Page 181

Chapter 4: System Design and Configuration

Expansion Base Output Hold Option

1 2 3 4 5 6

Bit = 0 Output Off (Default) 7

Bit = 1 Output Hold 8 D2–CM Expansion Base Hold Output Expansion V–memory Register Slot 0 Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Base No. 9 10 11 WARNING: Selecting “HOLD LAST STATE” means that outputs on the expansion bases will not be 12 under program control in the event of a communications failure. Consider the consequences to process operation carefully before selecting this mode. 13 14 A B C D The bit settings in V–memory registers V7741 and V7742 determine the expansion bases’ outputs response to a communications failure. The CPU will exit the RUN mode to the STOP mode when an expansion base communications failure occurs. If the Output Hold bit is ON, the outputs on the corresponding module will hold their last state when a communication error occurs. If OFF (default), the outputs on the module unit will turn off in response to an error. The setting does not have to be the same for all the modules on an expansion base. The selection of the output mode will depend on your application. You must consider the consequences of turning off all the devices in one or all expansion bases at the same time vs. letting the system run “steady state” while unresponsive to input changes. For example, a conveyor system would typically suffer no harm if the system were shut down all at once. In a way, it is the equivalent of an “E–STOP”. On the other hand, for a continuous process such as waste water treatment, holding the last state would allow the current state of the process to continue until the operator can intervene manually. V7741 and V7742 are reserved for the expansion base Output Hold option. The bit definitions are as follows:

Exp. Base 1 Exp. Base 2 Exp. Base 3 Exp. Base 4

V7741

Bit

V7742

Bit

0 8 0 8

1 9 1 9

2 10 2 10

3 11 3 11

4 12 4 12

5 13 5 13

6 14 6 14

DL205 User Manual, 4th Edition, Rev. D

7 15 7 15

4-15

Page 182

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4-16

Enabling I/O Configuration Check using DirectSOFT Enabling the I/O Config Check will force the CPU, at power up, to examine the local and expansion I/O configuration before entering the RUN mode. If there is a change in the I/O configuration, the CPU will not enter the RUN mode. For example, if local expansion base #1 does not power up with the CPU and the other expansion bases, the I/O Configuration Check will prevent the CPU from entering the RUN mode. If the I/O Configuration check is disabled and automatic addressing is used, the CPU would assign addresses from expansion base #1 to base #2 and possibly enter the RUN mode. This is not desirable, and can be prevented by enabling the I/O Configuration check. Manual addressing can be used to manually assign addresses to the I/O modules. This will prevent any automatic addressing re–assignments by the CPU. The I/O Configuration Check can also be used with manual addressing. To display the I/O Config Check window, use DirectSOFT>PLC menu>Setup>I/O Config Check.

Select “Yes,” then save to disk or to PLC, if connected to the PLC.

DL205 User Manual, 4th Edition, Rev. D

Page 183

Chapter 4: System Design and Configuration

Expanding DL205 I/O

1 Expanding I/O beyond the local chassis is useful for a system which has a sufficient number of sensors and other field devices located a relatively long distance from the CPU. Two forms of 2 communication can be used to add remote I/O to your system: either an Ethernet or a serial communication network. A discussion of each method follows. 3 Ethernet Remote Master, H2-ERM(100, -F) 4 The Ethernet Remote Master, H2-ERM(100, -F), is a module that provides a low-cost, highspeed Ethernet Remote I/O link to connect either a DL240, a DL250-1 or a DL260 CPU to

5 slave I/O over a high-speed Ethernet link.

