The text of a manual · part 2 of 2
B-Series Switches: Pressure, Differential Pressure, Temperature, pages 9 to 16
Pages 9 to 16 of 16
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Ashcroft B424B
Page 9
OPTIONAL FEATURES AND ACCESSORIES
B-SERIES SWITCH OPTIONS
Code
Description
XBP XBX XCH XC8 XCN XFM
Wall Mounting Bracket in. H2O 1 ⁄2˝ Male NPT Bushing Chained Cover CSA Approval Cenelec EEx d IIC T6 FM Approval – Single Element FM Approval – Dual Element XFP Fungus Proofing XFS Factory Adjusted Setpoint XG3 Belleville Actuator XG4 Teflon Actuator and Pressure Conn. XG5 UL Limit Control to 150˝ H2O XG6 UL Limit Control to 600 psi XG7 Secondary Chamber with Vent XG8 Steam Limit Control to 300 psi XG9 Fire Safe Welded Actuator XHS High Static Diflerential Pressure High Pressure, 40 psi, (static) DIP XHX 160 psi (proof) DIP 100 psi proof pressure XJK Left Conduit Connection XJL 3⁄4˝ to 1⁄2˝ Reducing Bushing XK3 Terminal Block (700 Series only) XL9 Low Hardness SS Press. Conn. XNH Tagging Stainless Steel XPK Pilot Light(s) Top Mounted XPM 3⁄4˝ Sealed Conduit Connection with 16˝ Lead Wires XTA 316 Stainless Steel Pressure Connection for in. H2O Range XTM 2˝ Pipe Mounting Bracket XUD 316 Stainless Steel Pressure Conn. Pressure Connection: X06 1⁄2 NPT Male, 1⁄4 NPT Female 316 Stainless Steel (Combination) X07 1⁄2 NPTF Press. Conn., 316 SS X2B Breather Drain X6B Cleaned for Oxygen Service Diaphragm Seal
Appicable Switch Series Differential TempPressure Pressure erature All (psi) (in. H2O) (psi) (in. H2O) Ranges Notes
• • • • • • • • • •
• • • • • • •
• • • • • • • •
• • • • • • •
• • • •
17 17 • •
• • • • • • •
11
2 16,17 8 1, 17 1, 17 13 7 7 15
CENELEC APPROVAL FOR HAZARDOUS LOCATIONS CENELEC is a European designation that deals with standards for equipment and protective systems intended for use in potentially explosive atmospheres. This approval is required for switches intended for use in hazardous locations, especially important to OEMs who export to Europe and contractors specifying or purchasing products for European applications. XCN option adds special features to Ashcroft 700-Series switch enclosures that meet the requirements for the highest levels of security and danger, such as: • Special locking device requiring an Allen wrench to remove cover • Special vents that blow out should the diaphragm rupture, thus preventing pressure build-up in the enclosure • Special conduit plug requiring an Allen wrench for removal • Available on pressure, temperature and differential pressure models • Meets Explosion Class EEx d IIC T6
•
• • • • • •
• • •
• • •
• • •
• • •
• •
• •
• •
• •
•
•
•
•
•
•
9 6 12 4
Order option XCN
•
•
•
• •
•
•
•
•
•
• • • •
• • • •
• • • •
• •
•
5 10 • 3
•
NOTES: 1 Buna N and Viton diaphragm. 2 Advise static or working pressure for differential pressure switches. 3 Buna N cannot be cleaned for oxygen service. 4 N/A on 700 Series. 5 Standard with 1000 and 3000 psi ranges. Bottom connection only on DIP in H2O ranges. 6 Terminal Blocks standard with 700 dual switches. 7 Stainless steel diaphragm only.
8 Pressure connection 1⁄4 NPTF. 9 Standard on 700 Series. N/A with DPDT element on 400 Series. 10 N/A with Monel diaphragm. 11 Standard on 400 Series. 12 N/A on 3000 psi range. Available with Teflon diaphragm only. 13 SS diaphragm required. Teflon diaphragm is the backup. NEMA 7 only.
