is exceeded.

Any of the complete line of Ashcroft diaphragm seals may be used with most Ashcroft switches. See Bulletin DS-1.