Each H2-ERM(100) module can support up to 16 additional H2-EBC systems, 16 Terminator

I/O EBC systems, or 16 fully expanded H4-EBC systems. 6

The H2-ERM(100) connects to your control network using Category 5 UTP cables for distances up to 100m (328ft). Repeaters are used to extend the distances and to expand the 7 number of nodes. The fiber optic version, H2-ERM-F, uses industry standard 62.5/125 ST-style fiber optic cables and can be run up to 2,000m (6560ft). 8 The PLC, ERM and EBC slave modules work together to update the remote I/O points. These three scan cycles are occurring at the same time, but asynchronously. We recommend that 9 critical I/O points that must be monitored every scan be placed in the CPU base. Specifications H2-ERM H2-ERM100 H2-ERM-F 10 Communications Data Transfer Rate 11 Link Distance Ethernet Port 12 Ethernet Protocols 13 Power Consumption 14 A B C D I/O Expansion Overview

230 240

250-1 260

10BaseT Ethernet 10/100BaseT Ethernet 10Mbps

100Mbps

10BaseFL Ethernet 10Mbps

100 meters (328 ft)

2000 meters (6560 ft)

RJ45

ST-style fiber optic

TCP/IP, IPX

TCP/IP, IPX, Modbus TCP/IP, DHCP, HTML configuration

320mA @ 5VDC

TCP/IP, IPX

450mA @ 5VDC

DL205 User Manual, 4th Edition, Rev. D

4-17

Page 184

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4-18

Ethernet Remote Master Hardware Configuration Use a PC equipped with a 10/100BaseT or a 10BaseFL network adapter card and the Ethernet Remote Master (ERM) Workbench software configuration utility (included with the ERM manual, H24-ERM-M) to configure the ERM module and its slaves over the Ethernet remote I/O network. PC running ERM WorkBench to configure the ERM network DirectLogic PLC

Dedicated Hub(s) for ERM Network

ERM Module DirectLogic DL205 I/O with EBC Module

GS–EDRV or HA–EDRV2

DirectLogic DL405 I/O with EBC Module

AC Drive

Terminator I/O with EBC Module

When networking ERMs with other Ethernet devices, we recommend that a dedicated Ethernet remote I/O network be used for the ERM and its slaves. While Ethernet networks can handle an extremely large number of data transactions, and normally very quickly, heavy Ethernet traffic can adversely affect the reliability of the slave I/O and the speed of the I/O network. Keep ERM networks, multiple ERM networks and ECOM/office networks isolated from one another. Once the ERM remote I/O network is configured and running, the PC can be removed from the network. DirectLogic PLC

Dedicated Hub(s) for ERM Network

ERM Module DirectLogic DL205 I/O with EBC Module

GS–EDRV or HA–EDRV2

AC Drive

DL205 User Manual, 4th Edition, Rev. D

DirectLogic DL405 I/O with EBC Module

Terminator I/O with EBC Module

Page 185

Chapter 4: System Design and Configuration

Installing the ERM Module

1 2 3 4 5 ERM Module ID 6 Set the ERM Module ID before installing the module in the DL205 base. Always set the module ID to 0. A Module ID can be set in one of two ways: 7 • Use the DIP switches on the module (1-63) • Use the configuration tools in NetEdit Use the DIP switch to install and change slave modules without using a PC to set the Module 8 ID. Set the module’s DIP switch, insert the module in the base, and connect the network cable. The Module ID is set on power up, and it is ready to communicate on the network. 9 10 11 12 13 14 H2-ERM(100) A The Module IDs can also be set or changed on the network from a single PC by using the tools in NetEdit. The Module ID equals the sum of the binary values of the slide switches set in the ON position. B For example, if slide switches 1, 2 and 3 are set to the ON position, the Module ID will be 14. This is found by adding 8+4+2=14. The maximum value which can be set on the DIP switch C is 32+16+8+4+2=63. This is achieved by setting switches 0 through 5 to the ON position. The 6 and 7 switch positions are inactive. D This section will briefly describe the installation of the ERM module. More detailed information is available in the Ethernet Remote Master Module manual, H24-ERM-M, which will be needed to configure the communication link to the remote I/O. In addition to the manual, configuration software will be needed. The ERM Workbench software utility must be used to configure the ERM and its slave modules. The utility is provided on a CD which comes with the ERM manual. The ERM module can be identified by two different methods, either by Module ID (dip switch) or by Ethernet address. Whichever method is used, the ERM Workbench is all that is needed to configure the network modules. If IP addressing (UDP/IP) is necessary or if the Module ID is set with software, the NetEdit software utility (included with the ERM Workbench utility) will be needed in addition to the ERM Workbench.