14 Available in ranges vacuum to 600 psi. Not available with stainless steel or Monel diaphragm. 15 Buna N and Viton diaphragm – 15#D & 30#D only. 16 24, 32, 64 or 68 element only. 17 N/A on all combinations
9
Page 10
PRODUCT SELECTION INFORMATION
SELECTION Before making your selection, consider the following: 1. Actuator The actuator responds to changes in pressure, temperature or differential pressure and operates the switch element in response to these changes. The actuator is normally exposed to process fluid and must therefore be chemically compatible with it. The following may be used to help select actuator type: For nominal pressure ranges 0-15 psi through 0-3000 psi, Dresser’s standard actuator is a diaphragm-sealed piston. In this actuator, process pressure acting on the piston area causes it to overcome the adjustment spring force and actuate a snap-action switch. A diaphragm and O-ring seal the process media from this mechanism. These are available in various materials, i.e.: Buna N, Teflon and Viton. The standard process connection is stainless steel. Optional Monel pressure connection is available.
10
For H2O Pressure and Differential Pressure Ranges, a diaphragm actuator is used. In this design, the standard pressure connections are carbon steel. Diaphragms are available in Viton, Buna N and Teflon. Always review process temperature limits before making seal selections. Optional stainless steel pressure connections are available (option XTA).
For High Differential Pressure Actuator Ranges, 3-15 to 60-600 psid, a Dual Diaphragm-Sealed Piston Actuator is used. This actuator is designed to for high staticpressure applications. The standard pressure connections are nickel-plated brass. Diaphragms are available in Viton, Buna N and Teflon. Always review process temperature limits before making seal selections. Optional stainless steel pressure connections are available (option XUD). For all temperature ranges the standard Ashcroft® temperature actuator operates on the vapor pressure principle: the vapor pressure in a sealed thermal system is applied to a sensing element, which in turn actuates a switch. This is known as a SAMA Class II system. Various filling materials are used, including Propane, Butane, Methyl Alcohol, N Propyl Alcohol and Xylene. High overtemperature capability is possible with this type of system. The interface between liquid and vapor is the point at which sensing occurs. This is the “sensitive” portion of the bulb. Bulb extensions and capillary are normally filled with vapor, and have little effect on the setpoint, regardless of ambient temperature variations; therefore, no ambient compensation is required. For best results, the bulb should be mounted within 60 degrees of vertical to assure the liquid remains in the bulb. 2. Enclosure The enclosure protects the switch element and mechanism from the environment and has provisions for mounting and wiring. All
Ashcroft switch enclosures are epoxy-coated aluminum or stainless steel for maximum corrosion resistance. Choose between watertight NEMA 4, 4X for most industrial applications and explosion-proof NEMA 7/9 for most process applications. Ashcroft enclosures include watertight cover gaskets, external mounting holes and one or two 3⁄4 NPT electrical conduit holes for ease of installation. Pressure switches may also be mounted directly to the process by means of the standard 1⁄4 NPTF or optional 1⁄2 NPT pressure connection. Note: When installing Ashcroft switches, refer to instruction sheets included with each switch, the National Electrical Code, and any other local codes or requirements to assure safety. 3. The Switching Function Next, consider the switching function. Most applications for alarm and shutdown are satisfied by single setpoint, fixed deadband models. For high/low or alarm and shutdown, the dual setpoint models may be selected. For pump, compressor, level and other control applications, an adjustable deadband model is often the best choice. Consult your Ashcroft representative for dual setpoint or adjustable-deadband pressure and temperature switches. 4. The Switch Element Finally, the electrical switching element must be compatible with the electrical load being switched. For ease of selection, all electrical switching elements are snap acting, SPDT
Page 11
PRODUCT SELECTION INFORMATION
