The text of a manual · part 7 of 60
DL205 PLC User Manual, Volume 1 of 2, pages 61 to 70
Pages 61 to 70 of 598
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D2-04TD1, AutomationDirect D2-08TD2, AutomationDirect D2-16ND3-2, AutomationDirect D2-32ND3, Konnect-It D2-04TD1, Koyo D2-04TD1, Konnect-It D2-08TD2, Koyo D2-08TD2, and 5 more models
Page 61
Chapter 2: Installation, Wiring and Specifications
Sinking / Sourcing Concepts
1 2 Sinking = provides a path to supply ground (–) 3 Sourcing = provides a path to supply source (+) 4 First you will notice these are only associated with DC circuits and not AC, because of the reference to (+) and (–) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are sinking only or sourcing only 5 can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and 6 the circuit will not operate. However, you can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”. 7 For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, you will have to connect it so the input provides a path to 8 ground (–). Start at the PLC input terminal, follow through the input sensing circuit, exit at the common 9 terminal, and connect the supply (–) to the common terminal. By adding the switch, between the supply (+) and the input, the circuit has been completed . Current 10 flows in the direction of the arrow when the switch is closed. 11 Apply the circuit principle above to the four possible combinations of input/output sinking/sourcing types as shown below. The I/O module 12 specifications at the end of this chapter list the input or output type. Sinking Input Sinking Output 13 14 A B Sourcing Input Sourcing Output C D Before going further in the study of wiring strategies, you must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First the following short definitions are provided, followed by practical applications.
PLC
Input (sinking)
+
Input Sensing
–
Common
Input
+
–
Common
Common
+
–
Input
PLC
Input Sensing
PLC
Input Sensing
PLC
Output Switch
PLC
Output
Load
+
–
Common
Common
+
Output Switch
Output
Load
–
DL205 User Manual, 4th Edition, Rev. D
2-17
Page 62
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
I/O “Common” Terminal Concepts In order for a PLC I/O circuit to operate, current must enter at one terminal and exit at another. Therefore, at least two terminals are associated with every I/O point. In the figure to the right, the Input or Output terminal is the main path for the current. One additional terminal must provide the return path to the power supply.
PLC
Main Path (I/O Point)
I/O Circuit
+ – Return Path
PLC
If there was unlimited space and budget for I/O terminals, every I/O point could have two dedicated terminals as the figure above shows. However, providing this level of flexibility is not practical or even necessary for most applications. So, most Input or Output points on PLCs are in groups which share the return path (called commons). The figure to the right shows a group (or bank) of four input points which share a common return path. In this way, the four inputs require only five terminals instead of eight.
Input 1
Input Sensing
Input 2 Input 3 Input 4 + –
Common
NOTE: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons.
Most DL205 input and output modules group their I/O points into banks that share a common return path. The best indication of I/O common grouping is on the wiring label, such as the one shown to the right. There are two circuit banks with eight input points in each. The common terminal for each is labeled “CA” and “CB”, respectively. In the wiring label example, the positive terminal of a DC supply connects to the common terminals. Some symbols you will see on the wiring labels, and their meanings are: AC supply
DC supply –
Input Switch
AC or DC supply
+
Output Load L
2-18
Field Device
DL205 User Manual, 4th Edition, Rev. D
IN 24 VDC A 0 4 1 5 2 6 7 B 3 D2–16ND3–2 20-28VDC 8mA CLASS 2
CA 0 4 1 5 2 6 3 7 NC CB 0 4 1 5 2 6 3 7 D2-16ND3-2
Page 63
Chapter 2: Installation, Wiring and Specifications
Connecting DC I/O to “Solid State” Field Devices
1 2 3 Solid State Input Sensors Several DL205 DC input modules are flexible because they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field 4 device has an open-collector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the +24 auxiliary supply or another 5 supply (+12VDC or +24VDC), as long as the input specifications are met. 6 7 8 In the next circuit, a field device has an open-collector PNP transistor output. It sources current to the PLC input point, which sinks the current back to ground. Since the field device 9 is sourcing current, no additional power supply is required. 10 11 12 Solid State Output Loads 13 Sometimes an application requires connecting a PLC output point to a solid state input on a device. This type of connection is usually made to carry a low-level control signal, not to send 14 DC power to an actuator. Several of the DL205 DC output modules are the sinking type. This means that each DC output provides a path to ground when it is energized. In the following circuit, the PLC output A point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. B C D In the previous section on Sourcing and Sinking concepts, the DC I/O circuits were explained to sometimes only allow current to flow one way. This is also true for many of the field devices which have solid-state (transistor) interfaces. In other words, field devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking.
