Page 81
Chapter 2: Installation, Wiring and Specifications
D2–08TD2, DC Output
D2–08TD1, DC Output D2-08TD1 DC Output
D2-08TD2 DC Output
8 (current sinking) Outputs per Module 1 (2 I/O terminal points) Commons per Module NPN open collector Output Type 10.2–26.4 VDC Operating Voltage 40VDC Peak Voltage 1.5 VDC maximum ON Voltage Drop N/A AC Frequency 0.5 mA Minimum Load Current 0.3 A/point; 2.4 A/common Max Load Current 0.1 mA @ 40VDC Max Leakage Current 1A for 10ms Max Inrush Current Base Power Required 5VDC 100mA 1ms OFF to ON Response 1ms ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.3 oz. (65g) Weight
1 per common 5A fast blow, non-replaceable
Fuses
8 (current sourcing) Outputs per Module 1 Commons per Module PNP open collector Output Type 12–24 VDC Operating Voltage 10.8–26.4 VDC Output Voltage 40VDC Peak Voltage 1.5 VDC ON Voltage Drop N/A AC Frequency N/A Minimum Load Current 0.3 A per point; 2.4 A per Max Load Current common 1.0 mA @ 40VDC Max Leakage Current 1A for 10 ms Max Inrush Current Base Power Required 5VDC 100 mA 1ms OFF to ON Response 1ms ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.1 oz. (60g) Weight 5A fast blow, non-replaceable Fuse
Derating Chart
Points 8 6 4
OUT
2 0 0 32
10 20 30 40 50 55 ˚ C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
12--24VDC +
Internally connected
C C
0 1 2 3 D2--08TD1
12--24 VDC 4 5 6 7
10.2- 26.4VDC 0.2mA-0.3A
0
L
C
4
L
C
1
L
5
L
2
L
6
L
3
L
L
0 L 1
5
7
L
4
2 6 3 Internal module circuitry
L
Optical Is olator
OUTP UT
7 D2--08TD1
+ 12--24VDC COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5A COM
DL205 User Manual, 4th Edition, Rev. D
2-37
Page 82
Chapter 2: Installation, Wiring and Specifications
D2–16TD1–2, DC Output
1 D2-16TD1-2 DC Output Outputs per Module 2 Commons per Module Output Type DC required 3 External Operating Voltage Voltage 4 Peak ON Voltage Drop AC Frequency 5 Minimum Load Current Max Load Current Leakage Current 6 Max Max Inrush Current Power Required 5VDC 7 Base OFF to ON Response ON to OFF Response 8 Terminal Type (included) Status Indicator 9 Weight Fuses 10 11 12 13 14 A B C D
D2-16TD2-2 DC Output
16 (current sinking) 1 (2 I/O terminal points) NPN open collector 24VDC ±4V @ 80 mA max 10.2-26.4 VDC 30VDC 0.5 VDC maximum N/A 0.2 mA 0.1A/point 1.6A/common 0.1 mA @ 30 VDC 150mA for 10 ms 200mA 0.5 ms 0.5 ms Removable; D2-16IOCON Logic side
2.3 oz. (65g) None
Derating Chart
Points 16 12 8 4
OUT
0
0 32
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F ) C
0
L
4
L
1
L
12--24 VDC 4 5 6 7
5
L
6
10.2- 26.4 VDC 0.1A CLASS2
7
0
C
1
2
L L
A
3
L L
12--24VDC +
A 0 1 2 B 3 D2--16TD1--2
24VDC
+
+V 0
L
4
L
Internally connected
1
L
5
L
2
L
6
L
3
L
7
L
2 3
+V 0 1 2 3
+V Internal module circuitry
B
C 4 5 6 7
C 4 5 6 7
+
24VDC L
+
OUTP UT
Optical Is olator
12--24 VDC
COM COM
* Can also be used with 5VDC supply
2-38
D2–16TD2–2, DC Output
DL205 User Manual, 4th Edition, Rev. D
Outputs per Module Commons per Module Output Type Operating Voltage Peak Voltage ON Voltage Drop AC Frequency Minimum Load Current
16 (current sourcing) 2 NPN open collector 10.2-26.4 VDC 30VDC 1.0 VDC maximum N/A 0.2 mA 0.1A/point Max Load Current 1.6A/module 0.1 mA @ 30 VDC Max Leakage Current 150mA for 10 ms Max Inrush Current Base Power Required 5VDC 200mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator 2.8 oz. (80g) Weight None Fuses
Page 83
Chapter 2: Installation, Wiring and Specifications
F2–16TD1(2)P, DC Output With Fault Protection NOTE: Not supported in D2-230, D2-240 and D2-250 CPUs.
