Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 10 of 60

DL205 PLC User Manual, Volume 1 of 2, pages 91 to 100

Pages 91 to 100 of 598

The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D2-04TD1, AutomationDirect D2-08TD2, AutomationDirect D2-16ND3-2, AutomationDirect D2-32ND3, Konnect-It D2-04TD1, Koyo D2-04TD1, Konnect-It D2-08TD2, Koyo D2-08TD2, and 5 more models

Page 91

Chapter 2: Installation, Wiring and Specifications

F2–08TR, Relay Output F2-08TR Relay Output Outputs per Module Outputs Points Consumed Commons per Module Output Type

8 8 2 (isolated), 4-pts. per common 8, Form A (SPST normally open) 7A @ 12–28 VDC, 12–250VAC; Operating Voltage 0.5 A @ 120VDC 150VDC, 265VAC Peak Voltage N/A ON Voltage Drop 47 to 63 Hz AC Frequency 10 mA @ 12 VDC Minimum Load Current 10A/point 3 (subject to derating) Max Load Current (resistive) Max of 10A/common N/A Max Leakage Current 12A Max Inrush Current Base Power Required 5VDC 670mA 15ms (typical) OFF to ON Response 5ms (typical) ON to OFF Response Removable; D2-8IOCON Terminal Type (included) Logic side Status Indicator 5.5 oz. (156g) Weight None Fuses

Typical Relay Life1 (Operations) at Room Temperature Voltage & Type of Load 2

Load Current 50mA 5A

7A

24 VDC Resistive 24 VDC Solenoid 110 VDC Resistive 110 VDC Solenoid 220 VAC Resistive 220 VAC Solenoid

10M – – – –

300k 75k 300k 200k 150k 100k

600k 150k 600k 500k 300k 250k

1) Contact life may be extended beyond those values shown with the use of arc suppression techniques described in the DL205 User Manual. Since these modules have no leakage current, they do not have built-in snubber. For example, if you place a diode across a 24VDC inductive load, you can significantly increase the life of the relay. 2) At 120VDC 0.5 A resistive load, contact life cycle is 200k cycles. 3) Normally closed contacts have 1/2 the current handling capability of the normally open contacts. Derating Chart

2.5 A/pt.

8 6

3 A/pt.

Number Points On 4 (100% duty 2 cycle)

5A/pt. 10 A/pt.

0 0 32 OUT

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F )

RELAY

0 1 2 3 F 2--08TR 12- 250VAC 10A50/60Hz 12- 28VDC 10ma-10A

4 5 6 7

Typical Circuit 12--28VDC 12--250VAC

Internal Circuitry

Common

L L

NO 0 NO 1

L

NO

C0-3 L L

NO 2 NO 3

L

NO 4

L

NO 5 C4-7

L L

NO 6 NO 7

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2-47

Page 92

Chapter 2: Installation, Wiring and Specifications

F2–08TRS, Relay Output

F2-08TRS Relay Output 1 Outputs per Module Points Consumed 2 Outputs Commons per Module Type 3 Output Operating Voltage Voltage 4 Peak ON Voltage Drop Frequency 5 ACMinimum Load Current Max Load Current (resistive) Leakage Current 6 Max Max Inrush Current Power Required 5VDC 7 Base OFF to ON Response ON to OFF Response 8 Terminal Type (included) Status Indicator 9 Weight Fuses 10 11 12 13 14 A B C D

8 8 8 (isolated) 3, Form C (SPDT) 5, Form A (SPST normally open) 7A @ 12–28 VDC, 12–250 VAC 0.5A @ 120VDC 150VDC, 265VAC N/A 47 to 63Hz 10mA @ 12VDC 7A/point 3 (subject to derating) N/A 12A 670mA 15ms (typical) 5ms (typical) Removable; D2-16IOCON Logic side 5.5 oz. (156g) None

12--28VDC 12--250VAC

NO 0

L

C1

C0

12--28VDC 12--250VAC

NO 1

L

12--28VDC 12--250VAC

NC 0

C2

C3 normally clos ed L

12--28VDC 12--250VAC

NO 2

L

NO 3

12--28VDC 12--250VAC

L

C4

C5

12--28VDC 12--250VAC

NO 4

L normally clos ed L

12--28VDC 12--250VAC

NO 5

NC 6

C6

L

NC 7 normally clos ed L C7

12--28VDC 12--250VAC

Typical Relay Life1 (Operations) at Room Temperature Voltage & Type of Load 2

Load Current 50mA 5A

7A

24VDC Resistive 24VDC Solenoid 110VDC Resistive 110VDC Solenoid 220VAC Resistive 220VAC Solenoid

