Chapter 4: System Design and Configuration

Removing a Manual Configuration

1 2 Power–On I/O Configuration Check The DL205 CPUs can also be set to automatically check the I/O configuration on power-up. 3 By selecting this feature, you can detect any changes that may have occurred while the power was disconnected. For example, if someone places an output module in a slot that previously held an input module, the CPU will not go into RUN mode and the configuration check will 4 detect the change and print a message on the Handheld Programmer or DirectSOFT screen (use AUX 44 on the HPP to enable the configuration check). 5 If the system detects a change in the PLC/Setup/I/O configuration check at power-up, error code E252 will be generated. You can use AUX 42 (HPP) or DirectSOFT I/O diagnostics to determine the exact base and slot location where the change occurred. When a configuration 6 error is generated, you may actually want to use the new I/O configuration. For example, you may have intentionally changed an I/O module to use with a program change. You can use 7 PLC/Diagnostics/I/O Diagnostics in DirectSoft or AUX 45 to select the new configuration, or, keep the existing configuration stored in memory. 8 WARNING: You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of 9 personal injury or damage to equipment. WARNING: Verify that the I/O configuration being selected will work properly with the CPU program. Always correct any I/O configuration errors before placing the CPU in RUN mode. Uncorrected errors 10 can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment. 11 12 13 14 A B C D After a manual configuration, the system will automatically retain the new I/O addresses through a power cycle. You can remove (overwrite) any manual configuration changes by changing all of the manually configured addresses back to automatic.

DL205 User Manual, 4th Edition, Rev. D

4-5

Page 172

Chapter 4: System Design and Configuration

I/O Points Required for Each Module

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Each type of module requires a certain number of I/O points. This is also true for some specialty modules, such as analog, counter interface, etc.

DC Input Modules D2–08ND3 D2–16ND3–2 D2–32ND3(–2)

AC Input Modules D2–08NA–1 D2–08NA–2 D2–16NA

DC Output Modules D2–04TD1 D2–08TD1 D2–16TD1–2 (2-2) D2–16TD1(2)P D2–32TD1(–2)

AC Output Modules D2–08TA F2–08TA D2–12TA

Relay Output Modules D2–04TRS D2–08TR F2–08TRS F2–08TR D2–12TR

Combination Modules D2–08CDR

Analog Modules F2–04AD–1 & 1L F2–04AD–2 & 2L F2–08AD–1 F2–02DA–1 & 1L F2–02DA–2 & 2L F2–08DA–1 F2–08DA–2 F2–02DAS–1 F2–02DAS–2 F2–4AD2DA F2–8AD4DA-1 F2–8AD4DA-2 F2–04RTD F2–04THM

4-6

Number of I/O Pts. Required Specialty Modules, etc. Number of I/O Pts. Required 8 Input 16 Input 32 Input 8 Input 8 Input 16 Input 8 Output (Only the first four points are used) 8 Output 16 Output 16 Output 32 Output 8 Output 8 Output 16 Output (See note 1)

H2–ECOM(–F) D2–DCM H2–ERM(100,–F) H2–EBC(–F) D2–RMSM D2–RSSS F2–CP128 H2–CTRIO(2)

None None None None None None None None

D2–CTRINT

8 Input 8 Output

F2–DEVNETS–1 H2–PBC F2–SDS–1 D2–08SIM D2-EM D2-CM H2-ECOM(100)

None None None 8 Input None None None

8 Output (Only the first four points are used) 8 Output 8 Output 8 Output 16 Output (See note 1) 8 In, 8 Out (Only the first four points are used for each type) 16 Input 16 Input 16 Input 16 Output 16 Output 16 Output 16 Output 32 Output 32 Output 16 Input & 16 Output 32 Input & 32 Output 32 Input & 32 Output 32 Input 32 Input

NOTE: 12pt. modules consume 16 points. The first 6 points are assigned, two are skipped, and then the next 6 points are assigned. For example, a D2–12TA installed in slot 0 would use Y0–Y5, and Y-10-Y15. Y6–Y7 and Y16–Y17 would be unused.