(single pole-double throw), or 2 (SPDT). Refer to catalog pages for switch element choices. Select a switch element with electrical rating that exceeds the electrical rating of the device being controlled by the switch. For better reliability and safety, optional Hermetically Sealed switching elements may be specified. ADDITIONAL SWITCH TERMINOLOGY Accuracy – (see repeatability) Accuracy normally refers to conformity of an indicated value to an accepted standard value. There is no indication in switch products; thus, instead, the term repeatability is used as the key performance measure. Automatic Reset Switch – Switch which returns to normal state when actuating variable (pressure or temperature) is reduced. Adjustable or Operating Range – That part of the nominal range over which the switch setpoint may be adjusted. Normally about 15% to 100% of the nominal range for pressure and differential pressure switches and the full span for temperature switches. Burst Pressure – The maximum pressure that may be applied to a pressure switch without causing leakage or rupture. This is normally at least 400% of nominal range for Ashcroft switches. Switches subjected to pressures above the nominal range can be permanently damaged. Deadband – The difference between the setpoint and the reset point, normally expressed in units of the actuating variable. Sometimes referred to as differential. Division 1 – A National Electrical Code Classification of hazardous locations. In Division 1 locations, hazardous concentrations of flammable gases or vapors exist continuously, intermittently or periodically under normal conditions; frequently because of repair or maintenance operation/leakage or due to breakdown or faulty operation of equipment or processes which might also cause simultaneous failure of electrical equipment. Explosion-proof NEMA 7/9 enclosures are required in Division 1 locations. Division 2 – A National Electrical Code Classification of Hazardous locations. In Division 2 hazardous locations, flammable or volatile liquid or flammable gases are handled, processed or used, but will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown or in case of abnormal operation of equipment. Either Nema 7/9 explosion-proof enclosures or any enclosure with hermetically sealed switch contacts may be used in Division 2 locations.
Explosion Proof – A term commonly used in industry referring to enclosures capable of withstanding an internal explosion of a specified gas without igniting surrounding gases. Strict installation practices in accordance with the national electrical code are also required for safety. Fixed Deadband – The difference between the setpoint and the reset point of a pressure or temperature switch. It further signifies that this deadband is a fixed function of the pressure switch and not adjustable. Hermetically Sealed Switch – A switch element whose contacts are completely sealed from the environment to provide additional safety and reliability. Contact arc cannot cause an explosion, and atmospheric corrosive elements cannot affect the contacts. Manual Reset Switch – Pressure or Temperature switch in which contacts remain actuated even after the actuating variable returns to normal. On Ashcroft manual reset switches, a button must be pushed to reset the contacts. National Electrical Manufacturers Association (NEMA) – This group has defined several categories of enclosures, usually referred to as “types.” Further, they designate certain features and capabilities each type must include. For example, among other features, a NEMA 4 enclosure must include a threaded conduit connector, external mounting provision and cover gaskets. When selecting a NEMA 4 enclosure from any manufacturer, a buyer is assured of receiving these features. NEMA 4 – Watertight and dusttight enclosures intended for use indoors or outdoors to protect the equipment against splashing, falling or hose-directed water, external condensation and water seepage. They are also sleet-resistant. NEMA 4X – Watertight, dusttight and corrosion-resistant enclosures with same qualifications as NEMA 4, but with added corrosion resistance. NEMA 7 – Enclosures for indoor Class I, Division 1 Hazardous locations with gas or vapor atmospheres. NEMA 9 – Enclosures for indoor Class II, Division 1 Hazardous locations with combustible dust atmospheres. Normal Switch Position – Contact position before actuating pressure (or variable) is applied. Normally closed contacts open when the switch is actuated. Normally open contacts close when the switch is actuated. Normally Closed – Refers to switch contacts that are closed in the normal switch state or position (unactuated). A pressure change opens the contacts.