These modules detect the following fault status and turn the related X bit(s) on. 1. Missing external 24VDC for the module 2. Open load1 3. Over temperature (the output is shut down) 4. Over load current (the output is shut down) Fault Status Missing external 24VDC Open load1 Over temperature Over load current
X bit Fault Status Indication All 16 X bits are on. Only the X bit assigned to the faulted output is on
When these modules are installed, 16 X bits are automatically assigned as the fault status indicator. Each X bit indicates the fault status of each output. In this example, X10-X27 are assigned as the fault status indicator. X10: Fault status indicator for Y0 X11: Fault status indicator for Y1
Example D2-250-1 or D2-260
X26: Fault status indicator for Y16 X27: Fault status indicator for Y17
Slot 0 Slot 1 Slot 2 Slot 3 Slot 4
The fault status indicators (X bits) can be reset by performing the indicated operations in the following table: Fault Status Missing external 24VDC Open load1 Over temperature Over load current
D2-08ND3
F2-16TD1P or F2-16TD2P
X0 - X7
X10 - X27 Y0 - Y17
Operation Apply external 24VDC Connect the load.
Jumper Switch J6
Turn the output (Y bit) off or power cycle the PLC
PC Board
NOTE 1: Open load detection can be disabled by removing the jumper switch J6 on the module PC board.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Continued on next two pages. DL205 User Manual, 4th Edition, Rev. D
2-39
Page 84
Chapter 2: Installation, Wiring and Specifications
F2–16TD1P, DC Output With Fault Protection
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
NOTE: Not supported in D2-230, D2-240 and D2-250 CPUs.
NOTE: Supporting Firmware: D2-250-1 must be V4.80 or later D2-260 must be V2.60 or later
Points 16
Derating Chart
12 8 4
OUT
0 10 20 30 40 50 55°C 50 68 86 104 122 131°F Ambient Temperature (°C/°F)
0 32
0V 0
L
4
L
1
L
5
L
6
L
A
3
L
0 1
7
L 24VDC
12–24VDC +
+
24V 0V 0
L
4
L
1
L
5
L
2
L
6
L
3
L
7
L
Internally connected
2 3 24V 0 1 2 3
24V Internal module circuitry
12-24 VDC 4 5 6 7
10.2-26.4 VDC 0.25A CLASS2
2
L
A 0 1 2 B 3 F2–16TD1P
B
0V 4 5 6 7 0V 4 5 6 7
+ 24VDC OUTPUT L
+ 12–24 VDC
0V 0V
2-40
Optical Isolator
When the A/B switch is in the A position, the LEDs display the output status of the module’s first 8 output points. Positon B displays the output status of the module’s second group of 8 output points.
DL205 User Manual, 4th Edition, Rev. D
F2-16TD1P DC Output with Fault Protection Inputs per module Outputs per module Commons per module Output type Operating voltage Peak voltage AC frequency ON voltage drop Overcurrent trip
16 (status indication) 16 (current sinking) 1 (2 I/O terminal points) NMOS FET (open drain) 10.2–26.4 VDC, external 40VDC N/A 0.7 V (output current 0.5 A) 0.6A, min., 1.2A, max.