10M – – – –

300k 75k 300k 200k 150k 100k

1) Contact life may be extended beyond those values shown with the use of arc suppression techniques described in the DL205 User Manual. Since these modules have no leakage current, they do not have built-in snubber. For example, if you place a diode across a 24VDC inductive load, you can significantly increase the life of the relay. 2) At 120VDC 0.5 A resistive load, contact life cycle is 200k cycles. 3) Normally, closed contacts have 1/2 the current handling capability of the normally open contacts. Derating Chart

8 6

5A/pt. 6A/ pt. 7A/pt.

0 0 32

OUT

4 5 6 7

12- 250VAC 7A50/60Hz 12- 28VDC 10ma- 7A C1 NO 1 C2 NO 2 C4 NO 4 NC 6 C6 NO 6

10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )

RELAY

0 1 2 3 F 2--08TR S

Typical Circuit (points 1,2,3,4,5) 12--28VDC 12--250VAC

Internal Circuitry

Common

L

NO

NO 0 C0 NC 0

Typical Circuit (P oints 0, 6, & 7 only)

C3 NO 3 C5 NO 5

12--28VDC 12--250VAC

NC 7

Common

C7 NO7

L

2-48

4A/ pt.

Number Points On 4 (100% duty 2 cycle)

NO 6

NO 7

600k 150k 600k 500k 300k 250k

L

DL205 User Manual, 4th Edition, Rev. D

L L

NO NC

Internal Circuitry

Page 93

Chapter 2: Installation, Wiring and Specifications

D2–12TR, Relay Output D2-12TR Relay Output 12 Outputs per Module 16 (four unused, see chart below) Outputs Points Consumed 2 (6-pts. per common) Commons per Module Relay, form A (SPST) Output Type 5–30 VDC; 5–240 VAC Operating Voltage 30VDC; 264VAC Peak Voltage N/A ON Voltage Drop 47 to 60 Hz AC Frequency 5mA @ 5VDC Minimum Load Current Max Load Current (resistive) 1.5 A/point; Max of 3A/common 0.1 mA @ 265VAC Max Leakage Current Output: 3A for 10ms Max Inrush Current Common: 10A for 10ms Base Power Required 5VDC 450mA 10ms OFF to ON Response 10ms ON to OFF Response Removable; D2-16IOCON Terminal Type (included) Logic side Status Indicator 4.6 oz. (130g) Weight (2) 4A slow blow, replaceable Fuses Order D2-FUSE-4 (5 per pack)

Typical Relay Life (Operations) Voltage/Load

Current

Closures

24VDC Resistive 24VDC Solenoid 110VDC Resistive 110VDC Solenoid 220VAC Resistive 220VAC Solenoid

1A 1A 1A 1A 1A 1A

500k 100k 500k 200k 350k 100k

Addresses Used Points

Used?

Yn+0 Yn+1 Yn+2 Yn+3 Yn+4 Yn+5 Yn+6 Yn+7

Yes Yes Yes Yes Yes Yes No No

Points

Yn+10 Yn+11 Yn+12 Yn+13 Yn+14 Yn+15 Yn+16 Yn+17 n is the starting address

12

A 0 1 2 B 3 D2--12TR

5--30 VDC 5--240 VAC L L L L L

L

5--30 VDC 5--240 VAC L L L L L

CA 0 4

5

NC 3 NC

0 1

4 5

4

0.5A / Pt. 0.75A / Pt.

2

1.25A / Pt. 1.5A / Pt.

0 0 32

10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )

CA Internal module circuitry

4 5 L

3

OUTP UT

NC CB 0 4 1 5

0 1 2

CB 5

3

2 NC

NC

To LE D

4

3 L

8

5- 240VAC 1.5A50/60Hz 5- 30VDC 5mA- 1.5A

1

2

RELAY

Yes Yes Yes Yes Yes Yes No No

Derating Chart

Points

OUT

Used?