ON

7

Not Used

6

5 4 3 2 1 0 . . . . . . 25 24 23 22 21 20 . . . . . . (32)(16) (8) (4) (2) (1)

Binary Value

Installation and Safety Guidelines

DL205 User Manual, 4th Edition, Rev. D

4-19

Page 186

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4-20

Insert the ERM Module The DL205 system only supports the placement of the ERM module in the CPU base. It does not support installation of the ERM module in either local expansion or remote I/O bases. The number of usable slots depends on how many slots the base has. All of the DL205 CPUs support the ERM module, except the D2-230. DL205

CPU

Slot 0

Slot 1 Slot 2

Slot 3

Slot 4

Do not install the ERM in Slot 0.

NOTE: The module will not work in slot 0 of the DL205 series PLCs, the slot next to the CPU.

Network Cabling Of the three types of ERM modules available, one supports the 10BaseT standard, another supports 10/100BaseT and the other one supports the 10BaseFL standard. The 10/100BaseT standard uses twisted pairs of copper wire conductors and the 10BaseFL standard is used with fiber optic cabling. 10/100BaseT

10BaseFL

Unshielded Twisted-Pair cable with RJ45 connectors

62.5/125 MMF fiber optics cable with ST-style connectors

DL205 User Manual, 4th Edition, Rev. D

Page 187

Chapter 4: System Design and Configuration 10/100BaseT Networks A patch (straight-through) cable is used to connect a PLC (or PC) to a hub or to a repeater. Use a crossover cable to connect two Ethernet devices (point-to-point) together. It is recommended that pre-assembled cables be purchased for convenient and reliable networking. The above diagram illustrates the standard wire positions of the RJ45 connector. It is recommended that Catagory 5, UTP cable be used for all ERM 10/100BaseT cables.

1 2 3 4 5 10/100BaseT 6 7 8 9 10 Refer to the ERM manual for using the fiber optic cable with the H2-ERM-F. 11 An explanation of the use of the ERM Workbench software is too lengthy for this manual. The full use of the workbench and NetEdit utilities is discussed in the ERM manual. 12 13 14 A B C D Patch (Straight–through) Cable

TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

1 RD+ 2 RD– 3 TD+ 4 5 6 TD– 7 8

RJ45

Crossover Cable

1 2 3 4 5 6 78

8-pin RJ45 Connector (8P8C)

RJ45

TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

RJ45

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

GRN/WHT GRN OR/WHT BLU BLU/WHT OR BRN/WHT BRN

1 2 3 4 5 6 7 8

TD+ TD– RD+ RD–

RJ45

DL205 User Manual, 4th Edition, Rev. D

4-21

Page 188

Chapter 4: System Design and Configuration

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Ethernet Base Controller, H2-EBC(100)(-F) The Ethernet Base Controller module H2-EBC(100)(-F) provides a low-cost, high-performance Ethernet link between a network master controller and an DirectLOGIC PLC I/O slave system. Also, the H2-EBC100 supports the Modbus TCP/IP client/server protocol. The Ethernet Base Controller (EBC) serves as an interface between the master control system and the DL205/405 I/O modules. The control function is performed by the master controller, not the EBC slave. The EBC occupies the CPU slot in the base and communicates across the backplane to input and output modules. Various master controllers with EBC slaves are shown in the diagram below. Example EBC Systems: Various Masters with EBC Slaves Modbus TCP/IP Masters (H2-EBC100 only)

PC-based Control System

OR

OR

All H2/H4 Series EBCs UDP/IP, IPX 10Mbps

Ethernet Hub

H2-EBC100 TCP/IP, UDP/IP, IPX Modbus TCP/IP 10/100Mbps

EBC Serial HMI EBC

EBC

The H2-EBC module supports industry standard 10BaseT Ethernet communications, the H2-EBC100 module supports industry standard 10/100BaseT Ethernet communications and the H2-EBC-F module supports 10BaseFL (fiber optic) Ethernet standards. H2-EBC

H2-EBC100

H2-EBC-F

Communications Data Transfer Rate Link Distance Ethernet Port

Specifications

10BaseT Ethernet

10/100BaseT Ethernet

10BaseFL Ethernet

10 Mbps max.

100 Mbps max.

10 Mbps max.

100m (328ft)