Minimum load current
0.2mA
Maximum load current
0.25A/point; 4A/common
Max leakage current
0.2mA (load detect enabled); 0.3mA disabled
Max inrush current
150 mA for 10ms
Base power required 5V OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses External DC required
70 mA 0.5 ms 0.5 ms Removable (D2-16IOCON) Logic Side 2.0 oz. (25g) None
External DC overvoltage shutdown
27V, outputs are restored when voltage is within limits
24VDC ±10% @ 50mA
Page 85
Chapter 2: Installation, Wiring and Specifications
F2–16TD2P, DC Output with Fault Protection NOTE: Not supported in D2-230, D2-240 and D2-250 CPUs.
NOTE: Supporting Firmware: D2-250-1 must be V4.80 or later D2-260 must be V2.60 or later
Derating Chart 2
4
OUT 10 50
0 32
20 68
30 86
40 50 55°C 104 122 131°F C
12–24VDC
0V
+
4
A 0 1 2 B 3 F2–16TD2P
A 24V
+
V
0 1 2
L
4
L L
3 24V
L
2
L
0 1
L L
2
L
3 24VDC
– +
B
24V
16 (status indication) 16 (current sourcing) 1 NMOS FET (open source) 10.2–26.4 VDC, external 40VDC N/A 0.7 V (output current 0.5 A) 0.6 A min., 1.2 A max.
Minimum load current
0.2 mA
Maximum load current
0.25 A/point; 4A/common
Max leakage current
0.2 mA (load detect enabled); 0.3 mA disabled
Max inrush current
150mA for 10ms
Base power required 5V OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses External DC required
70mA 0.5 ms 0.5 ms Removable (D2-16IOCON) Logic Side 2.0 oz. (25g) None
External DC overvoltage shutdown
27V, outputs are restored when voltage is within limits
24VDC ±10% @ 50mA
10.2-26.4 VDC 0.25A CLASS2
2
24VDC
12-24 VDC 4 5 6 7
F2-16TD2P DC Output with Fault Protection Inputs per module Outputs per module Commons per module Output type Operating voltage Peak voltage AC frequency ON voltage drop Overcurrent trip
V1 4 5 6 7 0V 4 5 6 7
Reg
0V 12–24VDC +
L
O
0V
OUTPUT
When the A/B switch is in the A position, the LEDs display the output status of the module’s first 8 output points. Positon B displays the output status of the module’s second group of 8 output points.
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2-41
Page 86
Chapter 2: Installation, Wiring and Specifications
D2–32TD1, DC Output
D2–32TD2, DC Output
D2-32TD1 DC Output 1 Outputs per Module per Module 2 Commons Output Type Operating Voltage Voltage 3 Peak ON Voltage Drop Load Current 4 Minimum Max Load Current Max Leakage Current Inrush Current 5 Max Base Power Required 5VDC to ON Response 6 OFF ON to OFF Response Terminal Type (not included) 7 Status Indicator Weight 8 Fuses External DC Power Required 9 10 11 12 13 14 A B C D
32 (current sinking) 4 (8 I/O terminal points) NPN open collector 12–24 VDC 30VDC 0.5 VDC maximum 0.2 mA 0.1 A/point; 3.2 A per module 0.1 mA @ 30VDC 150mA for 10ms 350mA 0.5 ms 0.5 ms Removable 40-pin connector1 Module activity (no I/O status indicators) 2.1 oz. (60g) None 20–28 VDC max. 120mA (all points on)
1
Connector sold separately. See Terminal Blocks and Wiring for wiring options.
2-42
DL205 User Manual, 4th Edition, Rev. D
D2-32TD2 DC Output 32 (current sourcing) Outputs per Module 4 (8 I/O terminal points) Commons per Module Transistor Output Type 12 to 24 VDC Operating Voltage 30VDC Peak Voltage 0.5 VDC @ 0.1 A ON Voltage Drop 0.2 mA Minimum Load Current 0.1 A/point; 0.8 A/common Max Load Current 0.1 mA @ 30VDC Max Leakage Current 150mA @ 10ms Max Inrush Current Base Power Required 5VDC 350mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (not included) Removable 40-pin connector1
Status Indicator Weight Fuses 1
Module activity (no I/O status indicators) 2.1 oz (60g) None
Connector sold separately. See Terminal Blocks and Wiring for wiring options.
