Chapter 3: CPU Specifications and Operations Feature

DL230

DL240

DL250–1

DL260

1 2 3 4 5 6 Math 7 ASCII PID Loop Control, Built In 8 Time of Day Clock/Calendar Run Time Edits 9 Supports Overrides Internal diagnostics 10 Password security System error log 11 User error log Battery backup 12 CPU Base Electrical Specifications 13 Specification AC Powered Bases 24 VDC Powered Bases 125 VDC Powered Bases 14 Part Numbers A Input Voltage Range Maximum Inrush Current B Maximum Power Voltage Withstand (dielectric) Insulation Resistance C Auxiliary 24 VDC Output D Fusing (internal to base power Number of instructions available (see Chapter 5 for details) Control relays Special relays (system defined) Stages in RLLPLUS Timers Counters Immediate I/O Interrupt input (hardware / timed) Subroutines Drum Timers Table Instructions For/Next Loops

92

129

240

297

256 112 256 64 64 Yes Yes / No No No No No

256 144 512 128 128 Yes Yes / Yes Yes No No Yes

1024 144 1024 256 128 Yes Yes / Yes Yes Yes No Yes

Integer

Integer

Integer, Floating Point

No No No Yes No Yes Yes No No Yes (optional)

No No Yes Yes Yes Yes Yes Yes Yes Yes (optional)

Yes, OUT Yes, 4 Loops Yes Yes Yes Yes Yes Yes Yes Yes (optional)

2048 144 1024 256 256 Yes Yes / Yes Yes Yes Yes Yes Integer, Floating Point, Trigonometric Yes, IN/OUT Yes, 16 Loops Yes Yes Yes Yes Yes Yes Yes Yes (optional)

D2–03B–1 D2–04B–1 D2–06B–1 D2–09B–1

D2–03BDC1–1 D2–04BDC1–1 D2–06BDC2–1 D2–06BDC1–1 D2–09BDC2–1 D2–09BDC1–1 10.2–28.8 VDC (24VDC) 100–240 VAC +10% –15% 104–240 VDC +10% –15% with less than 10% ripple 30A 10A 20A 80VA 25W 30W 1 minute @ 1500VAC between primary, secondary, field ground, and run relay > 10Mq at 500VDC 20–28 VDC, less than 1V p-p 20–28 VDC, less than 1V p-p None 300mA max. 300mA max.

supply)

Non–replaceable 2A @ 250V slow blow fuse

Non–replaceable 3.15 A @ 250V slow blow fuse

Non–replaceable 2A @ 250V slow blow fuse

DL205 User Manual, 4th Edition, Rev. D

3-5

Page 102

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

CPU Hardware Setup Communication Port Pinout Diagrams Cables are available that allow you to quickly and easily connect a Handheld Programmer or a personal computer to the DL205 CPUs. However, if you need to build a cable(s), use the pinout descriptions shown on the following pages. You can also use the Tech Support/Cable Wiring diagrams located on our website. The DL240, DL250–1 and DL260 CPUs have two ports while the DL230 has only one. All of the CPUs require at least one RJ-12 connector. The DL250-1 and DL260 require one 15 pin D-shell connector.

Port 1 DL250–1 and DL260 RJ12 Phone Jack RS-232, 9600 baud Communication Port –K-sequence –DirectNET slave –Modbus RTU slave –easily connect DirectSOFT, handhelds, operator interfaces, any DirectNet master

3-6

RUN CPU

PWR BATT

DL230 CPU

DL260 Port 2 DL250–1 and DL260 15-pin HD Connector RS-232/RS-422, up to 38.4K baud Communication Port –K-sequence –DirectNET Master/Slave –Modbus RTU Master/Slave –easily connect DirectSOFT, handhelds, operator interfaces, any DirectNet or Modbus master or slave

Port 1 RJ12 Phone Jack RS-232, 9600 baud Communication Port –K-sequence –easily connect DirectSOFT, handhelds, operator interfaces, etc. Port 2