Normally Open Switch – Refers to the contacts that are open in the normal switch state or position (unactuated). A pressure change closes the contacts. Overpressure Rating(s) – A nonspecific term that could refer to either burst or proof pressure, or both. Proof Pressure – The maximum pressure which may be applied without causing damage. This is determined under strict laboratory conditions including controlled rate of change and temperature: This value is for reference only. Consult factory for applications where switch must operate at pressures above nominal range. Repeatability (Accuracy) – The closeness of agreement among a number of consecutive measurements of the output setpoint for the same value of the input under the same operating conditions, approaching from the same direction, for full-range traverses. Note: It is usually measured as nonrepeatability and expressed as repeatability in percent of span or nominal range. It does not include hysteresis or deadband. Reset Point – The reset point is the Pressure, Temperature or Differential Pressure Value where the electrical switch contacts will return to their original or normal position after the switch has activated. Setpoint – The setpoint is the Pressure, Temperature or Differential Pressure value at which the electrical circuit of a switch will change state or actuate. It should be specified either on increase or decrease of that variable. (See also reset point.) Single-Pole Double Throw (SPDT) Switching Element – A SPDT switching element has one normally open, one normally closed, and one common terminal. The switch can be wired with the circuit either normally open (N/O) or normally closed (N/C). SPDT is standard with most Ashcroft pressure and temperature switches. Snap Action – In switch terminology, snap action generally refers to the action of contacts in the switch element. These contacts open and close quickly and snap closed with sufficient pressure to firmly establish an electrical circuit. The term distinguishes products from mercury bottle types that were subject to vibration problems. Static Pressure – For differential pressure switches, static pressure refers to the lower of the two pressures applied to the actuator.
11
Page 12
ADDITIONAL PRESSURE AND TEMPERATURE SWITCH APPLICATION INFORMATION DIFFICULT PROCESS MEDIA
STEAM SERVICE
VIBRATION
When specifying pressure or temperature switches, the material in contact with media must be compatible with it. Otherwise, failure could occur, resulting in leakage, injury, and loss of life, property or production. The user should review prior experience with materials of construction in the process for guidance in material selection. If this is not appropriate, contact Dresser’s Control Instrument Operation for assistance. Relevant information such as process media, concentration of each constituent, temperature, pressure, the presence of contaminants, particulate, vibration or pulsation is necessary to make the best recommendation. Refer also to Product Information Page ASH-PI-14B “Corrosion Data Guide.”
In order to prevent live steam from coming into contact with the switch actuator, a siphon filled with water should be installed between the switch and the process line. We recommend the optional stainless steel welded process connection and diaphragm even though viton is rated for use with steam. Experience has shown that in many steam applications, the 300°F high temperature limit of Viton is exceeded by steam under pressure.
Generally, vibration will not harm Ashcroft pressure switches. However, premature tripping may occur under severe conditions. This tends to be annoying, but repeatable for a given situation and might be in the order of 5% to 10% of switch range from the setpoint, i.e. a 100 psi switch set at 50 psi on increasing pressure might trip somewhere between 40 and 45 psi on increasing pressure. This would not reduce the life of the pressure switch.
Some applications are best handled by adding an Ashcroft diaphragm seal to isolate the fluid media from the pressure or differential pressure switch. Diaphragm seals are recommended where: • The process media being sensed could clog the pressure element. • The process media temperature is above or below the ratings of the actuator seal materials. • The application calls for a sanitary process connection. Note: The addition of a diaphragm seal may increase the deadband and response time of the pressure switch to process pressure changes. Please consult the Control Instrument Operation for details. Refer also to Ashcroft Product Bulletin DS-1 and Product Information Page SW/PI-30B, “Switch, Diaphragm Seal Combination.”
In some boiler applications, a special U.L. listing, “MBPR,” which requires unique features, is needed. Dresser offers these features with option XG8. Refer also to Product Information Page SW/PI-27A, “Steam Limit Control Switch.” NACE The National Associations of Corrosion Engineers (NACE) publishes a standard covering the requirements of metallic materials in contact with process media containing Hydrogen Sulfide. We recommend the use of Monel (code P) wetted materials for most applications. Other alternatives include adding applicable diaphragm seals or low hardness stainless steel pressure connection (XL9) and teflon diaphragm. Refer also to Product Information Page SW-22A, “Pressure Switches Meeting NACE Standard MR-01-75.” HIGH TEMPERATURE PROCESS
OXIDIZING MEDIA When specifying a pressure switch for use in oxidizing media, such as chlorine, oxygen and several other chemical compounds, the wetted materials must be compatible with the media, and the switch should be cleaned for oxygen service. This is necessary to remove any residue that might react violently with the oxidizing media. Specify option X6B (clean for oxygen service). Refer also to Product Information Page SW/PI-6B, “Oxygen Cleaning for Ashcroft Switches.”
