Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 27 of 33

Power Focus 3000: Control and Drive Unit for TENSOR-S Electric Nut Runners: User Interfaces, pages 253 to 262

Pages 253 to 262 of 315, from Power Focus 3000: Control and Drive Unit for TENSOR-S Electric Nut Runners

The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Atlas Copco PF3007-C-HW and Atlas Copco PF3007-G-HW

Page 253

Appendix B

22

Appendix B: Description of connecting devices

22.1

Printer

Connector: 25-pin DSUB female. Function: Parallel printer Electrical data: Normal TTL levels. High level signal = 1 Outputs Inputs High > 2.4 V High > 2.0 V Low < 0.4 V Low < 0.8 V Pin 1 2 3

Function Strobe Data bit 0 Data bit 1

Pin 10 11 12

4 5 6 7 8 9

Data bit 2 Data bit 3 Data bit 4 Data bit 5 Data bit 6 Data bit 7

13 14 15 16 17 18

Function Acknowledge Busy Paper end (out of paper) Select Auto feed Error Initialise printer Select input Ground

Pin 19 20 21

Function Ground Ground Ground

22 23 24 25

Ground Ground Ground Ground

253

Page 254

Appendix B

22.2

Serial RS232 #1

Connector: 9-pin DSUB female. Function: RS232 serial. Pin 1 2 3 4 5 6 7 8 9

Function Not used RD, Receive data TD, Transmit data Not used GND Not used Not used Dig in. Not used Dig out. Not used

22.3

Serial RS232 #2

Connector: 9-pin DSUB female. Function: RS232 serial connection. Use crossover cable to connect to PC. Pin 1 2 3 4 5 6 7 8 9

254

Function Not used RD, Receive data TD, transmit data +5V ma x 200 mA GND Not used Not used Not used Not used

Page 255

Appendix B

22.4

Ethernet

Connector: Shielded RJ45 for 10-baseT connection Function: 10 Mbit Ethernet communication. Pin 1 2 3 4 5 6 7 8

Function Out inverse Out In inverse ------In Inverse -------

22.5

RBU

Connector: 15-pin DSUB female. Function: For connection of Atlas Copco RBU. The RBU (Rapid Backup Unit) unlocks the software you need and works as a backup memory for your PF3000 set-up data. The pin configuration is propriety information for Atlas Copco. This connector cannot be used for other purposes.

255

Page 256

Appendix B

22.6

Tool Connector

Connector: (16 + 4) pin Function: For connection of Atlas Copco Tensor electric tools. Pin A B C D E F G H J K L M N P R S 1 2 3 GND

256

Description +5 VDC, Excitation tq transducer bridge -5 VDC, Excitation tq transducer bridge +Signal from tq transducer - Signal from tq transducer Signal ground (connected to safety ground and cabinet) Tool commutation signal, Sines Tool commutation signal, Cosines +8/12VDC to tool memory, lights and commutation GND (0V) to tool memory, lights, commutation and temp, start-, stop- and rev-switch. Motor temp signal Start and reverse switch input Tool memory, clock Tool memory, data Yellow tool light Green tool light Red tool light Motor R-phase Motor S-phase Motor T-phase Safety power ground

Page 257

Appendix B

22.7

Digital Input

Connector: 10-pin detachable screw terminal. Mating connector Phoenix MCVR 1.5/10 -ST- 3.81 or compatible. Function: Isolated opto-coupled digital input. Logical function is set in the configuration of the Power Focus 3000. Electrical data: “High” input (10 - 40) VDC. Current needed to activate input is 5 mA at 24 V. This input can be connected to run both positive and negative logic (active high or active low). Isolated 24 VDC output. (19 V - 30 V) 1 A maximum load. This output can be used to feed external equipment such as Stack lights and buzzers. Atlas Copco I/O bus accessories are also powered from this output. Pin 13 14 15 16 17 18 19 20 21 22

Function Digital input 1 + Digital input 1 Digital input 2 + Digital input 2 Digital input 3 + Digital input 3 Digital input 4 + Digital input 4 + 24 VDC isolated GND (+24VDC isolated)

2.7k

2.7k

257

Page 258

Appendix B

22.8

Relays

Connector: 12-pin detachable screw terminal. Mating connector Phoenix MCVR 1.5/10 -ST3.81 or compatible. Function: Two way dry contact relays. Isolated outputs. Logical function is set in the configuration of the Power Focus 3000. Electrical data: Max 50 V DC/AC. Switching load: min 1 mA, max 500 mA resistive load.

Pin 1 2 3 4 5 6 7 8 9 10 11 12

258

Function Relay 1 Normally open Relay 1 common Relay 1 Normally closed Relay 2 Normally open Relay 2 common Relay 2 Normally closed Relay 3 Normally opened Relay 3 common Relay 3 Normally closed Relay 4 Normally opened Relay 4 common Relay 4 Normally closed

Page 259

Appendix B

22.9

I/O-bus #1

Connector: 9-pin DSUB male. Function: To connect Atlas Copco I/O-bus accessories and interconnect several Power Focus 3000 in synchronisation mode. Parallel with I/O bus connector #2. There is a range of Power Focus accessories that connect over the proprietary Power Focus I/O bus, for example: - Selector (socket tray) - RE alarm - I/O-expander To have a well functioning I/O bus, always use bus terminations. All accessories and Power Focus units are equipped with two parallel connectors. When all cables are connected, place a termination in the empty connectors. I/O bus connectors #1 and #2 are fully parallel and can be used in any combination. If nothing is connected to the I/O bus there is no need for terminations. Note! Read the Sync chapter for I/O bus sync configuration information. Pin 1 2 3 4 5 6 7 8 9

Function +24 V iso. Signal Low 0 V (+8V iso) 0 V (+24 V iso) Not used 0 V (+8V iso) Signal High Not used +8 V iso. (Note: I/O bus only)

259

Page 260

Appendix B

22.10 I/O-bus #2 Connector: 9-pin DSUB male. Function: To connect Atlas Copco I/O bus accessories and interconnect several Power Focus 3000 in synchronisation mode. Parallel with I/O bus connector #1.

260

Page 261

Appendix B

22.11 Remote start connector Connector: 4-pin detachable screw terminal. Mating connector Phoenix MCVR 1.5/04 –ST-3.81 or compatible. Function: Remote Start input for use with external start switch. To run tool in reverse, first close the reverse switch and then close the start switch. Pin 1 and 2 must be connected at power on to be able to use the built- in tool trigger. If remote start is to be controlled from other inputs (I/O expander, FieldBus or digital inputs), pins 2 and 4 must be connected at power on. Pin 1 2 3 4

Function Tool built-in start switch Common Remote reverse Remote start

Remote start wiring diagram Start

4

4

4

3

3

3

2

2

1

1

1

Remote Control

Start and direction controlled from the tool trigger.

Start and direction controlled from I/Obus, FieldBus or digital inputs.

2

Reverse

Note! Make sure that the power is switched off when changing the Remote Start Connector.

261

Page 262

Appendix B

22.12 Mains power connector Connector: IEC320 Electrical data: Input voltage (90 - 120) VAC, (200 - 240) VAC, (50 - 60) Hz. Auto select of voltage input span.

22.13 FieldBus connector See Chapter “FieldBus ”.

262