PORT ?1

RJ12 Phone Jack RS-232, up to 19.2K baud Communication Port –K-sequence –DirectNET slave –easily connect DirectSOFT, handhelds, operator interfaces, or any DirectNet master

DL205 User Manual, 4th Edition, Rev. D

Port 2 Additional DL260 Features –ASCII IN/OUT Instructions –Extended Modbus Instructions –RS-485 support

PWR BATT

RUN CPU

DL240 CPU

RUN TERM CH1 CH2 CH3 CH4

PORT1

PORT2

Page 103

Chapter 3: CPU Specifications and Operations

Port 1 Specifications

1 2 • Connect to DirectSOFT, D2–HPP, DV–1000, HMI panels 3 • Fixed station address of 1 • 8 data bits, one stop 4 • Asynchronous, Half–duplex, DTE • Odd parity 5 Port 1 Pin Descriptions (DL230 and DL240) 6 7 6-pin Female Modular Connector 8 Port 1 Specifications 9 The operating parameters for Port 1 on the DL250–1 and DL260 CPU are fixed. This applies to the DL250 as well.

10 • 6-pin female modular (RJ12 phone jack) type connector

• K–sequence protocol (slave only)

11 • DirectNET (slave only) • Modbus RTU (slave only) - supported only on D2-250-1 and D2-260 12 • RS-232, 9600 baud • Connect to DirectSOFT, D2–HPP, DV1000 or DirectNET master 13 • 8 data bits, one start, one stop • Asynchronous, Half–duplex, DTE 14 • Odd parity Port 1 Pin Descriptions (DL250-1 and DL260) A B 6-pin Female C Modular Connector D NOTE: The 5V pins are rated at 200mA maximum, primarily for use with some operator interface units. 230 The operating parameters for Port 1 on the DL230 and DL240 CPUs are fixed. • 6-pin female modular (RJ12 phone jack) type connector 240 250-1 • K–sequence protocol (slave only) • RS-232, 9600 baud 260

1

6

1 2 3 4 5 6

0V 5V RXD TXD 5V 0V

Power (–) connection (GND) Power (+) connection Receive Data (RS-232) Transmit Data (RS-232) Power (+) connection Power (–) connection (GND)

1 2 3 4 5 6

0V 5V RXD TXD 5V 0V

Power (–) connection (GND) Power (+) connection Receive Data (RS-232C) Transmit Data (RS-232C Power (+) connection Power (–) connection (GND)

230 240

250-1 260

1

6

DL205 User Manual, 4th Edition, Rev. D

3-7

Page 104

Chapter 3: CPU Specifications and Operations

Port 2 Specifications operating parameters for Port 2 on the DL240 CPU are configurable using Aux functions 1 The on a programming device.

• female modular (RJ12 phone jack) 2 type connector

• K–sequence protocol, DirectNET (slave), 3 • RS-232, Up to 19.2K baud 6-pin Female Modular Connector • Address selectable (1–90) Port 2 Pin Descriptions (DL240 only) 4 • to DirectSOFT, D2–HPP, DV-1000, HMI, or DirectNET master • 8 data bits, one start, one stop 5 • Asynchronous, Half–duplex, DTE • Odd or no parity 6 2 Specifications 7 Port Port 2 on the DL250-1 and DL260 CPUs is located on the 15-pin D-shell connector. It is configurable using AUX functions on a device. This applies to the 8 programming DL250 as well. • 15-Pin female D type connector 9 • K-sequence, DirectNET Master/ Slave, Modbus RTU Master/Slave, Remote 10 I/O, (ASCII IN/OUT DL260 only) • non-isolated, distance within 15m (approximately 50ft) 11 • non-isolated, distance within 1000 m (approximately 3280ft) 12 Port 2 Pin Descriptions (DL250–1 / DL260) • non–isolated, distance within 1000m (DL260 only 13 • Up to 38.4 K baud • Address selectable (1–90) 14 • to DirectSOFT, D2–HPP, operator interfaces, any DirectNET or Modbus master/slave, (ASCII devices-DL260 A only) • 8 data bits, one start, one stop B • Half–duplex, DTE Remote I/O C • Odd/even/none parity D 230 240