12
Refer to the actuator seal table for process temperature limits for pressure switch actuators. Pressure switches mounted directly to the process can withstand up to 300°F when equipped with optional Viton, stainless steel or Monel wetted parts. If process temperature exceeds 300°F, four feet of 1⁄2˝ tubing between the process and the switch will generally protect the switch from damage. Alternatively, an Ashcroft diaphragm seal selected from bulletin DS-1 can be used to isolate the switch from the hot process.
The best approach in this type of application is to mount the switch remotely, connecting the switch to the process or equipment with flexible tubing. If this is not possible, consider the use of the Belleville actuator, option XG3. Refer also to Product Information Page SW/PI58, “Belleville Actuator.” PULSATION Pressure pulsation below the range of the pressure switch will not harm it. However, because the switch can react to pressure pulses less than one-second duration, it might be desirable to include a dampening device. Several Ashcroft accessories such as snubbers address this situation. Refer to the accessory section of Ashcroft Ordering Handbook (OH-1), or consult your Ashcroft representative for more information. MOUNTING All Ashcroft pressure, temperature and differential pressure switches with snap acting contacts may be mounted in any position. This includes the sensing bulbs of temperature switches. This is an important advantage of snap acting switch designs.
Page 13
ADDITIONAL PRESSURE AND TEMPERATURE SWITCH APPLICATION INFORMATION SWITCH ELEMENT SELECTION B-Series switches are available with a wide variety of snap acting switch elements to meet most electrical requirements. The standard contact arrangement is single pole, double throw (S.P.D.T.). This includes both normally open and normally closed contacts. Standard contact material is fine silver which generally is suitable for switching 8 volts or more, up to the rating in the Switch Element Selection Table. When switching less than 8 volts, optional Gold Alloy contacts are recommended. Optional dual, or 2 S.P.D.T. contacts may be supplied in B-Series enclosures for applications requiring two switch functions at the same setpoint. These contacts are technically not double pole, double throw (D.P.D.T.). They are synchronized at the factory to actuate within 1% of nominal range of each other. For simultaneous actuation of 2 S.P.D.T. contacts, option XG3 should be ordered. Refer also to SW/PI-58 “Belleville Actuator.” HAZARDOUS LOCATIONS a. Division I. Ashcroft 700 series or other explosion proof enclosures are required to meet the requirements of Division I Hazardous Locations as defined by the National Electrical Code.
INFORMATION & GUIDELINES FOR SETTING ASHCROFT PRESSURE, TEMPERATURE AND DIFFERENTIAL PRESSURE SWITCHES All Ashcroft pressure, temperature and differential pressure switches can be set at any point between about 15% and 100% of the range as designated on the label or the nominal range table. Ashcroft pressure and temperature switches can be either set in the field or ordered from the factory preset to your requirements. When set at the factory, the specification is ±1% of the nominal range. Factory setting, or XFS, is a very popular option, and as a result, we often receive orders that do not have enough information or have incorrect information. HOW TO ORDER When “XFS” is desired: 1. Setpoint must be indicated. 2. Increasing or decreasing pressure must be indicated. Ex: B424B XFS 100# Set: 60# decreasing 3. For differential pressure switches, static operating pressure must also be specified.
b. Division II. These enclosures also meet the less stringent requirements for Division II Hazardous Locations. Alternatively, Ashcroft 400 series or other watertight enclosures with hermetically sealed switch elements are approved for use in Division II hazardous locations. c. Intrinsic Safety. Ashcroft 400 and 700 series pressure and temperature switches may be used with approved barriers in most intrinsically safe systems. These switches do not create or store energy and are therefore designated “simple devices’’ in these systems.