Page 87
Chapter 2: Installation, Wiring and Specifications
F2–08TA, AC Output F2-08TA AC Output Outputs per Module Commons per Module Output Type Operating Voltage Peak Voltage ON Voltage Drop AC Frequency Minimum Load Current Max Load Current
8 2 (Isolated) SSR (Triac with zero crossover) 24–140 VAC 140VAC 1.6 V(rms) @ 1.5 A 47 to 63 Hz 50 mA 1.5 A / pt @ 30ºC 1.0 A / pt @ 60ºC 4.0 A / common; 8.0 A / module @ 60ºC 0.7 mA (rms)
Max Leakage Current Peak One Cycle Surge 15A Current Base Power Required 5VDC 250mA 0.5 ms - 1/2 cycle OFF to ON Response 0.5 ms - 1/2 cycle ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 3.5 oz. Weight None Fuses
D2–08TA, AC Output D2-08TA AC Output Outputs per Module Commons per Module Output Type Operating Voltage Peak Voltage
8 1 (2 I/O terminal points) SSR (Triac) 15–264 VAC 264VAC < 1.5 VAC (>0.1 A) ON Voltage Drop < 3.0 VAC (<0.1 A) 47 to 63Hz AC Frequency 10mA Minimum Load Current 0.5 A/point; 4A/common Max Load Current 4mA (264VAC, 60Hz) 1.2 mA (100VAC, 60Hz) Max Leakage Current 0.9 mA (100VAC, 50Hz) 10A for 10ms Max Inrush Current Base Power Required 5VDC 250mA 1 ms OFF to ON Response 1 ms + 1/2 cycle ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.8 oz. (80g) Weight 1 per common, 6.3 A slow blow, Fuses non-replaceable
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2-43
Page 88
Chapter 2: Installation, Wiring and Specifications
D2–12TA, AC Output
1 D2-12TA AC Output Outputs per Module Points Consumed 2 Outputs Commons per Module Type 3 Output Operating Voltage Peak Voltage 4 ON Voltage Drop AC Frequency 5 Minimum Load Current Max Load Current 6 7 8 9 10 11 12 13 14 A B C D
12 16 (four unused, see chart below) 2 (isolated) SSR (Triac) 15–132 VAC 132VAC < 1.5 VAC (>50mA) < 4.0 VAC (<50mA) 47 to 63 Hz 10mA 0.3 A/point; 1.8 A/common
Points
Derating Chart
2mA (132VAC, 60Hz) Max Leakage Current 10A for 10ms Max Inrush Current Base Power Required 5VDC 350mA 1ms OFF to ON Response 1ms + 1/2 cycle ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator 2.8 oz. (80g) Weight (2) 1 per common 3.15 A slow blow, replaceable Order D2-FUSE-1 (5 per pack)
Fuses
P oints
Addres s es Us ed P oints Us ed?
Yn+0 Yn+1 Yn+2 Yn+3 Yn+4 Yn+5 Yn+6 Yn+7
Yes Yes Yes Yes Yes Yes No No
250mA / Pt.
12
300mA / Pt.
9 6 3 0
0 32
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F ) 15--132 VAC L L L L L L
15--132 VAC L L L L L L
2-44
CA
OUT A 0 1 2 B 3 D2--12TA 15- 132VAC 10mA- 0.3A 50/60 Hz
0
4
1
0
5
1
NC
2
2 3
NC
NC
CB
0
4
1
5
2
18--110 VAC 4 5
2
4 5 Internal module circuitry
CB
Optical Is olator
L
4 5
3
COM
NC
3
NC
Yes Yes Yes Yes Yes Yes No No
CA
OUTP UT
1
Us ed?