1

250-1

6

260

1 2 3 4 5 6

0V 5V RXD TXD RTS 0V

Power (–) connection (GND) Power (+) connection Receive Data (RS-232) Transmit Data (RS-232) Request to Send Power (–) connection (GND)

230 240

250-1

1

260

6

11

10

5

15

15-pin Female D Connector

1 5V 5VDC 2 TXD2 Transmit Data (RS-232) 3 RXD2 Receive Data (RS-232) 4 RTS2 Ready to Send (RS–232) 5 CTS2 Clear to Send (RS–232) 6 RXD2 – Receive Data – RS–422) (RS–485 DL260) 7 0V Logic Ground 8 0V Logic Ground 9 TXD2 + Transmit Data + (RS–422) (RS–485 DL260) 10 TXD2 – Transmit Data – (RS–422) (RS–485 DL260) 11 RTS2 + Request to Send + (RS–422) (RS–485 DL260) 12 RTS2 – Request to Send – (RS–422)(RS–485 DL260) 13 RXD2 + Receive Data + (RS–422) (RS–485 DL260) 14 CTS2 + Clear to Send + (RS422) (RS–485 DL260) 15 CTS2 – Clear to Send – (RS–422) (RS–485 DL260)

3-8

DL205 User Manual, 4th Edition, Rev. D

Page 105

Chapter 3: CPU Specifications and Operations

Selecting the Program Storage Media

1 The DL230 and DL240 CPUs provide built-in EEPROM storage. This type of memory is non-volatile and is not dependent on battery backup to retain the program. The EEPROM 2 can be electrically reprogrammed without being removed from the CPU. You can also set Jumper 3, which will write protect the EEPROM. The jumper is set at the factory to allow 3 changes to EEPROM. If you select write protection by changing the jumper position, you cannot make changes to the program. 4 WARNING: Do NOT change Jumper 2. This is for factory test operations. If you change Jumper 2, the CPU will not operate properly. 5 6 7 8 EEPROM 9 EEPROM Sizes 10 The DL230 and DL240 CPUs use different sizes of EEPROMs. The CPUs come from the factory with EEPROMs already installed. However, if you need extra EEPROMs, select one 11 that is compatible with the following part numbers. CPU Type EEPROM Part Number Capacity 12 13 EEPROM Operations Many AUX functions are specifically for use with an EEPROM in the Handheld Programmer. 14 This enables you to quickly and easily copy programs between a program developed offline in the Handheld Programmer and the CPU. Also, you can erase EEPROMs, compare them, etc. A See the DL205 Handheld Programmer Manual for details on using these AUX functions with the Handheld Programmer. B NOTE: If the instructions are supported in both CPUs and the program size is within the limits of the DL230, you can move a program between the two CPUs. However, the EEPROM installed in the Handheld C Programmer must be the same size as (or larger than) the CPU being used. For example, you could not install a DL240 EEPROM in the Handheld Programmer and download the program to a DL230. Instead, if the program is within the size limits of the DL230, use a DL230 chip in the Handheld when you obtain the D program from the DL240. Built-in EEPROM

230 240

250-1 260

Jumper in position shown selects write protect for EEPROM

DL230 DL240

Hitachi HN58C65P–25 Hitachi HN58C256P–20

8K byte (2Kw) 32K byte (3Kw)

DL205 User Manual, 4th Edition, Rev. D

3-9

Page 106

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Installing the CPU CPU must be installed in the first slot in the base (closest to the power supply). You 230 The cannot install the CPU in any other slot. When inserting the CPU into the base, align the 240

PC board with the grooves on the top and bottom of the base. Push the CPU straight into 250-1 the base until it is firmly seated in the backplane connector. Use the retaining clips to secure 260 the CPU to the base.