For other Ashcroft switch models request Ashcroft Bulletin, Switch Quick Guide QG-3 All product information pages mentioned in this bulletin can be downloaded from our web site. www.dresser.com/instruments
13
Page 14
TYPE 400 DIMENSIONS
Pressure switch – psi ranges
Pressure switch – inches of water ranges
B
I Ø 0.28 (3 Holes)
G
B
Ø 0.28 (3 Holes)
2.7 lb E
D
A
D
(1.2 kg)
H
A A (X06)
H
X06 Variation 1/2 NPT Male & 1/4 NPT Female
3/4 NPT
C
3/4 NPT
J
G 1/4 NPT Female
F
Ø 0.34 (2 Holes)
C
Bracket When Required “XBP” Variation I K
1/4 NPT Female
F E
A
B
C
D
E
F
G
A
B
C
D
E
F
G
H
I
5
4
31⁄4
35⁄16
23⁄4
25⁄16
13⁄16
1.8 lb
511⁄16
4
31⁄4
35⁄16
51⁄8
238⁄49
57⁄16
27⁄8
23⁄4
(83)
(84)
(70)
(59)
(30)
(.81 kg)
(144) (102)
(83)
(84)
(130)
(44)
(138)
(73)
(70)
(127) (102)
Differential pressure switch – inches of water ranges
Differential pressure switch – psi differential ranges A
D
Ø 0.28 (3 Holes)
B
C
Ø 0.28 (3 Holes)
E
2.7 lb A
D
(1.2 kg)
H
F H
3/4 NPT
1/4 NPT Female (DP Only)
1/4 NPT Low Pressure Inlet
1/4 NPT High Pressure Inlet
3/4 NPT
C
J
G Ø 0.34 (2 Holes) F E
B G
A
B
C
D
E
F
G
A
5
31⁄4
35⁄16
2⁄
23⁄4
71⁄8
25⁄16
3.6 lb
511⁄16
(102)
(83)
(84)
(59)
(70)
(181)
(59)
(1.6 kg)
(144) (102)
5 16
C
D
E
F
4
31⁄4
35⁄16
51⁄8
238⁄49
(83)
(84)
(130)
G
I
J
1
23⁄4
27⁄8
57⁄16
(44) (25.4) (70)
(73)
(138)
G H
Ø 0.28 (3 Holes)
I
C
H
B H
Ø 0.28 (3 Holes)
G
Temperature switch – remote mount
Temperature switch – direct mount B
B
Bracket When Required “XBP” Variation I K
1/4 NPT Female
C
A
I
A
3/4 NPT
3/4 NPT
7/8 Hex 1/2 NPT Male
F D
E
E “L” F
2-5/16 Active Bulb Length
2.5 lb (1.1 kg)
“S”
D
2.31 Active Bulb Length
Ø 3/8
J
Ø 3/8
14
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
45⁄8
4
35⁄16
31⁄4
15⁄8
47⁄8
25⁄16
13⁄16
45⁄8
4
35⁄16
31⁄4
15⁄8
25⁄16
13⁄16
3.5 lb
(84)
(83)
(41)
(124)
(59)
(30)
(117) (102)
(84)
(83)
(41)
(59)
(30)
(1.6 kg)
(117) (102)
Page 15
TYPE 700 DIMENSIONS
Pressure switch – psi ranges
Pressure switch – inches of water ranges E
B
HAZAR N PO WE DO TO U TI GH R B S TL E Y
CAUT IO
CAUT I
C AU T
C AU T
D’OU ION V M E T RI R TR . C E BI E
D
D’OU ION V M E T RI R TR . C E BI E
HAZAR ON PO WE DO TO U TI GH R B S TL E Y
H
.
.