Field Device
PLC DC Input
Input (sourcing)
Output (sinking)
Supply
Ground
–
+
Common
Field Device +V
PLC DC Input
Input
Output (sourcing) Ground
(sinking)
Common
PLC DC Sinking Output Power +DC pwr
Field Device +V
Output
(sinking)
+
Common
–
Input (sourcing) 10–30 VDC Ground
DL205 User Manual, 4th Edition, Rev. D
2-19
Page 64
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-20
In the next example a PLC sinking DC output point is connected to the sinking input of a field device. This is a little tricky, because both the PLC output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, a sourcing capability needs to be added to the PLC output by using a pull-up resistor. In the circuit below, a Rpull-up is connected from the output to the DC output circuit power input. PLC DC Output
Power
+DC pwr
Field Device
R pull-up
(sourcing)
(sinking)
Output Supply Common
+
Input (sinking)
–
Ground
R input
NOTE 1: DO NOT attempt to drive a heavy load (>25mA) with this pull-up method NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the PLC output is OFF, from a ladder logic point of view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device.
It is important to choose the correct value of Rpull-up. In order to do so, you need to know the nominal input current to the field device (Iinput) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15mA). Then use Iinput and the voltage of the external supply to compute Rpull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly. I input
=
R pull-up =
V input (turn–on) R input V supply – 0.7 I input
– R input
P pull-up =
V supply2 R pullup
Of course, the easiest way to drive a sinking input field device as shown below is to use a DC sourcing output module. The Darlington NPN stage will have about 1.5 V ON-state saturation, but this is not a problem with low-current solid-state loads. PLC DC Sourcing Output +DC pwr
Common Field Device Output (sourcing) Supply
DL205 User Manual, 4th Edition, Rev. D
+
Input (sinking)
–
Ground
R input
Page 65
Chapter 2: Installation, Wiring and Specifications
Relay Output Guidelines Several output modules in the DL205 I/O family feature relay outputs: D2–04TRS, D2–08TR, D2–12TR, D2–08CDR, F2–08TR and F2–08TRS. Relays are best for the following applications:
1 • Loads that require higher currents than the solid-state outputs can deliver 2 • Cost-sensitive applications • output channels need isolation from other outputs (such as when some loads require different 3 voltages than other loads) Some applications in which NOT to use relays: 4 • Loads that require currents under 10 mA • Loads which must be switched at high speed or heavy duty cycle 5 Relay outputs in the DL205 output modules are available in two 6 contact arrangements, shown to the right. The Form A type, or SPST (single pole, single throw) type is normally open and is the 7 simplest to use. The Form C type, or SPDT (single pole, double throw) type has a center contact which moves and a stationary contact on either side. This provides a normally closed contact 8 and a normally open contact. Some relay output module’s relays share common terminals, 9 which connect to the wiper contact in each relay of the bank. Other relay modules have relays which are completely isolated 10 from each other. In all cases, the module drives the relay coil when the corresponding output point is on. 11 Relay Outputs – Transient Suppression for Inductive Loads in a Control System 12 The following pages are intended to give a quick overview of the negative effects of transient voltages on a control system and provide some simple advice on how to effectively minimize them. The need for transient suppression is often not apparent to the newcomers in the 13 automation world. Many mysterious errors that can afflict an installation can be traced back to a lack of transient suppression. 14 What is a Transient Voltage and Why is it Bad? Inductive loads (devices with a coil) generate transient voltages as they transition from being A energized to being de-energized. If not suppressed, the transient can be many times greater than the voltage applied to the coil. These transient voltages can damage PLC outputs or other electronic devices connected to the circuit, and cause unreliable operation of other electronics B in the general area. Transients must be managed with suppressors for long component life and reliable operation of the control system. C This example shows a simple circuit with a small 24V/125mA/3W relay. As you can see, when the switch is opened, thereby de-energizing the coil, the transient voltage generated across the D switch contacts peaks at 140V. Relay with Form A contacts