n is the starting address
3 0
Yn+10 Yn+11 Yn+12 Yn+13 Yn+14 Yn+15 Yn+16 Yn+17
D2--12TA
DL205 User Manual, 4th Edition, Rev. D
15--132 VAC
3.15A
To LE D
Page 89
Chapter 2: Installation, Wiring and Specifications
D2–04TRS, Relay Output Max Leakage Current Max Inrush Current Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicator Weight
D2-04TRS Relay Output 4 Outputs per Module 8 (only 1st 4pts. are used) Outputs Points Consumed 4 (isolated) Commons per Module Relay, form A (SPST) Output Type 5-30 VDC / 5-240 VAC Operating Voltage 30 VDC, 264 VAC Peak Voltage 0.72 VDC maximum ON Voltage Drop 47 to 63 Hz AC Frequency 10mA Minimum Load Current Max Load Current (resistive) 4A/point; 8A/module (resistive)
Fuses
0.1 mA @ 264VAC 5A for < 10ms 250mA 10ms 10ms Removable; D2-8IOCON Logic side 2.8 oz. (80g) 1 per point 6.3 A slow blow, replaceable Order D2-FUSE-3 (5 per pack)
Typical Relay Life (Operations) Voltage & Load Current Type of Load 1A
2A
3A
4A
24VDC Resistive 24VDC Solenoid 110 VAC Resistive 110 VAC Solenoid 220 VAC Resistive 220 VAC Solenoid
200k 40k 250k 100k 150k 50k
100k –– 150k 50k 100k ––
50k – 100k – 50k ––
500k 100k 500k 200k 350k 100k
Derating Chart
Points 4
2A / Pt.
3
3A / Pt. 4A / Pt.
At 24 VDC, solenoid (inductive) loads over 2A cannot be used.
2
At 100 VAC, solenoid (inductive) loads over 3A cannot be used.
1
At 220 VAC, solenoid (inductive) loads over 2A cannot be used.
0
OUT
RELAY
10 50
0 32
20 30 40 68 86 104 Ambient Temperature (˚C/˚F )
50 55 ˚ C 122 131 ˚ F
0 1 2 3 D2--04TR S 5-240VAC 4A50/60Hz 5- 30VDC 10mA- 4A
NC 5--30 VDC 5--240 VAC
NC
0 L
C1 1
L
C2 2
L
C3 3 L
Internal module circuitry
NC NC C0
C0
L C1 L C2 L C3 L
0
L
OUTP UT
1 To LE D 2 3
COM 5--30 VDC 5--240 VAC
6.3A
D2--04TR S
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2-45
Page 90
Chapter 2: Installation, Wiring and Specifications
D2–08TR, Relay Output
1 D2-08TR Relay Output Outputs per Module 2 Outputs Points Consumed per Module 3 Commons Output Type Operating Voltage Voltage 4 Peak ON Voltage Drop Frequency 5 ACMinimum Load Current Max Load Current (resistive) 6 Typical Relay Life (Operations) 7 Voltage/Load Current Closures 8 9 10 11 12 13 14 A B C D
Max Leakage Current
8 8 1 (2 I/O terminals) Relay, form A (SPST) 5–30 VDC; 5–240 VAC 30VDC, 264VAC N/A 47 to 60 Hz 5mA @ 5VDC 1A/point; 4A/common
24VDC Resistive 24VDC Solenoid 110VDC Resistive 110VDC Solenoid 220VAC Resistive 220VAC Solenoid
1A 1A 1A 1A 1A 1A
0 1 2 3 D2--08TR
Internally connected
C
L L L L L
4
1
5
2
L L
2-46
Derating Chart
Points 8 RELAY
6
4 5 6 7
4
C
0.5A / Pt.
1A / Pt.
2 0 0 32
3
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
C
L
0
L 1
4
Internal module circuitry
5
2
6
6
L
Fuses
5-240VAC 1A50/60Hz 5- 30VDC 5mA- 1A
C
0
Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicator Weight
500k 100k 500k 200k 350k 100k
OUT
5--30 VDC 5--240 VAC
Max Inrush Current
0.1 mA @265 VAC Output: 3A for 10ms Common: 10A for 10ms 250mA 12ms 10ms Removable; D2-8IOCON Logic side 3.9 oz. (110g) One 6.3A slow blow, replaceable Order D2-FUSE-3 (5 per pack)
3
L
OUTP UT
7
7
To LE D
D2--08TR
DL205 User Manual, 4th Edition, Rev. D
COM 5--30 VDC 5--240 VAC
6.3A