Page 241

Chapter 5: Standard RLL Instructions

Out (OUT)

230 240 250-1 260

1 2 3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range 4 A aaa aaa aaa aaa 5 6 7 In the following Out example, when input X1 is on, output Y2 and Y5 will energize. 8 9 10 11 In the following Out example, the program contains two Out instructions using the same location (Y10). The physical output of Y10 is ultimately controlled by the last rung of logic referencing Y10. X1 will override the Y10 output being controlled by X0. To avoid this 12 situation, multiple outputs using the same location should not be used in programming. If you need to have an output controlled by multiple inputs, see the OROUT instruction on 13 page 5–19. 14 A B C D The Out instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified image register point or memory location. Multiple Out instructions referencing the same discrete location should not be used since only the last Out instruction in the program will control the physical output point. Instead, use the next instruction, the Or Out.

Inputs Outputs Control Relays Global Global

DS HPP

Used Used

X Y C GX GY

0–177 0–177 0–377 -

Aaaa OUT

0–477 0–477 0–377 -

0–777 0–777 0–1777 -

0–1777 0–1777 0–3777 0–3777 0–3777

Handheld Programmer Keystrokes

DirectSOFT X1

Y2

OUT Y5

OUT

X0

$

STR

B

GX OUT

C

GX OUT

F

1 2

5

ENT ENT ENT

Y10

OUT

X1

Y10

OUT

DL205 User Manual, 4th Edition, Rev. D

5-17

Page 242

Chapter 5: Standard RLL Instructions

1 2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Out Bit-of-Word (OUTB) 230 240 250-1 260

DS HPP

5-18

The Out Bit-of-Word instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified bit in the referenced memory location. Multiple Out Bit-of-Word instructions referencing the same bit of the same word generally should not be used since only the last Out instruction in the program will control the status of the bit. Operand Data Type

DL250-1 Range

V-memory bb aaa bb memory map B See page 3-55

BCD, 0 to 15

See memory map page 3-56 See memory map page 3-56

BCD, 0 to 15 memory map PB See page 3-55

Pointer

DL260 Range aaa

A

Used Used

Aaaa.bb OUT

BCD

BCD

In the following Out Bit-of-Word example, when input X1 is on, bit 3 of V1400 and bit 6 of V1401 will turn on. DirectSOFT X1

B1400.3 OUT B1401.6

Handheld Programmer Keystrokes

STR

1

OUT

SHFT K

3

OUT

SHFT

B

K

6

OUT ENT

B

V

1

4

0

0

V

1

4

0

1

ENT

ENT

The following Out Bit-of-Word example contains two Out Bit-of-Word instructions using the same bit in the same memory word. The final state bit 3 of V1400 is ultimately controlled by the last rung of logic referencing it. X1 will override the logic state controlled by X0. To avoid this situation, multiple outputs using the same location must not be used in programming. location must not be used in programming. X0

B1400.3 OUT

X1

B1400.3 OUT

DL205 User Manual, 4th Edition, Rev. D

Page 243

Chapter 5: Standard RLL Instructions

Or Out (OROUT)

230 240 250-1 260

1 2 3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa 4 5 6 In the following example, when X1 or X4 is on, Y2 will energize. 7 8 9 10 11 Not (NOT) 12 The Not instruction inverts the status of the rung at the point of the instruction. 13 In the following example, when X1 is off, Y2 will energize. This is because the Not instruction 14 inverts the status of the rung at the Not instruction. A B C D The Or Out instruction allows more than one rung of discrete logic to control a single output. Multiple Or Out instructions referencing the same output coil may be used, since all contacts controlling the output are logically OR’d together. If the status of any rung is on, the output will also be on.

Inputs Outputs Control Relays Global Global

DS HPP

Used Used

X Y C GX GY

0–177 0-177 0–377 -

0–477 0-477 0–377 -

Y2

$

OR OUT

$

Y2

230 240 250-1 260 DS HPP

Used Used

0–1777 0-1777 0–3777 0–3777 0–3777

F

3

E

D

F

3

1

5

4

5

ENT ENT

ENT

C

ENT

C

2

ENT

ENT ENT

2

ENT

Handheld Programmer Keystrokes

DirectSOFT X1

D

STR

O INST#

OR OUT

B

STR

O INST#

X4

0–777 0-777 0–1777 -

Handheld Programmer Keystrokes

DirectSOFT X1

A aaa OR OUT

Y2

OUT

$

B

STR

SHFT

GX OUT

N TMR

1

ENT

O INST#

T MLR

C

ENT

2

DL205 User Manual, 4th Edition, Rev. D

ENT

5-19

Page 244

Chapter 5: Standard RLL Instructions

1

2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Positive Differential (PD) The Positive Differential instruction is typically known as a one shot. When the input logic produces an off-to-on transition, the output will energize for one CPU scan.

