Chapter 5: Standard RLL Instructions

Parallel Elements

1 2 3 4 5 6 Joining Series Branches in Parallel Quite often it is necessary to join several groups of series elements in parallel. The Or Store (ORSTR) instruction allows this operation. The following example shows a simple network 7 consisting of series elements joined in parallel. 8 9 10 Joining Parallel Branches in Series 11 You can also join one or more parallel branches in series. The And Store (ANDSTR) instruction allows this operation. The following example shows a simple network with contact branches 12 in series with parallel contacts. 13 14 A Combination Networks B You can combine the various types of series and parallel branches to solve most C any application problem. The following example shows a simple combination D network. You may also have to join contacts in parallel. The OR instruction allows you to do this. The following example shows two contacts in parallel and a single output coil. The instructions would be STR X0, OR X1, followed by OUT Y0. DirectSOFT Example

Handheld Mnemonics

X0

Y0

OUT

X1

STR X0 OR X1 OUT Y0 END

END

DirectSOFT Example

X0

Handheld Mnemonics

Y0

X1

OUT

X2

X3

END

DirectSOFT Example

X0

STR X0 AND X1 STR X2 AND X3 ORSTR OUT Y0 END

Handheld Mnemonics

Y0

X1

OUT

X2

STR X0 STR X1 OR X2 ANDSTR OUT Y0 END

END

X0

X2

X5

Y0

OUT

X1

X3

X4

X6

END

DL205 User Manual, 4th Edition, Rev. D

5-7

Page 232

Chapter 5: Standard RLL Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-8

Comparative Boolean The DL205 Micro PLCs provide Comparative Boolean instructions that allow you to quickly and easily solve compare two numbers. The Comparative Boolean provides evaluation of two 4-digit values using boolean contacts. The valid evaluations are: equal to, not equal to, equal to or greater than, and less than. In the example ,when the BCD value in V-memory location V1400 is equal to the constant value 1234, Y3 will energize. Y3 V1400 K1234 OUT

Boolean Stack

There are limits to how many elements you can include in a rung. This is because the DL205 CPUs use an 8-level boolean stack to evaluate the various logic elements. The boolean stack is a temporary storage area that solves the logic for the rung. Each time you enter a STR instruction, the instruction is placed on the top of the boolean stack. Any other STR instructions on the boolean stack are pushed down a level. The ANDSTR, and ORSTR instructions combine levels of the boolean stack when they are encountered. Since the boolean stack is only eight levels, an error will occur if the CPU encounters a rung that uses more than the eight levels of the boolean stack. The following example shows how the boolean stack is used to solve boolean logic. X0 STR

STR

STR

X1 ORSTR

AND X4

Y0 OUT

X2 AND

X5

X3

Output

ANDSTR

OR

STR X0

STR X1

STR X2

AND X3

1

1

STR X1

1

STR X2

1

STR X2

2

2

STR X0

2

STR X1

2

STR X1

3

3

3

STR X0

3

STR X0

4

4

4

STR X0

4

ORSTR

AND X4

1

X1 or (X2 AND X3)

1

X4 AND {X1 or (X2 AND X3)}

1

NOT X5 OR X4 AND {X1 OR (X2 AND X3)}

2

STR X0

2

STR X0

2

STR X0

3

3

ANDSTR 1

XO AND (NOT X5 or X4) AND {X1 or (X2 AND X3)}

2 3

DL205 User Manual, 4th Edition, Rev. D

ORNOT X5

3

Page 233

Chapter 5: Standard RLL Instructions

Immediate Boolean

1 2 3 4 NOTE: Even though the immediate input instruction reads the most current status from the input point, it only uses the results to solve that one instruction. It does not use the new status to update the image register. 5 Therefore, any regular instructions that follow will still use the image register values. Any immediate instructions that follow will access the I/O again to update the status. The immediate output instruction will 6 write the status to the I/O and update the image register. 7 8 9 CPU Scan 10 11 12 13 14 A B C D The DL205 Micro PLCs can usually complete an operation cycle in a matter of milliseconds. However, in some applications you may not be able to wait a few milliseconds until the next I/O update occurs. The DL205 PLCs offer immediate input and outputs which are special boolean instructions that allow reading directly from inputs and writing directly to outputs during the program execution portion of the CPU cycle. You may recall that this is normally done during the input or output update portion of the CPU cycle. The immediate instructions take longer to execute because the program execution is interrupted while the CPU reads or writes the I/O point. This function is not normally done until the read inputs or the write outputs portion of the CPU cycle.

