Chapter 2: Installation, Wiring and Specifications 5. ground terminal on the DL205 base must be connected to a single point ground. Use copper stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact. Remove anodized finishes and use copper lugs and star washers at termination points. A general rule is to achieve a 0.1 ohm of DC resistance between the DL205 base and the single point ground.
1 2 6. must be a single point ground (i.e., copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. For this connection you should 3 use #12 AWG stranded copper wire at a minimum. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your region. A 4 good common ground reference (Earth ground) is essential for proper operation of the DL205. Methods of providing an adequate common ground reference include: • Installing a ground rod as close to the panel as possible. 5 • Connection to incoming power system ground. 7. evaluate any installations where the ambient temperature may approach the lower or upper 6 limits of the specifications. Place a temperature probe in the panel, close the door and operate the system until the ambient temperature has stabilized. If the ambient temperature is not within the 7 operating specification for the DL205 system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the DL205 operating specifications. 8. mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. 8 Tapped holes instead of nut–bolt arrangements should be used whenever possible. To ensure good contact on termination areas, impediments such as paint, coating or corrosion should be removed 9 in the area of contact. 9. DL205 system is designed to be powered by 110/220 VAC, 24VDC, or 125VDC normally available throughout an industrial environment. Electrical power in some areas where the PLCs 10 are installed is not always stable and storms can cause power surges. Due to this, powerline filters are recommended for protecting the DL205 PLCs from power surges and EMI/RFI noise. The Automation Powerline Filter, for use with 120VAC and 240VAC, 1–5 Amps, is an excellent choice 11 (can be located at www.automationdirect.com); however, you can use a filter of your choice. These units install easily between the power source and the PLC. 12 Enclosures Your selection of a proper enclosure is important to ensure safe and proper operation of your 13 DL205 system. Applications of DL205 systems vary and may require additional features. The minimum considerations for enclosures include: 14 • Conformance to electrical standards • Protection from the elements in an industrial environment A • Common ground reference • Maintenance of specified ambient temperature B • Access to equipment • Security or restricted access C • Sufficient space for proper installation and maintenance of equipment D DL205 User Manual, 4th Edition, Rev. D
2-7
Page 52
Chapter 2: Installation, Wiring and Specifications
Environmental Specifications
The following table lists the environmental specifications that generally apply to the DL205 1 system (CPU, Bases, I/O Modules). The ranges that vary for the Handheld Programmer are noted at the bottom of this chart. I/O module operation may fluctuate depending on the ambient temperature and your application. Refer to the appropriate I/O module specifications 2 for the temperature derating curves applying to specific modules. 3 Specification Rating Storage Temperature 4 Ambient Operating Temperature* Ambient Humidity** Resistance 5 Vibration Shock Resistance Immunity 6 Noise Atmosphere 7 8 9 Power The power source must be capable of supplying voltage and current complying with the base 10 power supply specifications. Specification AC Powered Bases 24VDC Powered Bases 125VDC Powered Bases 11 Part Numbers 12 Input Voltage Range 13 Maximum Inrush Current Maximum Power 14 Voltage Withstand (dielectric) Insulation Resistance A Auxiliary 24 VDC Output (internal to base power B Fusing supply) C D –4°F to 158°F (–20°C to 70°C) 32°F to 131°F (0°C to 55°C)
30% – 95% relative humidity (non–condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3–304)
No corrosive gases
* Operating temperature for the Handheld Programmer and the DV-1000 is 32° to 122°F (0° to 50°C) Storage temperature for the Handheld Programmer and the DV-1000 is - 4° to 158° F (- 20° to 70°C). ** will operate below 30% humidity. However, static electricity problems occur much more frequently at lower humidity levels. Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, anti-static floor coverings, etc., if you use the equipment in low humidity environments.
D2–03B–1, D2–03BDC1–1, D2–04B–1, D2–04BDC1–1, D2–06BDC2–1, D2–06B–1 D2–06BDC1–1, D2–09BDC2–1 D2–09B–1 D2–09BDC1–1 100–240 VAC (+10%/ –15%) 10.2 – 28.8 VDC (24VDC) with 104–240 VDC 50/60Hz less than 10% ripple +10% –15% 30A 10A 20A 80VA
25W
30W
1 minute @ 1500VAC between primary, secondary, and field ground
2-8
> 10 MΩ at 500VDC 20–28 VDC, less than 1V p-p None 300mA max.
20–28 VDC, less than 1V p-p 300mA max.