Relay with Form C contacts
DL205 User Manual, 4th Edition, Rev. D
2-21
Page 66
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-22
Example: Circuit with no Suppression
Oscilloscope
Volts 160 140 120
24 VDC
100
+ -
80
Relay Coil (24V/125mA/3W, AutomationDirect part no. 750-2C-24D)
60 40 20 0 -20
In the same circuit, replacing the relay with a larger 24V/290mA/7W relay will generate a transient voltage exceeding 800V (not shown). Transient voltages like this can cause many problems, including: • contacts driving the coil may experience arcing, which can pit the contacts and reduce the relay’s lifespan. • state (transistor) outputs driving the coil can be damaged if the transient voltage exceeds the transistor’s ratings. In extreme cases, complete failure of the output can occur the very first time a coil is de-energized. • circuits, which might be connected to monitor the coil or the output driver, can also be damaged by the transient voltage.
A very destructive side-effect of the arcing across relay contacts is the electromagnetic interference (EMI) it can cause. This occurs because the arcing causes a current surge, which releases RF energy. The entire length of wire between the relay contacts, the coil, and the power source carries the current surge and becomes an antenna that radiates the RF energy. It will readily couple into parallel wiring and may disrupt the PLC and other electronics in the area. This EMI can make an otherwise stable control system behave unpredictably at times. PLC’s Integrated Transient Suppressors Although the PLC’s outputs typically have integrated suppressors to protect against transients, they are not capable of handling them all. It is usually necessary to have some additional transient suppression for an inductive load. The next example uses the same 24V/125mA/3W relay used earlier. This example measures the PNP transistor output of a D0-06DD2 PLC, which incorporates an integrated Zener diode for transient suppression. Instead of the 140V peak in the first example, the transient voltage here is limited to about 40V by the Zener diode. While the PLC will probably tolerate repeated transients in this range for some time, the 40V is still beyond the module’s peak output voltage rating of 30V.
DL205 User Manual, 4th Edition, Rev. D
Page 67
Chapter 2: Installation, Wiring and Specifications Example: Small Inductive Load with Only Integrated Suppression
1 2 3 4 5 6 The next example uses the same circuit as above, but with a larger 24V/290mA/7W relay, thereby creating a larger inductive load. As you can see, the transient voltage generated is much worse, peaking at over 50V. Driving an inductive load of this size without additional transient 7 suppression is very likely to permanently damage the PLC output. 8 9 10 11 12 13 Additional transient suppression should be used in both these examples. If you are unable to measure the transients generated by the connected loads of your control system, using 14 additional transient suppression on all inductive loads would be the safest practice. A B C D 2VFLOORVFRSH
9ROWV
9'&
&RLO
Example: Larger Inductive Load with Only Integrated Suppression 2VFLOORVFRSH
9ROWV
9'&
&RLO
DL205 User Manual, 4th Edition, Rev. D
2-23
Page 68
Chapter 2: Installation, Wiring and Specifications Types of Additional Transient Protection
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-24
DC Coils: The most effective protection against transients from a DC coil is a flyback diode. A flyback diode can reduce the transient to roughly 1V over the supply voltage, as shown in this example. DC Flyback Circuit
Volts
Oscilloscope
30 25 20
+ 24 VDC _
15 10 5 0 -5
Sinking
Sourcing
Many AutomationDirect socketed relays and motor starters have add-on flyback diodes that plug or screw into the base, such as the AD-ASMD-250 protection diode module and 784-4C-SKT-1 socket module shown below. If an add-on flyback diode is not available for your inductive load, an easy way to add one is to use AutomationDirect’s DN-D10DR-A diode terminal block, a 600VDC power diode mounted in a slim DIN rail housing.