X0 _ X7

X10 _ X17

X20 _ X27

X30 _ X37

Y0 _ Y7

Y10 _ Y17

Y20 _ Y27

Y30 _ Y37

Th e CPU reads the inputs from the local base and stores the status in an input image register .

Read Inputs

X128 OFF

... X2 X1 X0 ... ON OFF OFF Input Image Register

OFF

X0

OFF

X1

Read Inputs from Specialty I/O

Solve the Application Program X0 I

Y0

Immediate instruction does not use the input image register , but instead reads the status from the module I/O Point X0 Changes immediately. ON

X0

OFF

X1

Write Outputs

Write Outputs to Specialty I/O Diagnostics

DL205 User Manual, 4th Edition, Rev. D

5-9

Page 234

Chapter 5: Standard RLL Instructions

Boolean Instructions

1 Store (STR) The Store instruction begins a new rung or an additional 2 branch in a rung with a normally open contact. Status of the contact will be the same state as the associated image register point or memory location. 3 Store Not (STRN) 4 The Store Not instruction begins a new rung or an additional branch in a rung with a normally closed

5 contact. Status of the contact will be opposite the state of the associated image register point or memory location. 6 In the following 7 Operand Data Type DL230 Range DL240 Range DL250–1 Range DL260 Range A aaa aaa aaa aaa 8 9 10 11 12 Store example, when input X1 is on output Y2 will energize. 13 14 A B In the following Store Not example, when input X1 is off output Y2 will energize. C D 230

Aaaa

240

250-1 260

230

Aaaa

240

250-1 260

Inputs Outputs Control Relays Stage Timer Counter Special Relay Global Global

DS HPP

X Y C S T CT SP GX GY

0 – 177 0 – 177 0 – 377 0 – 377 0 – 77 0 – 77 0 – 117, 540 – 577 – –

0 – 477 0 – 477 0 – 377 0 – 777 0 – 177 0 – 177 0 – 137 540 – 617 – –

0 – 1777 0 – 1777 0 – 3777 0 – 1777 0 – 377 0 – 377 0 – 777 0 –3777 0 – 3777

Used Used

Handheld Programmer Keystrokes

DirectSOFT X1

Y2

OUT

X1

$

B

STR

GX OUT

C

1 2

ENT ENT

Handheld Programmer Keystrokes

DirectSOFT

Y2

OUT

5-10

0 – 777 0 – 777 0 – 1777 0 – 1777 0 – 377 0 – 177 0 – 777 – –

DL205 User Manual, 4th Edition, Rev. D

SP STRN

B

GX OUT

C

1 2

ENT ENT

Page 235

Chapter 5: Standard RLL Instructions

Store Bit-of-Word (STRB) 230 240 250-1 260 230 240 250-1 260

1 2 Store Not Bit-of-Word (STRNB) 3 The Store Not instruction begins a new rung or an additional branch in a rung with a normally closed 4 contact. Status of the contact will be opposite the state of the bit referenced in the associated memory location. 5 Operand Data Type DL250-1 Range DL260 Range A aaa bb aaa bb 6 7 In the following Store Bit-of-Word example, when bit 12 of V-memory location V1400 is on, 8 output Y2 will energize. 9 10 11 12 13 In the following Store Not Bit-of-Word example, when bit 12 of V-memory location V1400 14 is off, output Y2 will energize. A B C D The Store Bit-of-Word instruction begins a new rung or an additional branch in a rung with a normally open contact. Status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb memory map BCD, 0 to 15 See memory map BCD, 0 to 15 B See page 3-55 page 3-56

V-memory memory map BCD, 0 to 15 See memory map BCD, 0 to 15 PB See page 3-55 page 3-56

