Page 71
Chapter 2: Installation, Wiring and Specifications
Special Placement Considerations for Analog Modules
1 2 3 Discrete Input Module Status Indicators 4 The discrete modules provide LED status indicators to show the status of the input points. 5 6 7 8 9 10 11 12 Color Coding of I/O Modules The DL205 family of I/O modules have a color coding scheme to help you quickly identify if a module is either an input module, output module, or a specialty module. This is done through 13 a color bar indicator located on the front of each module. The color scheme is listed below: 14 A B C D In most cases, the analog modules can be placed in any slot. However, the placement can also depend on the type of CPU you are using and the other types of modules installed to the left of the analog modules. If you’re using a DL230 CPU (or a DL240 CPU with firmware earlier than V1.4) you should check the DL205 Analog I/O Manual for any possible placement restrictions related to your particular module. You can order the DL205 Analog I/O Manual by ordering part number D2–ANLG–M.
Status indicators
Terminal
Terminal Cover (installed)
Wire tray area behind terminal cover
Color Bar
Module Type Discrete/Analog Output Discrete/Analog Input Other
Color Code Red Blue White
DL205 User Manual, 4th Edition, Rev. D
2-27
Page 72
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-28
Wiring the Different Module Connectors There are two types of module connectors for the DL205 I/O. Some modules have normal screw terminal connectors. Other modules have connectors with recessed screws. The recessed screws help minimize the risk of someone accidentally touching active wiring. Both types of connectors can be easily removed. If you examine the connectors closely, you’ll notice there are squeeze tabs on the top and bottom. To remove the terminal block, press the squeeze tabs and pull the terminal block away from the module. We also have DIN rail mounted terminal blocks, DINnectors (refer to our catalog for a complete listing of all available products). ZIPLinks come with special pre–assembled cables with the I/O connectors installed and wired. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, check all field device power before you remove the connector.
DL205 User Manual, 4th Edition, Rev. D
Page 73
Chapter 2: Installation, Wiring and Specifications
I/O Wiring Checklist Use the following guidelines when wiring the I/O modules in your system.
1 2 Terminal type Suggested AWG Range Suggested Torque 3 4 *NOTE: 16 AWG Type TFFN or Type MTW is recommended. Other types of 16 AWG may be acceptable, 5 but it really depends on the thickness and stiffness of the wire insulation. If the insulation is too thick or stiff and a majority of the module’s I/O points are used, then the plastic terminal cover may not close 6 properly or the connector may pull away from the module. This applies especially for high temperature thermoplastics such as THHN. 7 2. Always use a continuous length of wire, do not combine wires to attain a needed length. 3. Use the shortest possible wire length. 8 4. Use wire trays for routing where possible. 5. running wires near high energy wiring. Also, avoid running input wiring close to output wiring where possible. 9 6. minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. 10 7. Avoid running DC wiring in close proximity to AC wiring where possible. 8. Avoid creating sharp bends in the wires. 11 9. reduce the risk of having a module with a blown fuse, we suggest you add external fuses to your I/O wiring. A fast blow fuse, with a lower current rating than the I/O module fuse can 12 be added to each common, or a fuse with a rating of slightly less than the maximum current per output point can be added to each output. Refer to our catalog for a complete line of DINnectors, DIN-rail mounted fuse blocks. 13 14 A B C D 1. is a limit to the size of wire the modules can accept. The table below lists the suggested AWG for each module type. When making terminal connections, follow the suggested torque values.