Non–replaceable 2A @ 250V Non–replaceable 3.15A @ slow blow fuse 250V slow blow fuse
Non–replaceable 2A @ 250V slow blow fuse
DL205 User Manual, 4th Edition, Rev. D
Page 53
Chapter 2: Installation, Wiring and Specifications
Marine Use
1 2 3 NOTE: Wiring needs to be “low smoke” per the above paragraph. Teflon coated wire is also recommended. 4 Agency Approvals Some applications require agency approvals. Typical agency approvals that your application 5 may require are: • UL (Underwriters Laboratories, LLC) 6 • CSA (Canadian Standards Association) • FM (Factory Mutual Research Corporation) • CUL (Underwriters Laboratories of Canada) 7 24 VDC Power Bases 8 Follow these additional installation guidelines when installing D2-03BDC1-1, D2-04BDC1-1, D2-06BDC1-1 and D2-09BDC1-1 bases: 9 • these bases in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application. • bases must be used within their marked ratings. 10 • bases are intended to be installed within an enclosure rated at least IP54. • should be made to prevent the rated voltage being exceeded by transient disturbances of 11 more than 40%. 12 13 14 A B C D American Bureau of Shipping (ABS) certification requires flame-retarding insulation as per 4-8-3/5.3.6(a). ABS will accept Navy low smoke cables, cable qualified to NEC “Plenum rated” (fire resistant level 4), or other similar flammability resistant rated cables. Use cable specifications for your system that meet a recognized flame retardant standard (i.e., UL, IEEE, etc), including evidence of cable test certification (i.e. tests certificate, UL file number, etc).
DL205 User Manual, 4th Edition, Rev. D
2-9
Page 54
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Installing DL205 Bases
2-10
Choosing the Base Type The DL205 system offers four different sizes of bases and three different power supply options. The following diagram shows an example of a 6-slot base. Your choice of base depends on three things:
Power Wiring Connections
CPU Slot
I/O Slots
• Number of I/O modules required • Input power requirement (AC or DC power) • Available power budget
Mounting the Base All I/O configurations of the DL205 may use any of the base configurations. The bases are secured to the equipment panel or mounting location using four M4 screws in the corner tabs of the base. The full mounting dimensions are given in the previous section on Mounting Guidelines.
Mounting Tabs
WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component.
DL205 User Manual, 4th Edition, Rev. D
Page 55
Chapter 2: Installation, Wiring and Specifications
Using Mounting Rails The DL205 bases can also be secured to the cabinet using mounting rails. You should use rails that conform to DIN EN standard 50 022. Refer to our catalog for a complete line of DINrail, DINnectors and DIN-rail mounted apparatus. These rails are approximately 35mm high, with a depth of 7.5 mm. If you mount the base on a rail, you should also consider using end brackets on each end of the rail. The end brackets help keep the base from sliding horizontally along the rail. This helps minimize the possibility of accidentally pulling the wiring loose. If you examine the bottom of the base, you’ll notice small retaining clips. To secure the base to a DIN-rail, place the base onto the rail and gently push up on the retaining clips. The clips lock the base onto the rail. To remove the base, pull down on the retaining clips, lift up on the base slightly, and pull it away from the rail.
DIN Rail Dimensions 7.5mm
35 mm
Retaining Clips
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2-11
Page 56
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Installing Components in the Base
2-12
To insert components into the base: first slide the module retaining clips to the out position and align the PC board(s) of the module with the grooves on the top and bottom of the base. Push the module straight into the base until it is firmly seated in the backplane connector. Once the module is inserted into the base, push in the retaining clips to firmly secure the module to the base.
CPU must be positioned in the first slot of the base Align module PC board to slots in base and slide in Push the retaining clips in to secure the module to the DL205 base WARNING: Minimize the risk of electrical shock, personal injury, or equipment damage. disconnect the system power before installing or removing any system component.