COM 5--30 VDC 5--240 VAC

4A

D2--12TR

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2-49

Page 94

Chapter 2: Installation, Wiring and Specifications

D2–08CDR, 4 pt. DC Input / 4 pt. Relay Output D2-08CDR 4-pt. DC In / 4pt. Relay Out 1 General Specifications Base Power Required 5VDC 2 Terminal Type (included) Status Indicator 3 Weight Input Specifications per Module 4 Inputs Input Points Consumed Commons per Module 5 Input Voltage Range Peak Voltage Voltage Level 6 ON OFF Voltage Level AC Frequency 7 Input Impedance Input Current Current 8 Maximum Minimum ON Current Maximum OFF Current 9 OFF to ON Response ON to OFF Response 10 Fuses (input circuits) Typical Relay Life (Operations) 11 Voltage/Load Current Closures 12 13 14 A B C D 200mA Removable; D2-8IOCON Logic side 3.5 oz. (100 g)

4 (sink/source) 8 (only first 4-pts. are used) 1 20–28 VDC 30VDC 19VDC minimum 7VDC maximum N/A 4.7 kq 5mA @ 24VDC 8mA @ 30VDC 4.5 mA 1.5 mA 1 to 10 ms 1 to 10 ms None

24VDC Resistive 24VDC Solenoid 110VAC Resistive 110VAC Solenoid 220VAC Resistive 220VAC Solenoid

1A 1A 1A 1A 1A 1A

Output Specifications 4 Outputs per Module 8 (only first 4-pts. are used) Outputs Points Consumed 1 Commons per Module Relay, form A (SPST) Output Type 5–30 VDC; 5–240 VAC Operating Voltage 30VDC; 264VAC Peak Voltage N/A ON Voltage Drop 47 to 63 Hz AC Frequency 5mA @ 5VDC Minimum Load Current Max Load Current (resistive) 1A/point ; 4A/module 0.1 mA @ 264VAC Max Leakage Current OFF to ON Response ON to OFF Response Fuses (output circuits)

500k 100k 500k 200k 350k 100k

24VD C

+

O

L

2 1 IN/ OUT A 0 1 2 3 D2--08CDR

Internal module circuitry

To LE D

0 1

L

Sink

1 2

L

2

Source 24VDC

3

L

Optical Is olator

COM

+

Internal module circuitry

3 CB L

OUTP UT

5- 240VAC 1A50/60Hz 5- 30VDC 5mA- 1A

To LE D

3

COM

CB

5--30 VDC 5--240 VAC

DL205 User Manual, 4th Edition, Rev. D

V+

0

L

3

L

2-50

10 20 30 40 50 55°C 50 68 86 104 122131°F Ambient Temperature (°C/°F )

INP UT

1

2

0 32

CA

2

L

0

24VDC RELAY 0 B 1 2 3

D2- 08CDR 20- 28VDC 8mA

0

1

L

Outputs 1A / Pt. Inputs 5mA / Pt.

3

CA

--

Derating Chart

Points 4

Source Sink

3A for < 100ms 10A for < 10ms (common) 12ms 10ms 1 (6.3 A slow blow, replaceable); Order D2-FUSE-3 (5 per pack)

Max Inrush Current

5--30 VDC 5--240 VAC

6.3A

Page 95

Chapter 2: Installation, Wiring and Specifications

Glossary of Specification Terms Inputs or Outputs Per Module Indicates number of input or output points per module and designates current sinking, current sourcing, or either.

Commons Per Module Number of commons per module and their electrical characteristics.

Input Voltage Range The operating voltage range of the input circuit.

Output Voltage Range The operating voltage range of the output circuit.

Peak Voltage Maximum voltage allowed for the input circuit.

AC Frequency AC modules are designed to operate within a specific frequency range.

ON Voltage Level The voltage level at which the input point will turn ON.

OFF Voltage Level The voltage level at which the input point will turn OFF.

Input impedance Input impedance can be used to calculate input current for a particular operating voltage.

Input Current Typical operating current for an active (ON) input.

Minimum ON Current The minimum current for the input circuit to operate reliably in the ON state.

Maximum OFF Current The maximum current for the input circuit to operate reliably in the OFF state.

Minimum Load The minimum load current for the output circuit to operate properly.

External DC Required Some output modules require external power for the output circuitry.

ON Voltage Drop

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Sometimes called “saturation voltage,” it is the voltage measured from an output point to its common terminal when the output is ON at maximum load. DL205 User Manual, 4th Edition, Rev. D

2-51

Page 96

Chapter 2: Installation, Wiring and Specifications

Maximum Leakage Current The maximum current a connected maximum load will receive when the output point is OFF.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-52

Maximum Inrush Current The maximum current used by a load for a short duration upon an OFF to ON transition of an output point. It is greater than the normal ON state current and is characteristic of inductive loads in AC circuits.