Pointer

DS HPP

Used Used

Aaaa.bb

DirectSOFT

B1400.12

Y2

OUT

Handheld Programmer Keystrokes STR

SHFT

B

K

1

2

2

ENT

OUT

V

1

4

0

0

4

0

0

ENT

DirectSOFT

B1400.12

Y2

OUT

Handheld Programmer Keystrokes STRN

OUT

SHFT

B

V

K

1

2

2

ENT

1

ENT

DL205 User Manual, 4th Edition, Rev. D

5-11

Page 236

Chapter 5: Standard RLL Instructions

1

2

3 4

5 6 7 8 9 10 11 12 13 14 A B C D

Or (OR) 230 240 250-1 260

The Or instruction logically ors a normally open contact in parallel with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

Aaaa

Or Not (ORN) 230 240 250-1 260

The Or Not instruction logically ors a normally closed contact in parallel with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location. Operand Data Type aaa aaa aaa aaa

0-177 0-177 0–377 0–377 0–77 0–77 0-117, 540-577 -

0-477 0-477 0–377 0–777 0–177 0–177 0-137, 540-617 -

0-777 0-777 0–1777 0–1777 0–377 0–177 0-137, 540-717 -

0-1777 0-1777 0–3777 0–1777 0–377 0–377 0-137, 540-717 0-3777 0-3777

In the following Or example, when input X1 or X2 is on, output Y5 will energize.

DS Implied HPP Used

5-12

DL230 Range DL240 Range DL250-1 Range DL260 Range A X Y C S T CT SP GX GY

Inputs Outputs Control Relays Stage Timer Counter Special Relay Global Global

Aaaa

Handheld Programmer Keystrokes

DirectSOFT X1

Y5 OUT

X2

$

STR

Q

OR

GX OUT

B C F

1 2 5

ENT ENT ENT

In the following Or Not example, when input X1 is on or X2 is off, output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

Y5 OUT

X2

DL205 User Manual, 4th Edition, Rev. D

$

STR

B

R ORN

C

GX OUT

F

1 2 5

ENT ENT ENT

Page 237

Chapter 5: Standard RLL Instructions

Or Bit-of-Word (ORB)

240 250-1 260 230

230 240 250-1 260

1 2 3 Or Not Bit-of-Word (ORNB) The Or Not Bit-of-Word instruction logically ors a 4 normally closed Bit-of-Word contact in parallel with another contact in a rung. Status of the contact will be opposite the state of the bit referenced in the associated 5 memory location. Operand Data Type DL250-1 Range DL260 Range 6 aaa bb bb 7 8 In the following Or Bit-of-Word example, when input X1 or bit 7 of V1400 is on, output Y7 9 will energize. 10 11 12 13 In the following Or Not Bit-of-Word example, when input X1 is on or bit 7 of V1400 is off, 14 output Y7 will energize. A B C D The Or Bit-of-Word instruction logically ors a normally open Bit-of-Word contact in parallel with another contact in a rung. Status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb

Aaaa.bb

A aaa See memory map See memory map BCD, 0 to 15 B BCD, 0 to 15 page 3-55 page 3-56 memory map BCD, 0 to 15 See memory map BCD, 0 to 15 PB See page 3-55 page 3-56

V-memory Pointer

DirectSOFT

DS HPP

X1

Implied

Y7

OUT

Used

B1400.7

Handheld Programmer Keystrokes STR OR

1

ENT

SHFT

B

K

7

ENT

7

ENT

OUT

V

1

4

0

V

1

4

0

0

DirectSOFT

X1

Y7

OUT

B1400.7

Handheld Programmer Keystrokes STR

ORN

OUT

1

ENT

SHFT

B

K

7

ENT

7

ENT

DL205 User Manual, 4th Edition, Rev. D

0

5-13

Page 238

Chapter 5: Standard RLL Instructions

1

2

3 4

5 6 7 8 9 10 11 12 13 14 A B C D

And (AND) 230 240 250-1 260

Aaaa

The AND instruction logically ands a normally open contact in series with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