DL205 User Manual, 4th Edition, Rev. D
Always
Page 57
Chapter 2: Installation, Wiring and Specifications
Base Wiring Guidelines
1 The diagrams show the terminal connections 2 located on the power supply of the DL205 bases. The base terminals can accept up to 16 3 AWG. You may be able to use larger wiring depending on the type of wire used, but 16 AWG is the recommended size. Do not overtighten the 4 connector screws; the recommended torque value is 7.81 lb·in (0.882 N·m). + 5 NOTE: You can connect either a 115VAC or 220VAC supply to the AC terminals. Special wiring or jumpers 6 are not required as with some of the other DirectLOGIC products. 7 WARNING: Once the power wiring is connected, install the plastic protective cover. When the cover is removed there is a risk of electrical shock if you accidentally touch the wiring or wiring terminals. 8 9 12/24 VDC Base Terminal Strip 125 VDC Base Terminal Strip 10 11 12 13 14 A B C D
Base Wiring
110/220 VAC Base T erminal Strip
85 – 264 VAC G
LG
24 VDC OUT, 0.3A
+ 12 – 24 VDC – G
+
115 – 264 VDC – G
+ 24 VDC OUT, 0.3A –
DL205 User Manual, 4th Edition, Rev. D
2-13
Page 58
Chapter 2: Installation, Wiring and Specifications
I/O Wiring Strategies
2-14
The DL205 PLC system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems.
PLC Isolation Boundaries PLC circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A powerline filter will provide isolation between the power source and the power supply. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a PLC, it is extremely important to avoid making external connections that connect logic side circuits to any other. Secondary, or Logic side
Primary Side
PLC
Power Input
Main Power Supply
Filter
Isolation Boundary
CPU
Field Side
(backplane)
Input Module
Inputs
(backplane)
Output Module
Outputs
Programming Device, Operator Interface, or Network
Isolation Boundary
In addition to the basic circuits covered above, AC-powered and 125VDC bases include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits!
Primary Side Power Input
Filter
+24VDC Out
Main Power Supply
Auxiliary +24VDC Supply
DL205 PLC
Secondary, or Logic side Internal
CPU
Backplane
Comm.
Input Module
Output Module
To Programming Device, Operator Interface, Network
Inputs Commons
Outputs Commons
Field Side
Supply for Output Circuit
DL205 User Manual, 4th Edition, Rev. D
Safety Guidelines
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Page 59
Chapter 2: Installation, Wiring and Specifications
Powering I/O Circuits with the Auxiliary Supply
1 2 3 4 5 DL205 PLC Auxiliary Input Module Output Module 6 +24VDC Inputs Com. Outputs Com. Supply 7 – + 8 9 10 The 12/24 VDC-powered DL205 bases are designed for application environments in which low-voltage DC power is more readily available than AC. These include a wide range of battery–powered applications, such as remotely-located control, in vehicles, portable machines, 11 etc. For this application type, all input devices and output loads typically use the same DC power source. Typical wiring for DC-powered applications is shown in the following diagram. 12 + 13 – 14 DL205 PLC A Input Module Output Module Inputs Com. Outputs Com. B C D In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 300mA. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply. All AC powered and 125VDC DL205 bases feature the internal auxiliary supply. If input devices AND output loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram. AC Power or 125VDC Bases
Power Input
Loads
+
DC Power
–
Power Input
Loads
DL205 User Manual, 4th Edition, Rev. D
2-15
Page 60
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2-16
Powering I/O Circuits Using Separate Supplies In most applications it will be necessary to power the input devices from one power source, and to power output loads from another source. Loads often require high-energy AC power, while input sensors use low-energy DC. If a machine operator is likely to come in close contact with input wiring, then safety reasons also require isolation from high-energy output circuits. It is most convenient if the loads can use the same power source as the PLC, and the input sensors can use the auxiliary supply, as shown to the left in the figure below. If the loads cannot be powered from the PLC supply, then a separate supply must be used as shown to the right in the figure below. AC Power Power Input
Auxiliary +24VDC Supply
+
AC Power Power Input
DL205 PLC Input Module
Output Module
Inputs
Outputs Com.
Com.
–
Auxiliary +24VDC Supply
+
DL205 PLC Input Module
Output Module
Inputs
Outputs Com.
Com.
–
Loads
Loads
Load Supply
Some applications will use the PLC external power source to also power the input circuit. This typically occurs on DC-powered PLCs, as shown in the drawing below to the left. The inputs share the PLC power source supply, while the outputs have their own separate supply. A worstcase scenario, from a cost and complexity viewpoint, is an application which requires separate power sources for the PLC, input devices, and output loads. The example wiring diagram below on the right shows how this can work, but also the auxiliary supply output is an unused resource. You will want to avoid this situation if possible. +
+
–
–
DC Power AC Power
DL205 PLC Power Input
Power Input
Input Module
Output Module
Inputs
Outputs Com.
Com.
Auxiliary +24VDC Supply
+ Loads
Load Supply
DL205 User Manual, 4th Edition, Rev. D
DL205 PLC Input Module
Output Module
Inputs
Com.
Outputs Com.
Input Supply
Loads
– Load Supply