100m (328ft)

2000m (6560ft)

RJ45

ST-style fiber optic

Ethernet Protocols

TCP/IP, IPX

RJ45 TCP/IP, IPX/Modbus TCP/IP, DHCP, HTML configuration RJ12 K-Sequence, ASCII IN/OUT, Modbus RTU 300mA @ 5VDC

Serial Port Serial Protocols Power Consumption

4-22

DirectLOGIC PLC/ WinPLC with ERM

RJ12 K-Sequence, ASCII IN/ OUT 450mA @ 5VDC

DL205 User Manual, 4th Edition, Rev. D

TCP/IP, IPX None None 640mA @ 5VDC

Page 189

Chapter 4: System Design and Configuration

Install the EBC Module

1 2 3 • Module ID (IPX protocol only) • IP Address (for TCP/IP and Modbus TCP/IP protocols) 4 Set the Module ID The two methods which can be used to set the EBC module ID are either by DIP switch or 5 by software. One software method is to use the NetEdit3 program which is included with the EBC manual. To keep the set-up discussion simple here, only the DIP switch method will be 6 discussed. Refer to the EBC manual for the complete use of NetEdit3. It is recommended to use the DIP switch to set the Module ID because the DIP switch is simple 7 to set, and the Module ID can be determined by looking at the physical module, without reference to a software utility. 8 The DIP switch can be used to set the Module ID to a number from 1-63. Do not use Module ID 0 for communication. 9 If the DIP switch is set to a number greater than 0, the software utilities are disabled from setting the Module ID. Software utilities will only allow changes to the Module ID if the DIP 10 switch setting is 0 (all switches OFF). NOTE: The DIP switch settings are read at powerup only. The power must be cycled each time the DIP 11 switches are changed. Setting the Module ID with the DIP switches is identical to setting the DIP switches on the 12 H2-ERM(100) module. Refer to page 4-19 in this chapter. 13 Insert the EBC Module Once the Module ID DIP switches are set, insert the module in the CPU slot of any DL205 base. 14 A B C Insert H2-EBC in CPU slot D Like the ERM module discussed in the previous section, this section will briefly describe the installation of the H2 Series EBCs. More detailed information is available in the Ethernet Base Controller manual, H24-EBC-M, which will be needed to configure the remote I/O. Each EBC module must be assigned at least one unique identifier to make it possible for master controllers to recognize it on the network. Two methods for identifying the EBC module give it the flexibility to fit most networking schemes. These identifiers are:

DL205 User Manual, 4th Edition, Rev. D

4-23

Page 190

Chapter 4: System Design and Configuration

Network Cabling

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Of the two types of EBC modules available, one supports the 10/100BaseT standard and the other one supports the 10BaseFL standard. The 10/100BaseT standard uses twisted pairs of copper wire conductors and the 10BaseFL standard is used with fiber optic cabling. 10/100BaseT

RJ12 Serial Port RS232

ST-style Bayonet for 10BaseFL

RJ45 for 10/100BaseT

The 10BaseT and 100BaseT EBCs have an eight-pin modular jack that accepts RJ45 connectors. UTP Category 5 (CAT5) cable is highly recommended for use with all Ethernet 10/100BaseT connections. For convenient and reliable networking, purchase commercially manufactured cables which have the connectors already installed. To connect an EBC, or a PC, to a hub or repeater, use a patch cable (sometimes called a straight-through cable). The cable used to connect a PC directly to an EBC or to connect two hubs is referred to as a crossover cable. Patch (Straight–through) Cable

10/100BaseT

TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

1 RD+ 2 RD– 3 TD+ 4 5 6 TD– 7 8

RJ45

RJ45

Crossover Cable

1 2 3 4 5 6 78

8-pin RJ45 Connector (8P8C)

TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

RJ45

4-24

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

DL205 User Manual, 4th Edition, Rev. D

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

GRN/WHT GRN OR/WHT BLU BLU/WHT OR BRN/WHT BRN

1 2 3 4 5 6 7 8

TD+ TD– RD+ RD–

RJ45