DL205 User Manual, 4th Edition, Rev. D

Page 173

Chapter 4: System Design and Configuration

Calculating the Power Budget

1 When you determine the types and quantities of I/O modules you will be using in the DL205 system, it is important to remember there is a limited amount of power available from the 2 power supply. We have provided a chart to help you easily see the amount of power available with each base. The following chart will help you calculate the amount of power you need 3 with your I/O selections. At the end of this section is an example of power budgeting and a worksheet for your own calculations. 4 If the I/O you choose exceeds the maximum power available from the power supply, you may need to use local expansion bases or remote I/O bases. 5 WARNING: It is extremely important to calculate the power budget. If you exceed the power budget, the system may operate in an unpredictable manner, which may result in a risk of personal injury or 6 equipment damage. 7 CPU Power Specifications The following chart shows the amount of current available for the two voltages supplied from the DL205 base. Use these currents when calculating the power budget for your system. The 8 Auxiliary 24V Power Source mentioned in the table is a connection at the base terminal strip allowing you to connect to devices or DL205 modules that require 24VDC. 9 Bases 5V Current Supplied Auxiliary 24VDC Current Supplied 10 11 12 13 14 Module Power Requirements A Use the power requirements shown on the next page to calculate the power budget for your system. If an External 24VDC power supply is required, the external 24VDC from the base B power supply may be used as long as the power budget is not exceeded. C D Managing Your Power Resource

D2–03B–1 D2–04B–1 D2–06B–1 D2–09B–1 D2–03BDC1–1 D2–04BDC1–1 D2–06BDC1–1 D2–09BDC1–1 D2–06BDC2–1 D2–09BDC2–1

2600 mA 2600 mA 2600 mA 2600 mA 2600 mA 2600 mA 2600 mA 2600 mA 2600 mA 2600 mA

300 mA 300 mA 300 mA 300 mA None None None None 300 mA 300 mA

DL205 User Manual, 4th Edition, Rev. D

4-7

Page 174

Chapter 4: System Design and Configuration Power Consumed

1 Device 5V (mA) 2 CPUs 3 4 DC Input Modules 5 AC Input Modules 6 7 DC Output Modules 8 9 AC Output Modules 10 11 Relay Output Modules 12 13 Analog Modules 14 A B C D

24V Auxilliary (mA)

D2–230 D2–240 D2–250–1 D2–260

120 120 330 330

0 0 0 0

D2–08ND3 D2–16ND3–2 D2–32ND3(–2)

50 100 25

0 0 0

D2–08NA–1 D2–08NA–2 D2–16NA

50 100 100

0 0 0

D2–04TD1 D2–08TD1(–2) D2–16TD1–2 D2–16TD2–2 D2–32TD1(–2)

60 100 200 200 350

20 0 80 0 0

D2–08TA F2–08TA D2–12TA

250 250 350

0 0 0

D2–04TRS D2–08TR F2–08TRS F2–08TR D2–12TR

250 250 670 670 450

0 0 0 0 0

F2–04AD–1 50 F2–04AD–1L 100 F2–04AD–2 110 F2–04AD–2L 60 F2–08AD–1 100 F2–08AD–2 100 F2–02DA–1 40 F2–02DA–1L 40 F2–02DA–2 40 F2–02DA–2L 40 F2–08DA–1 30 F2–08DA–2 60 *requires external 5VDC for outputs **add an additional 20mA per loop

4-8

80 5mA @ 10-30V 5mA @ 10-30V 90mA @ 12V** 5mA @ 10-30V 5mA @ 10-30V 60** 70mA @ 12V** 60 70mA @ 12V** 50mA** 140

Power Consumed Device

24V Auxilliary (mA)

5V (mA)

Combination Modules D2–08CDR

200

0

H2–PBC H2–ECOM H2–ECOM100 H2–ECOM-F H2–ERM(100) H2–ERM–F H2–EBC H2–EBC–F H2–CTRIO(2) D2–DCM D2–RMSM D2–RSSS D2–CTRINT D2–08SIM D2–CM D2–EM F2–CP128 F2–DEVNETS–1 F2–SDS–1

530 450 300 640 320 450 320 450 275 300 200 150 50* 50 100 130 235 160 160

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

F2–02DAS–1 F2–02DAS–2 F2–4AD2DA F2–8AD4DA-1 F2–8AD4DA-2 F2–04RTD F2–04THM

100 100 90 35 35 90 110

50mA per channel 60mA per channel 80mA** 100 80 0 60

Specialty Modules

DL205 User Manual, 4th Edition, Rev. D

Page 175

Chapter 4: System Design and Configuration

Power Budget Calculation Example

1 Auxiliary Base # 2 Module Type 5 VDC (mA) Power Source 0 24 VDC Output (mA) Available Base Power D2–09B–1 2600 300 3 4 5 6 7 8 Total Power Required 1520 140 9 Remaining Power Available 2600–1520 = 1080 300 – 140 = 160 1. the power budget table to fill in the power requirements for all the system components. 10 First, enter the amount of power supplied by the base. Next, list the requirements for the CPU, any I/O modules, and any other devices, such as the Handheld Programmer, C-more HMI or the DV–1000 operator interface. Remember, even though the Handheld 11 Programmer or the DV–1000 are not installed in the base, they still obtain their power from the system. Also, make sure you obtain any external power requirements, such as the 12 24VDC power required by the analog modules. 2. the current columns starting with CPU slot and put the total in the row labeled “Total 13 Power Required.” 3. the row labeled “Total Power Required” from the row labeled “Available Base 14 Power.” Place the difference in the row labeled “Remaining Power Available.” 4. “Total Power Required” is greater than the power available from the base, the power budget will be exceeded. It will be unsafe to use this configuration, and you will need to A restructure your I/O configuration. B WARNING: It is extremely important to calculate the power budget. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage. C D The following example shows how to calculate the power budget for the DL205 system.