Base Power Required Power from the base power supply is used by the DL205 input modules and varies between different modules. The guidelines for using module power are explained in the power budget configuration section in Chapter 4–7.

OFF to ON Response The time the module requires to process an OFF to ON state transition.

ON to OFF Response The time the module requires to process an ON to OFF state transition.

Terminal Type Indicates whether the terminal type is a removable or non-removable connector or a terminal.

Status Indicators The LEDs that indicate the ON/OFF status of an input point. These LEDs are electrically located on either the logic side or the field device side of the input circuit.

Weight Indicates the weight of the module. See Appendix F for a list of the weights for the various DL205 components.

Fuses Protective devices for an output circuit, which stop current flow when current exceeds the fuse rating. They may be replaceable or non–replaceable, or located externally or internally.

DL205 User Manual, 4th Edition, Rev. D

Page 97

CPU Specifications and Operations In This Chapter

Chapter

3

CPU Overview. ...........................................................................3–2 CPU General Specifications.........................................................3–4 CPU Base Electrical Specifications. ..............................................3–5 CPU Hardware Setup..................................................................3–6 Selecting the Program Storage Media.........................................3–9 Using Battery Backup..................................................................3–14 CPU Operation. ..........................................................................3–21 I/O Response Time. ....................................................................3–27 CPU Scan Time Considerations...................................................3–29 PLC Numbering Systems. ...........................................................3–35 Memory Map. ............................................................................3–37 DL230 System V-memory...........................................................3–41 DL240 System V-memory...........................................................3–43 DL250–1 System V-memory (DL250 also) . ................................3–46 DL260 System V-memory...........................................................3–49 DL205 Aliases. ............................................................................3–52 DL230 Memory Map..................................................................3–53 DL240 Memory Map..................................................................3–54 DL250–1 Memory Map (DL250 also)..........................................3–55 DL260 Memory Map..................................................................3–56 X Input/Y Output Bit Map. .........................................................3–57 Control Relay Bit Map.................................................................3–59 Stage Control/Status Bit Map. ....................................................3–63 Timer and Counter Status Bit Maps............................................3–65 Remote I/O Bit Map. ..................................................................3–66

Page 98

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

CPU Overview

3-2

The Central Processing Unit is the heart of the PLC. Almost all system operations are controlled by the CPU, so it is important that it is set up and installed correctly. This chapter provides the information needed to understand: • differences between the various models of CPUs, and • The steps required to set up and install the CPU.

General CPU Features The DL230, DL240, DL250–1 and D2–260 are modular CPUs which can be installed in 3, 4, 6, or 9 slot bases. All I/O modules in the DL205 family will work with any of the CPUs. The DL205 CPUs offer a wide range of processing power and program instructions. All offer RLL and Stage program instructions (See Chapter 5). They also provide extensive internal diagnostics that can be monitored from the application program or from an operator interface.

DL230 CPU Features The DL230 has 2.4K words of memory comprised of 2.0K of ladder memory and approximately 400 words of V-memory (data registers). It has 92 different instructions available for programming, and supports a maximum of 256 I/O points. Program storage is in the factory-installed EEPROM. In addition to the EEPROM there is also RAM on the CPU which will store system parameters, V-memory, and other data which is not in the application program. The DL230 provides one built-in RS-232 communication port, so you can easily connect a handheld programmer or a personal computer without needing any additional hardware.

DL240 CPU Features The DL240 has a maximum of 3.8K of memory comprised of 2.5K of ladder memory and approximately 1.3K of V-memory (data registers). There are 129 instructions available for program development and a maximum of 256 points local I/O, and 896 points with remote I/O are supported. Program storage is in the factory-installed EEPROM. In addition to the EEPROM, there is also RAM on the CPU that will store system parameters, V-memory and other data which is not in the application program. The DL240 has two communication ports. The top port is the same port configuration as the DL230. The bottom port also supports the DirectNET protocol, so you can use the DL240 in a DirectNET network. Since the port is RS-232, you must use an RS-232/RS-422 converter for multi-drop connections.