D
G
G
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
E
E
H A
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
3/4 NPT (2 PLACES)
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
C
3/4 NPT (2 PLACES)
1/4 NPT FEMALE
F
0.28 THRU (3 PLACES)
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
A
E
B
F
0.28 THRU (3 PLACES)
3.6 lb
2.7 lb
I C
G
(1.2 kg)
BRACKET WHEN REQUIRED “XBP” VARIATION
1/4 NPT FEMALE
(1.6 kg)
J I
G
A
B
C
D
E
F
G
H
I
A
B
C
D
E
F
G
H
I
J
547⁄64
513⁄16
43⁄8
37⁄8
331⁄32
17⁄32
25⁄16
5⁄16
15⁄16
67⁄16
513⁄64
43⁄8
329⁄32
331⁄32
17⁄32
55⁄8
329⁄32
55⁄8
225⁄32
(146) (132) (111)
(99)
(100)
(31)
(59)
(8)
(49)
(164) (132) (111)
(99)
(96)
(31)
(59)
(8)
(130)
(71)
Differential pressure switch – inches of water ranges
Differential pressure switch – psi differential ranges
C AU T
C AU T
D’OU ION V M E T RI R TR . C E BI E
D
D’OU ION V M E T RI R TR . C E BI E
CAUT I
.
.
D
H
G
H
G
CAUT ION
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
E
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
HAZAR PO WE DO TO U TI GH R B S TL E Y
F
0.28 THRU (3 PLACES)
F
E
A
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
A
E
B
E 0.28 THRU (3 PLACES)
HAZAR ON PO WE DO TO U TI GH R B S TL E Y
B
1/4 NPT FEMALE (DP ONLY)
3/4 NPT (2 PLACES)
C
3/4 NPT (2 PLACES)
C
1/4 NPT LOW PRESSURE INLET
1/4 NPT HIGH PRESSURE INLET
J I
4.5 lb (2.0 kg)
3.6 lb
BRACKET WHEN REQUIRED “XBP” VARIATION
1/4 NPT FEMALE
G
(1.6 kg)
G
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
I
J
725⁄32
513⁄64
43⁄8
37⁄8
331⁄32
17⁄32
25⁄16
5⁄16
67⁄16
513⁄64
43⁄8
329⁄32
331⁄32
17⁄32
55⁄8
329⁄32
55⁄8
225⁄32
(198) (132) (111)
(99)
(100)
(31)
(59)
(8)
(164) (132) (111)
(99)
(96)
(31)
(59)
(8)
(130)
(71)
Temperature switch – direct mount B
Temperature switch – remote mount
E
B
F
.
C AU T
C AU T
D’OU ION V M E T RI R TR . C E BI E
D
D’OU ION V M E T RI R TR . C E BI E
CAUT
.
D
H
G
H
G
CAUT IO
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
E
HAZAR N PO WE DO TO U TI GH R B S TL E Y
F
E
IGNITION O F EN T EV SPHERE TUR N P R MO OPENING. C OFF AT RE RE O PER L OS AT FO EF O IN B
A
E 0.28 THRU (3 PLACES)
HAZARION PO WE DO TO U TI GH R B S TL E Y
0.28 THRU (3 PLACES)
A
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
LE COUR ANT E R RMER AVANT AVA . UP F E D E NT O N RVICE E SE N
3/4 NPT (2 PLACES)
J
3/4 NPT (2 PLACES)
G
7/8 HEX 1/2 NPT MALE
I
I L
J
C
C
S
2.31 (59) ACTIVE BULB LENGTH
3.7 lb
G
4.5 lb
(1.7 kg)
(2.0 kg)
0.379 (9)
2.31 (59) ACTIVE BULB LENGTH
3.00 (76)
0.379 (9)
A
B
C
D
E
F
G
H
I
J
A
B
C
D
E
F
G
H
I
J
515⁄64
513⁄64
43⁄8
37⁄8
331⁄32
17⁄32
25⁄16
5⁄16
15⁄16
27⁄16
515⁄64
513⁄64
43⁄8
37⁄8
331⁄32
17⁄32
25⁄16
5⁄16
21⁄2
27⁄16
(133) (132) (111)
(99)
(100)
(31)
(59)
(8)
(33)
(62)
(133) (132) (111)
(99)
(100)
(31)
(59)
(8)
(63)
(62)
15
Page 16
Instrument Division Sales and Customer Service Locations U.S. Headquarters
International Headquarters