AD-ASMD-250 Protection Diode Module
784-4C-SKT-1 Relay Socket
DL205 User Manual, 4th Edition, Rev. D
DN-D10DR-A Diode Terminal Block
Page 69
Chapter 2: Installation, Wiring and Specifications Two more common options for DC coils are Metal Oxide Varistors (MOV) or TVS diodes. These devices should be connected across the driver (PLC output) for best protection as shown below. The optimum voltage rating for the suppressor is the lowest rated voltage available that will NOT conduct at the supply voltage, while allowing a safe margin. AutomationDirect’s ZL-TSD8-24 transorb module is a good choice for 24VDC circuits. It is a bank of 8 uni-directional 30V TVS diodes. Since they are uni-directional, be sure to observe the polarity during installation. MOVs or bi-directional TVS diodes would install at the same location, but have no polarity concerns.
1 2 3 DC MOV or TVS Diode Circuit 4 5 6 7 AC Coils: 8 Two options for AC coils are MOVs or bi-directional TVS diodes. These devices are most effective at protecting the driver from a transient voltage when connected across the driver 9 (PLC output) but are also commonly connected across the coil. The optimum voltage rating for the suppressor is the lowest rated voltage available that will NOT conduct at the supply 10 voltage, while allowing a safe margin. AutomationDirect’s ZL-TSD8-120 transorb module is a good choice for 120VAC circuits. It 11 is a bank of eight bi-directional 180V TVS diodes. 12 13 14 A NOTE: Manufacturers of devices with coils frequently offer MOV or TVS diode suppressors as an add-on option which mount conveniently across the coil. Before using them, carefully check the suppressor’s ratings. Just because the suppressor is made specifically for that part does not mean it will reduce the B transient voltages to an acceptable level. C For example, a MOV or TVS diode rated for use on 24-48 VDC coils would need to have a high enough voltage rating to NOT conduct at 48V. That suppressor might typically start conducting at roughly 60VDC. If it were mounted across a 24V coil, transients of roughly D 84V (if sinking output) or -60V (if sourcing output) could reach the PLC output. Many +
24 VDC _
Sinking
Sourcing
AC MOV or Bi-Directional Diode Circuit
VAC semiconductor PLC outputs cannot tolerate such levels.
DL205 User Manual, 4th Edition, Rev. D
2-25
Page 70
Chapter 2: Installation, Wiring and Specifications
I/O Modules Position, Wiring, and Specification
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Slot Numbering The DL205 bases each provide different numbers of slots for use with the I/O modules. You may notice the bases refer to 3-slot, 4-slot, etc. One of the slots is dedicated to the CPU, so you always have one less I/O slot. For example, you have five I/O slots with a 6-slot base. The I/O slots are numbered 0–4. The CPU slot always contains a PLC CPU or other CPU–slot controller and is not numbered.
Module Placement Restrictions The following table lists the valid locations for all types of modules in a DL205 system: Module/Unit
Local CPU Base
CPUs DC Input Modules . AC Input Modules DC Output Modules AC Output Modules Relay Output Modules Analog Input and Output Modules Local Expansion Base Expansion Module Base Controller Module Serial Remote I/O Remote Master Remote Slave Unit Ethernet Remote Master CPU Interface Ethernet Base Controller WinPLC DeviceNet Profibus SDS Specialty Modules Counter Interface Counter I/O Data Communications Ethernet Communications BASIC CoProcessor Simulator Filler
CPU Slot Only
CPU Slot
I/O Slots
Local Expansion Base
Remote I/O Base
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A CPU Slot Only
A CPU Slot Only A Slot 0 Only
Slot 0 Only*
Slot 0 Only Slot 0 Only Slot 0 Only Slot 0 Only Slot 0 Only A*
A A A A A
A
A
A
A
A
* When used with H2-ERM(100) Ethernet Remote I/O system
2-26
Slot 0 Slot 1 Slot 2 Slot 3 Slot 4
DL205 User Manual, 4th Edition, Rev. D