DL205 User Manual, 4th Edition, Rev. D

Page 99

Chapter 3: CPU Specifications and Operations

DL250–1 CPU Features

1 2 3 4 5 6 DL260 CPU Features 7 The DL260 offers all the DL250–1 features, plus ASCII IN/OUT and expanded Modbus instructions. It also supports up to 1280 local I/O points by using up to four local expansion 8 bases. It has a maximum of 30.4K of program memory comprised of 15.8K of ladder memory (saved on flash memory) and 14.6K of V-memory (data registers). It also includes an internal RISC–based microprocessor for greater processing power. The DL260 has 297 instructions. 9 In addition to those in the DL250–1 instruction set, the DL260 instruction set includes table instructions, trigonometric instructions and support for 16 PID loops. 10 The DL260 has a total of two built–in communications ports. The top port is identical to the top port of the DL250–1. The bottom port is a 15–pin RS-232/RS-422/RS-485 port. It will 11 interface with DirectSOFT (version 4.0 or later), operator interfaces, and provides DirectNet, Modbus RTU Master/Slave connections. Port 2 also supports ASCII IN/OUT instructions. 12 13 14 A B C D The DL250–1 replaces the DL250 CPU. It offers all the DL240 features, plus more program instructions and a built–in Remote I/O Master port. It offers all the features of the DL250 CPU with the addition of supporting Local expansion I/O. It has a maximum of 14.8K of program memory comprised of 7.6K of ladder memory and 7.2K of V-memory (data registers). It supports a maximum of 256 points of local I/O and a maximum of 768 I/O points (maximum of two local expansion bases). In addition, port 2 supports up to 2048 points if you use the DL250–1 as a Remote master. It includes an internal RISC–based microprocessor for greater processing power. The DL250–1 has 240 instructions. The instructions are in addition to the DL240 instruction set which includes drum timers, a print function, floating point math, PID loop control for 4 loops and the Intelligent Box (IBox) instructions. The DL250–1 has a total of two built–in communications ports. The top port is identical to the top port of the DL240, with the exception of the DirectNet slave feature. The bottom port is a 15–pin RS-232/RS-422 port. It will interface with DirectSOFT and operator interfaces, and provides DirectNet and Modbus RTU Master/Slave connections.

DL205 User Manual, 4th Edition, Rev. D

3-3

Page 100

Chapter 3: CPU Specifications and Operations

CPU General Specifications

1 Feature Total Program memory (words) 2 Ladder memory (words) V-memory (words) V Memory (words) 3 Non-volatile Boolean execution /K and RLL Programming 4 RLL Handheld programmer 5 DirectSOFT programming for Windows. 6 Built-in communication ports 7 EEPROM Total CPU memory I/O points available I/O points available 8 Local Local Expansion I/O points (including I/O and expansion I/O points) 9 local Serial Remote I/O points (including I/O and expansion I/O points) 10 local Serial Remote I/O Channels 11 Max Number of Serial Remote Slaves Ethernet Remote I/O Discrete points Remote I/O Analog I/O 12 Ethernet channels 13 Ethernet Remote I/O channels Max Number of Ethernet slaves per 14 channel A I/O points per Remote channel B I/O Module Point Density C Slots per Base D PLUS

3-4

DL230

DL240

DL250–1

DL260

2.4K 2048 256 128 4–6 ms Yes Yes

3.8K 2560 1024 256 10–12 ms Yes Yes

14.8K 7680 (Flash) 7168 No 1.9 ms Yes Yes

Yes

Yes

Yes

One RS–232

Two RS–232

Standard on CPU

Standard on CPU

One RS–232 One RS–232 or RS–422 Flash

256 (X,Y,CR)

896 (X, Y, CR)

2048 (X, Y, CR)

256

256

256

N/A

N/A

768 1280 (2 exp. bases max.) (4 exp. bases max.)

N/A

896

2048

8192

N/A

2

8

8

N/A

7 Remote / 31 Slice 7 Remote / 31 Slice 7 Remote / 31 Slice

N/A

896

N/A

Map into V–memory Map into V–memory Map into V–memory

N/A

Limited by power budget

Limited by power budget

Limited by power budget

N/A

16

16

16

N/A

16,384 (limited to 896 by CPU)

16,384 (16 fully 16,384 (16 fully expanded H4–EBC expanded H4–EBC slaves using V– slaves using V– memory and bit–of– memory and bit–of– word instructions) word instructions

4/8/12/16/32 3/4/6/9

4/8/12/16/32 3/4/6/9

4/8/12/16/32 3/4/6/9

DL205 User Manual, 4th Edition, Rev. D

2048

30.4K 15872 (Flash) 14592 No 1.9 ms Yes Yes Yes (requires version 4.0 or higher) One RS–232 One RS–232, RS–422 or RS–485 Flash 8192 (X, Y, CR, GX, GY) 256

8192

4/8/12/16/32 3/4/6/9