CPU Slot Slot 0 Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Other Handheld Programmer

D2–260 D2–16ND3–2 D2–16NA D2–16NA F2–04AD–1 F2–02DA–1 D2–08TA D2–08TD1 D2–08TR

+ 330 + 100 + 100 + 100 + 50 + 40 + 250 + 100 + 250

+0 +0 +0 + 80 + 60 +0 +0 +0

D2–HPP

+ 200

+0

DL205 User Manual, 4th Edition, Rev. D

4-9

Page 176

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Power Budget Calculation Worksheet This blank chart is provided for you to copy and use in your power budget calculations. Base # 0

Module Type

5 VDC (mA)

Auxiliary Power Source 24 VDC Output (mA)

Available Base Power CPU Slot Slot 0 Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Other

4-10

Total Power Required Remaining Power Available

1. the power budget table to fill in the power requirements for all the system components. This includes the CPU, any I/O modules, and any other devices, such as the Handheld Programmer, C-more HMI or the DV–1000 operator interface. Also, make sure you obtain any external power requirements, such as the 24VDC power required by the analog modules. 2. the current columns starting with CPU slot and put the total in the row labeled “Total Power Required.” 3. the row labeled “Total Power Required” from the row labeled “Available Base Power.” Place the difference in the row labeled “Remaining Power Available.” 4. “Total Power Required” is greater than the power available from the base, the power budget will be exceeded. It will be unsafe to use this configuration, and you will need to restructure your I/O configuration. WARNING: It is extremely important to calculate the power budget. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

DL205 User Manual, 4th Edition, Rev. D

Page 177

Chapter 4: System Design and Configuration

Local Expansion I/O Use local expansion when you need more I/O points, a greater power budget than the local CPU base provides or when placing an I/O base at a location away from the CPU base, but within the expansion cable limits. Each local expansion base requires the D2–CM controller module in the CPU slot. The local CPU base requires the D2–EM expansion module, as well as each expansion base. All bases in the system must be the new (–1) bases. These bases have a connector on the right side of the base to which the D2–EM expansion module attaches. All local and local expansion I/O points are updated on every CPU scan. Use the DirectSOFT PLC Configure I/O menu option to view the local expansion system automatic I/O addressing configuration. This menu also allows manual addresses to be assigned if necessary. DL230 Total number of local / expansion bases per system Maximum number of expansion bases Total I/O (includes CPU base and expansion bases) Maximum inputs Maximum outputs Maximum expansion system cable length

DL240

DL250

DL250-1

These CPUs do not support local expansion systems

DL260

3 5 2 4 768 1280 512 1024 512 1024 30m (98ft.)

D2–CM Local Expansion Module The D2–CM module is placed in the CPU slot of each expansion base. The rotary switch is used to select the expansion base number. The expansion base I/O addressing (Xs and Ys) is based on the numerical order of the rotary switch selection and is recognized by the CPU on power–up. Duplicate expansion base numbers will not be recognized by the CPU. The status indicator LEDs on the D2– CM front panels have specific functions which can help in programming and troubleshooting. D2–CM Indicators PWR (Green) RUN (Green) DIAG (Red)

Status ON OFF ON OFF ON ON/OFF OFF

Expansion Controller

Meaning Power good Power failure D2–CM has established communication with PLC D2–CM has not established communication with PLC Hardware watch–dog failure I/O module failure (ON 500ms / OFF 500ms) No D2–CM error

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

4-11

Page 178

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

D2–EM Local Expansion Module The D2–EM expansion unit is attached to the right side of each base in the expansion system, including the local CPU base. (All bases in the local expansion system must be the new (–1) bases). The D2–EMs on each end of the expansion system should have the TERM (termination) switch placed in the ON position. The expansion units between the endmost bases should have the TERM switch placed in the OFF position. The CPU base can be located at any base position in the expansion system. The bases are connected in a daisy–chain fashion using the D2–EXCBL–1 (category 5 straight–through cable with RJ45 connectors). Either of the RJ45 ports (labelled A and B) can be used to connect one expansion base to another.