230 240 250-1 260

Operand Data Type

Inputs Outputs Control Relays

DS HPP

5-20

A aaa PD

DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa

X Y C

0–177 0–177 0–377

0–477 0–477 0–377

0–777 0–777 0–1777

0–1777 0–1777 0–3777

In the following example, every time X1 makes an off to on transition, C0 will energize for one scan. Used Used Handheld Programmer Keystrokes

DirectSOFT X1

C0 PD

$

B

STR

SHFT

P

CV

1

SHFT

ENT D

3

A

0

ENT

NOTE: To generate a “one–shot” pulse on an on–to–off transition, place a NOT instruction immediately before the PD instruction. The DL250–1 and DL260 CPUs support the STRND instruction.

DL205 User Manual, 4th Edition, Rev. D

Page 245

Chapter 5: Standard RLL Instructions

Store Positive Differential (STRPD)

1 2 3 symbol inside the contact represents the transition). This function is sometimes called a “oneshot.” ‘This contact will also close on a program-to-run transition if it is within a retentive range 4 and on before the PLC mode transition. Store Negative Differential (STRND) 5 The Store Negative Differential instruction begins a new rung or an additional branch in a rung with a 6 contact. The contact closes for one CPU scan when the state of the associated image register point makes an on-to-off transition. Thereafter, the contact 7 remains open until the next on-to-off transition (the symbol inside the contact represents the transition). 8 Operand Data Type DL250-1 Range DL260 Range 9 aaa aaa 10 11 12 In the following example, each time X1 is makes an off-to-on transition, Y4 will energize for one scan. 13 14 A B In the following example, each time X1 makes an on-to-off transition, Y4 will energize for one scan. C D

Store Positive Differential instruction begins a 230 The new rung or an additional branch in a rung with a 240 contact. The contact closes for one CPU scan when 250-1 the state of the associated image register point makes off-to-on transition. Thereafter, the contact 260 an remains open until the next off-to-on transition (the

230 240 250-1 260

Aaaa

Inputs Outputs Control Relays Stage Timer Counter Global Global

DS HPP

Aaaa

A X Y C S T CT GX GY

0–777 0–777 0–1777 0–1777 0–377 0–177 – –

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0–3777 0–3777

Used Used

Handheld Programmer Keystrokes

DirectSOFT

X1

Y4

OUT

STR

SHFT

GX OUT

P

CV

E

4

D

3

B

1

ENT

ENT

Handheld Programmer Keystrokes

DirectSOFT

X1

$

Y4

OUT

$

STR

GX OUT

SHFT

N TMR E

4

D

3

B

1

ENT

ENT

DL205 User Manual, 4th Edition, Rev. D

5-21

Page 246

Chapter 5: Standard RLL Instructions

Or Positive Differential (ORPD)

The Or Positive Differential instruction logically ORs a 1 contact in parallel with another contact in a rung. The status of the contact will be open until the associated image register point makes an off-to-on transition, closing it for one CPU 2 scan. Thereafter, it remains open until another off-to-on transition. 3 Or Negative Differential (ORND) 4 The Or Negative Differential instruction logically ORs a contact in parallel with another contact in a rung. The status of the contact will be open until the associated image register 5 point makes an on-to-off transition, closing it for one CPU scan. Thereafter, it remains open until another on-to-off 6 transition. Operand Data Type DL250-1 Range DL260 Range 7 A aaa aaa 8 9 10 11 In the following example, Y5 will energize whenever X1 is on, or for one CPU scan when X2 transitions from off to on. 12 13 14 A In the following example, Y5 will energize whenever X1 is on, or for one CPU scan when X2 B transitions from on to off. C D 230

Aaaa

240

250-1 260

230

Aaaa

240

250-1 260

Inputs Outputs Control Relays Stage Timer Counter Global Global

X Y C S T CT GX GY

0–777 0–777 0–1777 0–1777 0–377 0–177 – –

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0–3777 0–3777

DS Implied HPP Used

Handheld Programmer Keystrokes

DirectSOFT X1

Y5

OUT

X2

Q

OR

SHFT

P

1

CV

F

5

ENT

D

3

C

2

ENT

ENT

Handheld Programmer Keystrokes

Y5

OUT

X2

5-22

B

STR

GX OUT

DirectSOFT X1

$

DL205 User Manual, 4th Edition, Rev. D

$

B

STR

Q

OR

GX OUT

SHFT

1

N TMR F

5

ENT

D

3

ENT

C

2

ENT

Page 247

Chapter 5: Standard RLL Instructions

And Positive Differential (ANDPD)

1 2 3 And Negative Differential (ANDND) 4 The And Negative Differential instruction logically ANDs a normally open contact in series with another contact 5-23in a rung. The status of the contact will 5 be open until the associated image register point makes an on-to-off transition, closing it for one CPU scan.