3-10

WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component.

Retaining Clips

CPU must reside in first slot!

Connecting the Programming Devices The handheld programmer is connected to the CPU with a Handheld Programmer cable. You can connect the Handheld Programmer to either port on a DL240 CPU. The Handheld Programmer is shipped with a cable. The cable is approximately 6.5 ft (200cm).

Connect Handheld to either Port

If you are using a Personal Computer with the DirectSOFT programming package, you can use either the top or bottom port.

Connect PC to either Port

DL205 User Manual, 4th Edition, Rev. D

Page 107

Chapter 3: CPU Specifications and Operations

Status Indicators

1 2 3 4 5 6 7 8 9 10 11 CPU Setup Information Even if you have years of experience using PLCs, there are a few tasks you need to do before 12 you can start entering programs. This section includes some basic tasks, such as changing the CPU mode, but it also includes some tasks that you may never have to use. Here’s a brief list 13 of the items that are discussed: • Using auxiliary functions 14 • Clearing the program (and other memory areas) • How to initialize system memory A • Setting retentive memory ranges The following paragraphs provide the setup information necessary to ready the CPU for programming, including set-up instructions for either type of programming device you are B using. The D2–HPP Handheld Programmer Manual provides the Handheld keystrokes required to perform all of these operations. The DirectSOFT Manual provides a description of C the menus and keystrokes required to perform the setup procedures via DirectSOFT. D PWR

PWR BATT

RUN CPU

BATT

DL240

Port 1

DL230

RUN CPU

CPU

CPU

Mode Switch

RUN

TERM CH1 CH2 CH3 CH4

Adjustments

PORT1

Port 2

PORT1

Analog

PORT? 2

Status Indicators

DL260

DL250-1

Mode Switch Port 1

Port 2

Battery Slot

DL205 User Manual, 4th Edition, Rev. D

3-11

Page 108

Chapter 3: CPU Specifications and Operations

Status Indicators The status indicator LEDs on the CPU front panels have specific functions that can help in programming and troubleshooting. 1 2 Indicator Status Meaning PWR 3 RUN 4 CPU 5 BATT 6 7 Mode Switch Functions The mode switch on the DL240, DL250–1 and DL260 CPUs provides positions for enabling and disabling program changes in the CPU. Unless the mode switch is in the TERM position, 8 RUN and STOP mode changes will not be allowed by any interface device, (Handheld Programmer, DirectSOFT programing package or operator interface). Programs may be 9 viewed or monitored but no changes may be made. If the switch is in the TERM position and no program password is in effect, all operating modes as well as program access will be allowed through the connected programming or monitoring device. 10 The CPU mode can be changed in two ways: 11 • Use the CPU mode switch to select the operating mode. • the CPU mode switch in the TERM position and use a programming device to change operating modes. In this position, you can change between Run and Program modes. 12 NOTE: If the PLC is switched to the RUN Mode without a program in the CPU, the CPU will produce a 13 FATAL ERROR which can be cleared by cycling the power to the PLC. 14 Mode Switch Position CPU Action A RUN (Run Program) B TERM (Terminal) C STOP (DL250–1 and DL260 only Stop Program) D ON OFF ON OFF Blinking ON OFF ON

Power good Power failure CPU is in Run Mode CPU is in Stop or Program Mode CPU is in Firmware Upgrade Mode CPU self diagnostics error CPU self diagnostics good Low battery voltage (only with System Memory bit B7633.12 set)

OFF

CPU battery voltage is good or disabled

CPU is forced into the RUN mode if no errors are encountered. No changes are allowed by the attached programming/monitoring device.

RUN, PROGRAM and the TEST modes are available. Mode and program changes are allowed by the programming/monitoring device. CPU is forced into the STOP mode. No changes are allowed by the programming/monitoring device.