The status indicator LEDs on the D2–EM front panels have specific functions which can help in programming and troubleshooting. D2–EM Indicator

Status

Meaning

ON OFF

ACTIVE (Green)

D2–EM is communicating with other D2–EM D2–EM is not communicating with other D2–EM

WARNING: Connect/disconnect the expansion cables with the PLC power turned OFF in order for the ACTIVE indicator to function normally.

D2–EXCBL–1 Local Expansion Cable The category 5 straight–through D2–EXCBL–1 (1m) is used to connect the D2–EM expansion modules together. If longer cable lengths are required, we recommend that you purchase a commercially manufactured cable with RJ45 connectors already attached. The maximum total expansion system cable length is 30m (98ft). Do not use Ethernet hubs to connect the local expansion network together. D2–EXCBL–1 Cable

1 2 3 4 5 6 78

8-pin RJ45 Connector (8P8C)

1 2 3 4 5 6 7 8

RJ45

GRN/WHT GRN

1 2 3 4 5 GRN 6 7 8

GRN/WHT

RJ45

NOTE: Commercially available Patch (Straight–through) Category 5, UTP cables will work in place of the D2–EXCBL–1. The D2–EM modules only use the wires connected to pins 3 and 6 as shown above.

4-12

DL205 User Manual, 4th Edition, Rev. D

Page 179

Chapter 4: System Design and Configuration

DL260 Local Expansion System

1 2 3 4 NOTE: Do not use Ethernet hubs 5 to connect the local expansion system together. 6 7 8 NOTE: Use D2-EXCBL-1 (1m) (Category 5 straight-through 9 cable) to connect the D2-EMs together. 10 11 12 • CPU base can be located at any base position in the expansion system. 13 • discrete and analog modules are supported in the expansion bases. Specialty modules are not supported in the expansion bases. 14 • D2–CMs do not have to be in successive numerical order; however, the numerical rotary selection determines the X and Y addressing order. The CPU will recognize the local and A expansion I/O on power–up. Do not duplicate numerical selections. • TERM (termination) switch on the two endmost D2–EMs must be in the ON position. The other D2–EMs in between should be in the OFF position. B • the D2–EXCBL–1 or equivalent cable to connect the D2–EMs together. Either of the RJ45 ports (labeled A and B) on the D2–EM can be used to connect one base to another. C D The D2–260 supports local expansion up to five total bases (one CPU base + four local expansion bases) and up to a maximum of 1280 total I/O points. An example local expansion system is shown below. All local and expansion I/O points are updated on every CPU scan. No specialty modules can be located in the expansion bases (refer to the Module Placement Table earlier in this chapter for restrictions).

D2–CM Expansion Base Number Selection

D2–EM Termination Switch Settings

I/O addressing #5

I/O addressing #4

D2–260 CPU

30m (98ft.) max. cable length

I/O addressing #1

I/O addressing #2

I/O addressing #3

DL205 User Manual, 4th Edition, Rev. D

4-13

Page 180

Chapter 4: System Design and Configuration NOTE: When applying power to the CPU (DL250–1/260) and local expansion bases, make sure the expansion bases power up at the same time or before the CPU base. Expansion bases that power up after the CPU base will not be recognized by the CPU. (See chapter 3 Initialization Process timing specifications).

1 DL250–1 Local Expansion System 2 The D2–250–1 supports local expansion up to three total bases ( one CPU base + two local expansion bases) and up to a maximum of 768 total I/O points. An example local expansion 3 system is shown below. All local and expansion I/O points are updated on every CPU scan. No specialty modules can be located in the expansion bases (refer to the Module Placement 4 Table earlier in this chapter for restrictions). 5 D2–CM Expansion D2–EM Termination Switch Settings Base Number Selection 6 Use D2–EXCBL–1 (1m) (Category 5 straight– 7 through cable) to connect the D2-EMs together. . 8 D2–250–1 CPU 30m (98ft.) max. cable length 9 10 Note: Do not use 11 Ethernet hubs to connect the local expansion system 12 together. 13 • The CPU base can be located at any base position in the expansion system. 14 • discrete and analog modules are supported in the expansion bases. Specialty modules are not supported in the expansion bases. • D2–CMs do not have to be in successive numerical order, however, the numerical rotary A selection determines the X and Y addressing order. The CPU will recognize the local and expansion I/O on power–up. Do not duplicate numerical selections. B • TERM (termination) switch on the two endmost D2–EMs must be in the ON position. The other D2–EMs in between should be in the OFF position. C • the D2–EXCBL–1 or equivalent cable to connect the D2–EMs together. Either of the RJ45 ports (labelled A and B) on the D2–EM can be used to connect one base to another. D I/O addressing #3

I/O addressing #1

I/O addressing #2

4-14