10-Terminal Fixed 10-Terminal Removable 20-Terminal Removable
14 – 24 AWG 16* – 24 AWG 16* – 24 AWG
3.5 lb-inch (0.4 N·m) 7.81 lb-inch (0.88 N·m) 2.65 lb-in (0.3 N·m)
DL205 User Manual, 4th Edition, Rev. D
Safety Guidelines
DINnector External Fuses (DIN rail mounted Fuses)
2-29
Page 74
Chapter 2: Installation, Wiring and Specifications
D2-08ND3, DC Input D2-08ND3 DC Input
D2-16ND3-2 DC Input
Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance
Inputs per Module
8 (sink/source) 1 (2 I/O terminal points) 10.2–26.4 VDC 26.4 VDC 9.5 VDC minimum 3.5 VDC maximum N/A 2.7 kq 4.0 mA @ 12VDC Input Current 8.5 mA @ 24VDC 3.5 mA Minimum ON Current 1.5 mA Maximum OFF Current Base Power Required 5VDC 50mA 1 to 8 ms OFF to ON Response 1 to 8 ms ON to OFF Response Terminal Type (included) Removable, D2-8IOCON Logic side Status Indicator 2.3 oz. (65g) Weight
16 (sink/source) 2 isolated Commons per Module (8 I/O terminal points/com) 20–28 VDC Input Voltage Range 30VDC (10mA) Peak Voltage 19 VDC minimum ON Voltage Level 7VDC maximum OFF Voltage Level N/A AC Frequency 3.9 kq Input Impedance 6mA @ 24VDC Input Current 3.5 mA Minimum ON Current 1.5 mA Maximum OFF Current Base Power Required 5VDC 100mA 3 to 9 ms OFF to ON Response 3 to 9 ms ON to OFF Response Terminal Type (included) Removable, D2-16IOCON Logic side Status Indicator 2.3 oz. (65g) Weight
Derating Chart
Points
Derating Chart
Points
8
16
6
12 8
4
IN
2 0 10 20 30 40 50 55 °C 50 68 86 104 122131 °F Ambient Temperature (°C/°F )
0 32
12--24VDC - + Source Sink
-
+
Internally connected
C C
0 1 2 3 D2--08ND3
12--24 VDC 4 5 6 7
IN
4 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122131 ° F Ambient Temperature (°C/°F )
24 VDC
Source Sink
-
+
+
-
CA
4
20- 28VDC 8mA CLASS2
1 5
0
C
4
2 3
0
6
+
+
-
0
5
1
2 6
3
2
3 7
7 Internal module circuitry
D2--08ND3
INP UT
NC
1
6
V+
3
4
2
Internal module circuitry
CB 0
5
7
2
NC
1
3
1
7
Source 24 VDC Sink
4
2
0
6
C
1 5
3
V+
INP UT
To LE D
Sink Source
+
Source
DL205 User Manual, 4th Edition, Rev. D
+
-
-
COM - + 12--24VDC
Sink
2-30
To LE D
Optical Is olator
+
COM
A 0 1 2 B 3 D2--16ND3--2
0
10.2- 26.4VDC 4- 12mA
-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
D2-16ND3-2, DC Input
24 VDC
COM
Optical Is olator
CA 4 5 6 7 CB 4 5 6 7
24 VDC 4 5 6 7
Page 75
Chapter 2: Installation, Wiring and Specifications
D2–32ND3, DC Input D2-32ND3 DC Input Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance Input Current Minimum ON Current Maximum OFF Current Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (not included) Status Indicator Weight 1
32 (sink/source) 4 isolated (8 I/O terminal points / com) 20-28 VDC 30VDC 19VDC minimum 7VDC maximum N/A 4.8 kq 8.0 mA @ 24 VDC 3.5 mA 1.5 mA 25mA 3 to 9 ms 3 to 9 ms Removable 40-pin Connector1 Module Activity LED 2.1 oz. (60 g)
Connector sold separately. See Terminal Blocks and Wiring for wiring options.