3-12

DL205 User Manual, 4th Edition, Rev. D

Page 109

Chapter 3: CPU Specifications and Operations

Changing Modes in the DL205 PLC

1 RUN (Run Program) 2 TERM (Terminal) RUN 3 STOP 4 The CPU mode can be changed in two ways: you can use the CPU mode switch to select the operating mode, or you can place the mode switch in the TERM position and use a 5 programming device to change operating modes. With the switch in this position, the CPU can be changed between Run and Program modes. You can use either DirectSOFT or the Handheld Programmer to change the CPU mode of operation. With DirectSOFT use the 6 PLC menu option PLC > Mode or use the Mode button located on the Online toolbar. With the Handheld Programmer, use the MODE key. 7 8 9 10 11 PLC Menu 12 MODE Key Mode of Operation at Power Up 13 The DL205 CPUs will normally power up in the mode that it was in just prior to the power interruption. For example, if the CPU was in Program Mode when the power was disconnected, 14 the CPU will power up in Program Mode (see warning note below). WARNING: Once the super capacitor has discharged, the system memory may not retain the previous A mode of operation. When this occurs, the PLC can power-up in either Run or Program Mode if the mode switch is in the term position. There is no way to determine which mode will be entered as the startup mode. Failure to adhere to this warning greatly increases the risk of unexpected equipment startup. B The mode in which the CPU will power up in is also determined by the state of System Memory bit B7633.13. If the bit is set and the Mode Switch is in the TERM position, the C CPU will power-up in RUN mode. If B7633.13 is not set with the Mode Switch in TERM position, then the CPU will power up in the state it was in when it was powered down. D Mode Switch Position

CPU Action

CPU is forced into the RUN mode if no errors are encountered. No changes are allowed by the attached programming/ monitoring device. PROGRAM and the TEST modes are available. Mode and program changes are allowed by the programming/monitoring device. CPU is forced into the STOP mode. No changes are allowed by the programming/monitoring device.

DL205 User Manual, 4th Edition, Rev. D

3-13

Page 110

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Using Battery Backup

3-14

An optional lithium battery is available to maintain the system RAM retentive memory when the DL205 system is without external power. Typical CPU battery life is five years, which includes PLC runtime and normal shut-down periods. However, consider installing a fresh battery if your battery has not been changed recently and the system will be shut down for a period of more than ten days. NOTE: Before installing or replacing your CPU battery, back up your V-memory and system parameters. You can do this by using DirectSOFT to save the program, V-memory, and system parameters to hard/floppy disk on a personal computer.

To install the D2–BAT CPU battery in DL230 or DL240 CPUs: 1. push the battery connector onto the circuit board connector. 2. the battery into the retaining clip. Don’t use excessive force. You may break the retaining clip. 3. Make a note of the date the battery was installed.

DL250-1 and DL260 -1

DL230 and DL240 DL230 and DL240

To install the D2–BAT–1 CPU battery in the DL250–1/DL260 CPUs: (#CR2354) 1. the retaining clip on the battery door down and swing the battery door open. 2. the battery into the coin–type slot with the +, or larger, side out. 3. Close the battery door making sure that it locks securely in place. 4. Make a note of the date the battery was installed.

WARNING: Do not attempt to recharge the battery or dispose of an old battery by fire. The battery may explode or release hazardous materials.

Battery Backup The battery backup is available immediately after the battery has been installed in the DL205 CPUs. The battery low (BATT) indicator will turn on if the battery is less than 2.5VDC (refer to the Status Indicator table on page 3-12). Special Relay 43 (SP43) will also be activated. The low battery indication is enabled by setting bit 12 of V7633 (B7633.12). If the low-battery feature is not desired, do not set bit V7633.12. The super capacitor will retain memory IF it is configured as retentive regardless of the state of B7633.12. The battery will be the same, but for a much longer time.

DL205 User Manual, 4th Edition, Rev. D