Control Instrument Operation Milford, Connecticut 210 Old Gate Lane Milford, CT 06460 Tel: (203) 878-5641 Fax: (203) 877-8519
Stratford, Connecticut 250 E. Main Street Stratford, CT 06614-5145 Tel: (203) 378-8281 Fax: (203) 385-0357 International Operations
U.S. Sales Offices Chicago, Illinois 400 W. Lake Street Suite 318 Roselle, IL 60172-3573 Tel: (630) 980-9030 Fax: (630) 980-9440 Hartford, Connecticut 1501 East Main Street Meriden, CT 06450-2860 Tel: (203) 235-0450 Fax: (203) 235-0593 Houston, Texas 3838 North Sam Houston Parkway East Suite 120 Houston, TX 77032 Tel: (281) 590-1092 Fax: (281) 590-7100 Los Angeles, California 3931 MacArthur Blvd. Suite 202 Newport Beach, CA 92660 Tel: (949) 852-8948 Fax: (949) 852-8971 Mobile, Alabama 851 South Beltline Highway Suite 402, 4th Floor Mobile, AL 36606 Tel: (334) 473-1692 Fax: (334) 473-1782
Japan Dresser Japan Inc. Room 318, Shin Tokyo Building 3-1 Marunouchi 3-Chome, Chiyoda-ku, Tokyo, Japan Tel: 813-3201-1501/1506 Fax: 813-3213-6567/6673 Korea Dresser International S.A. Korea Office #2015 Kuk Dong Bldg. 60-1, 3-KA, Choongmu-Ro, Chungku, Seoul, Korea 100-705 Tel: 82-2-2274-079-2/3 Fax: 82-2-2274-0794
Brazil Dresser Industria e Comercio Ltda. Divisao Manometros Willy Rua Senador Vergueiro No. 433 09521-320 Sao Caetano do Sul Mexico Sao Paulo, Brazil Dresser Instrument Division Tel: 55-11-453-5477 Henry Ford No. 114, Fax: 55-11-453-8710 Esq. Foulton, Fracc Industrial San Nicolas Canada 54030 Tlalnepantla edo Dresser Canada, Inc. de Mexico 54030 2135 Meadowpine Blvd. Tel: 525-310-7217 Mississauga, Fax: 525-310-2608 Ontario L5N 6L5 Canada Saudi Arabia Tel: 905-826-8411 Dresser Al Rushaid Fax: 905-826-9106 (DARVICO) P.O. Box 10145 China Jubail Industrial City Dresser Trading Saudi Arabia 31961 Room 2403, 24th Floor Tel: 966-3-341-0278 CITIC Bldg. Fax: 966-3-341-7624 19 Jianguo Menwai St. Beijing, P.R.C. Singapore Tel: 86-10-6500-3139 Dresser Singapore Pte Ltd. Fax: 86-10-6512-0300 Instrument Operations Block 1004 Toa Payoh North France #07-15/17 Dresser Europe GmbH Singapore 318995 Division Instrumentation Tel: 65-252-6602 74, Rue d’ Arceuil Fax: 65-252-6603 F-94578, Silic 265, France United Kingdom Tel: 33-01-49-79-22-59 Dresser Europe GmbH Fax: 33-01-46-86-25-24 East Gillibrands, Skelmersdale, Germany Lancashire WN8 9TU Dresser Europe GmbH United Kingdom Postfach 11 20 Tel: 44-16-95-52600 Max-Planck-Str. 1 Fax: 44-16-95-52693 D-52499 Baesweiler Germany Venezuela Tel: 49-2401-8080 Manufacturas Petroleras Fax: 49-2401-7027 Venezolanas S.A. KM 7 Carretera A El Mojan Calle 18, #15B355 ZONA Maracaibo Edo Zulia, Venezuela Tel: 58-61-579-762 or 070 Fax: 58-61-579-461
Visit our web site www.dresser.com/instruments A Halliburton Company
All specifications are subject to change without notice. All sales subject to standard terms and conditions. © Dresser Equipment Group, Inc. 20M CP 3P8/99