IN Points
Derating Chart
32
ACT
16
+
24VDC
Source -
Sink +
+
24VDC
-
10 20 30 40 50 55 °C 50 68 86 104 122131 °F Ambient Temperature (°C/°F )
0 32
-
0
Sink +
Source -
+
24VDC
V+
-
Internal module circuitry
Sink +
Source -
INP UT To Logic
24 VDC
COM
+
+ +
Source
24VDC
-
Sink
Optical Is olator
Source
Sink +
-
A0 A4 A1 A5 A2 A6 A3 A7 COM I B0 B4 B1 B5 B2 B6 B3 B7 COM II C0 C4 C1 C5 C2 C6 C3 C7 COM III D0 D4 D1 D5 D2 D6 D3 D7 COM IV
24 VDC
D2--32ND3 A0 A4 A1 A5 A2 A6 A3 A7 CI CI B0 B4 B1 B5 B2 B6 B3 B7 CII CII C0 C4 C1 C5 C2 C6 C3 C7 CIII CIII D0 D4 D1 D5 D2 D6 D3 D7 CIV CIV
22--26VDC 4--6mA CLAS S 2
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-31
Page 76
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
D2–32ND3–2, DC Input
2-32
D2-32ND3-2 DC Input Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance Input Current Maximum Input Current Minimum ON Current Maximum OFF Current Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (not included) Status Indicator Weight 1
32 (Sink/Source) 4 isolated (8 I/O terminal points / com) 4.50 to 15.6 VDC min. to max. 16VDC 4VDC minimum 2VDC maximum N/A 1.0 kq @ 5–5 VDC 4mA @ 5VDC 11mA @ 12VDC 14mA @ 15VDC 16mA @ 15.6 VDC 3mA 0.5 mA 25mA 3 to 9 ms 3 to 9 ms Removable 40-pin connector1 Module activity LED 2.1 oz. (60g)
Connector sold separately. See Terminal Blocks and Wiring for wiring options.
Sink
5-15VDC Source
Sink
5-15VDC Source
Sink
5-15VDC Source
Sink
5-15VDC Source
DL205 User Manual, 4th Edition, Rev. D
Page 77
Chapter 2: Installation, Wiring and Specifications
D2-08NA-1, AC Input D2-08NA-1 AC Input Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance
8 1 (2 I/O terminal points) 80–132 VAC 132VAC 75VAC minimum 20VAC maximum 47–63 Hz 12kq @ 60Hz 13mA @ 100VAC, 60Hz 11mA @ 100 VAC, 50Hz 5mA 2mA 50mA 5 to 30 ms 10 to 50 ms Removable; D2-8IOCON Logic side 2.5 oz. (70g)
Input Current Minimum ON Current Maximum OFF Current Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicator Weight Derating Chart
Points 8 6 4
IN
2 0 10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
0 32
110 VAC
Internally connected
C
0 1 2 3 D2--08NA--1
C
80-132VAC 10-20mA 50/60Hz
4
C
5
0
6
1
0
110 VAC 4 5 6 7
C
1 2
4
3
5
7
2 6
Internal module circuitry
3 V+
7 D2--08NA-1
INP UT To LE D
COM Line
Optical Is olator
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
110 VAC COM
DL205 User Manual, 4th Edition, Rev. D
2-33
Page 78
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
D2-08NA-2, AC Input Operating Temperature Storage Temperature Humidity Atmosphere Vibration Shock Insulation Withstand Voltage Insulation Resistance
D2-08NA-2 AC Input Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance
8
1 (2 I/O terminal points) 170–265 VAC 265VAC 150VAC minimum 40VAC maximum 47–63 Hz 18kq @ 60Hz 9mA @ 220VAC, 50Hz 11mA @ 265VAC, 50Hz Input Current 10mA @ 220VAC, 60Hz 12mA @ 265VAC, 60Hz 10mA Minimum ON Current 2mA Maximum OFF Current Base Power Required 5VDC 100mA 5 to 30 ms OFF to ON Response 10 to 50 ms ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.5 oz. (70g) Weight
Noise Immunity RFI
32ºF to 131ºF (0º to 55ºC) -4ºF to 158ºF (-20ºC to 70ºC) 35% to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 1,500VAC 1 minute (COM-GND) 10M Q @ 500VDC NEMA 1,500V 1 minute SANKI 1,000V 1 minute 150MHz, 430MHz
Derating Chart
Points 8 6 4
220VAC
2 0 10 20 30 40 50 55 ˚ C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