And Not (ANDN) 230 240 250-1 260

Operand Data Type

DL230 Range DL240 Range A X Y C S T CT SP GX GY

Inputs Outputs Control Relays Stage Timer Counter Special Relay Global Global

DL250-1

DL260 Range aaa aaa aaa aaa

0–177 0–177 0–377 0–377 0–77 0–77 0-117, 540-577 -

0–477 0–477 0–377 0–777 0–177 0–177 0-137, 540-617 -

0–777 0–777 0–1777 0–1777 0–377 0–177 0-137, 540-717 -

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0-137, 540-717 0-3777 0-3777

In the following And example, when input X1 and X2 are on output Y5 will energize.

DS Implied HPP Used

5-14

Aaaa

The And Not instruction logically “ANDs” a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location.

Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5 OUT

$

STR

B

V AND

C

GX OUT

F

1 2 5

ENT ENT ENT

In the following And Not example, when input X1 is on and X2 is off output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5 OUT

DL205 User Manual, 4th Edition, Rev. D

$

STR

B

W ANDN

C

GX OUT

F

1 2 5

ENT ENT ENT

Page 239

Chapter 5: Standard RLL Instructions

AND Bit-of-Word (ANDB)

1 2 3 4 Operand Data Type DL250-1 Range DL260 Range aaa bb aaa bb 5 6 In the following And Bit-of-Word example, when input X1 and bit 4 of V1400 is on output 7 Y5 will energize. 8 9 10 11 12 In the following And Not Bit-of-Word example, when input X1 is on and bit 4 of V1400 is 13 off, output Y5 will energize. 14 A B C D

The And Bit-of-Word instruction logically ands a normally open contact in seriesAaaa.bb with another contact in a rung. The status of the contact will be the same state as the bit referenced in the 240

250-1 associated memory location. 260 And Not Bit-of-Word (ANDNB) 230 The And Not Bit-of-Word instruction logically ands a normally closed contact in series with Aaaa.bb 240 another contact in a rung. The status of the contact will be opposite the state of the bit 250-1 referenced in the associated memory location. 260 230

A

V-memory Pointer memory map B See page 3-55 memory map PB See page 3-55

BCD, 0 to 15 BCD

See memory map page 3-56 See memory map page 3-56

BCD, 0 to 15 BCD

DirectSOFT

DS Implied HPP Used

X1

B1400.4

Y5

OUT

Handheld Programmer Keystrokes STR

1

AND

ENT

SHFT

B

K

4

ENT

5

ENT

OUT

V

1

4

0

0

4

0

0

DirectSOFT X1

Y5

B1400.4

OUT

Handheld Programmer Keystrokes STR

ANDN

OUT

1

ENT

SHFT

B

K

4

ENT

V

5

ENT

1

DL205 User Manual, 4th Edition, Rev. D

5-15

Page 240

Chapter 5: Standard RLL Instructions

And Store (ANDSTR)

OUT The And Store instruction logically ands two branches 1 of a rung in series. Both branches must begin with 1 2 the Store instruction. 2

In the following And Store example, the branch consisting of contacts X2, X3, and X4 have 3 been anded with the branch consisting of contact X1. 4 5 6 7 8 9 (ORSTR) 1 10 Or Store OUT The Or Store instruction logically ors two branches of a rung in parallel. Both branches must begin with

2 the Store instruction. 11

12 In the following Or Store example, the branch consisting of X1 and X2 have been OR’d with the branch consisting of X3 and X4. 13 14 A B C D 230 240

250-1 260

DS Implied HPP Used

Handheld Programmer Keystrokes

DirectSOFT X1

X2

X3

Y5

OUT

X4

$ $

B

STR

C

STR

V AND

D

Q

E

OR

L ANDST

1

2 3 4

ENT ENT ENT ENT

ENT

GX OUT

F

5

ENT

230 240

250-1 260

DS Implied HPP Used

Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5

OUT

X3

X4

$

B

STR

V AND

C

$

D

STR

V AND

M ORST GX OUT

5-16

DL205 User Manual, 4th Edition, Rev. D

E

1

2

3

4

ENT ENT ENT ENT

ENT

F

5

ENT