0 32
Internally connected
C C 0 4 1 5
Internal module circuitry
V+
2 6
INP UT
3 To LE D
COM
Optical Is olator
220VAC
2-34
COM
DL205 User Manual, 4th Edition, Rev. D
7
Page 79
Chapter 2: Installation, Wiring and Specifications
D2-16NA, AC Input
F2-08SIM, Input Simulator
D2-16NA AC Input
F2-08SIM Input Simulator
Inputs per Module Commons per Module Input Voltage Range Peak Voltage ON Voltage Level OFF Voltage Level AC Frequency Input Impedance
16 2 (isolated) 80–132 VAC 132VAC 70VAC minimum 20VAC maximum 47–63 Hz 12kq @ 60Hz 11mA @ 100VAC, 50Hz 13mA @ 100VAC, 60Hz Input Current 15mA @ 132VAC, 60Hz 5mA Minimum ON Current 2mA Maximum OFF Current Base Power Required 5VDC 100mA 5 to 30 ms OFF to ON Response 10 to 50 ms ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator 2.4 oz. (68g) Weight
8 Inputs per Module Base Power Required 5VDC 50mA None Terminal Type Switch side Status Indicator 2.65 oz. (75g) Weight
Derating Chart
Points 16 12 8
IN
4 0 0 32
10 20 30 40 50 55 ˚ C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F ) 110 VAC
CA
A 0 1 2 B 3 D2--16NA
110 VAC 4 5 6 7
IN
SIM
0 1 2 3 F 2--08SI M
4 5 6 7
0 4
80- 132VAC 10- 20mA 50/60Hz
1
0
> ON
5 2 6
0
7
1
3
110 VAC
NC
2
CB
3
0 4
NC
1 5
0
2 6
1
7
2
3
3
CA 4 5
1 2
6 7 CB 4 5 6
3 4 5
7
6
D2--16NA
7
Internal module circuitry V+ INP UT To LE D
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Optical Is olator
110 VAC
DL205 User Manual, 4th Edition, Rev. D
2-35
Page 80
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
D2-04TD1, DC Output D2-04TD1 DC Output Outputs per Module Output Points Consumed Commons per Module Output Type Operating Voltage Peak Voltage ON Voltage Drop AC Frequency Max Load Current (resistive) Max Leakage Current Max Inrush Current Minimum Load Current
Points
4 (current sinking) 8 points (only first 4 pts. used) 1 (4 I/O terminal points) NMOS FET (open drain) 10.2-26.4 VDC 40VDC 0.72 VDC maximum N/A 4A/point 8A/common 0.1 mA @ 40 VDC 6A for 100 ms, 15A for 10 ms 50 mA
24VDC @ 20 mA max. External DC Required Base Power Required 5VDC 60mA 1ms OFF to ON Response 1ms ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.8 oz. (80 g) Weight
Derating Chart
Inductive Load Maximum Number of Switching Cycles per Minute
2A / Pt.
4
4 (1 per point) (6.3 A slow blow, non-replaceable)
Fuses
Load Current
3
3A / Pt.
2 1
OUT
4A / Pt.
0 1 2 3 D2--04TD1
0 0 32
2-36
10 20 30 40 50 55 ˚ C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
10.2- 26.4VDC 50mA- 4A
24VDC +
Internally connected
0V 24V
C +24V
C
12--24VDC + L
L
L
L
0.1A 0.5A 1.0A 1.5A 2.0A 3.0A 4.0A
12--24 VDC
C 0
C
0
L C
1
L
C
C
2
L
C
C
3
L
Duration of output in ON s tate 100ms 7ms 40ms 8000 1600 800 540 400 270 200
1400 300 140 90 70 ---
600 120 60 35 ----
At 40 mS duration, loads of 3.0A or greater cannot be used. At 100 mS duration, loads of 2.0A or greater cannot be used. Find the load current you expect to use and the duration that the output is ON. The number at the intersection of the row and column represents the switching cycles per minute. For example, a 1A inductive load that is on for 100 ms can be switched on and off a maximum of 60 times per minute. To convert this to duty cycle percentage use: (duration x cycles)/60. In this example, (60 x .1)/60 = .1, or 10% duty cycle.
1 24VDC
-- +
2
Reg
0V
3
To LE D Output
D2--04TD1
L 12--24 + VDC --
6.3A
Optical Is olator Common Other Circuits
DL205 User Manual, 4th Edition, Rev. D