6 Thereafter, it remains open until another on-to-off transition.

Operand Data Type DL250-1 Range DL260 Range 7 A aaa aaa 8 9 10 11 In the following example, Y5 will energize for one CPU scan whenever X1 is on and X2 transitions from off to on. 12 13 14 A In the following example, Y5 will energize for one CPU scan whenever X1 is on and X2 B transitions from on to off. C D The And Positive Differential instruction logically ANDs

230 a normally open contact in series with another contact 240 in a rung. The status of the contact will be open until associated image register point makes an off-to-on 250-1 the transition, closing it for one CPU scan. Thereafter, it 260 remains open until another off-to-on transition.

Aaaa

Aaaa

230 240

250-1 260

Inputs Outputs Control Relays Stage Timer Counter Global Global

X Y C S T CT GX GY

0–777 0–777 0–1777 0–1777 0–377 0–177 – –

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0–3777 0–3777

DS Implied HPP Used

Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5

OUT

$

B

STR

V

AND

SHFT

1

CV

F

GX OUT

5

ENT

D

3

C

2

ENT

ENT

Handheld Programmer Keystrokes

DirectSOFT X1

P

X2

Y5

OUT

$

B

STR

V

AND

GX OUT

SHFT

1

N TMR F

5

ENT

D

3

C

2

ENT

ENT

DL205 User Manual, 4th Edition, Rev. D

5-23

Page 248

Chapter 5: Standard RLL Instructions

Set (SET)

Optional memory range A aaa aaa SET

The Set instruction sets or turns on an image register 1 point/memory location or a consecutive range of image register points/memory locations. Once the point/ location is set, it will remain on until it is reset using 2 the Reset instruction. It is not necessary for the input controlling the Set instruction to remain on. 3 Reset (RST) 4 The Reset instruction resets or turns off an image register point/memory location or a range of image registers points/memory locations. Once the point/location is 5 reset, it is not necessary for the input to remain on.

6 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range aaa aaa aaa aaa 7 8 9 10 11 NOTE: You cannot set inputs (Xs) that are assigned to input modules In the following example, when X1 is on, Y2 through Y5 will energize. 12 13 14 A In the following example, when X2 is on, Y2 through Y5 will be reset or de–energized. B C D 230 240

250-1 260

Optional Memory range . A aaa aaa RST

230 240

250-1 260

A Inputs X 0–177 0–477 Outputs Y 0-177 0-477 Control Relays C 0–377 0–377 Stage S 0-377 0-777 Timer* T 0-77 0-177 Counter * CT 0-77 0-177 Global GX Global GY * Timer and counter operand data types are not valid using the Set instruction

DS HPP

0–1777 0-1777 0–3777 0-1777 0-377 0-377 0–3777 0–3777

Used Used

Handheld Programmer Keystrokes

DirectSOFT X1

Y2

Y5

SET

X2

$

STR

X SET

B

C

1

ENT

F

2

5

ENT

Handheld Programmer Keystrokes

DirectSOFT

Y2

Y5

RST

5-24

0–777 0-777 0–1777 0-1777 0-377 0-177 -

DL205 User Manual, 4th Edition, Rev. D

$

STR

S RST

C C

2 2

ENT

F

5

ENT

Page 249

Chapter 5: Standard RLL Instructions

Set Bit-of-Word (SETB)

Aaaa.bb SET

230 The Set Bit-of-Word instruction sets or turns on a bit in a V-memory Once the bit is set, it will remain on until it is reset using 240 location. the Reset Bit-of-Word instruction. It is not necessary for the input 250-1 controlling the Set Bit-of-Word instruction to remain on. 260 Reset Bit-of-Word (RSTB) 230 240 250-1 260

Operand Data Type

DL250-1 Range

Used Used

DL260 Range

A aaa aaa bb bb B See memory map BCD, 0 to 15 See memory map BCD, 0 to 15 PB See memory map BCD See memory map BCD

V-memory Pointer

DS HPP

A aaa.bb RST

The Reset Bit-of-Word instruction resets or turns off a bit in a V-memory location. Once the bit is reset, it is not necessary for the input to remain on.

In the following example, when X1 turns on, bit 1 in V1400 is set to the on state. DirectSOFT X1

B1400.1 SET

Handheld Programmer Keystrokes STR

1

SET

SHFT

B

K

1

ENT V

1

4

0

0

ENT

In the following example, when X2 turns on, bit 1 in V1400 is reset to the off state. DirectSOFT X2

B1400.1 RST

Handheld Programmer Keystrokes STR RST

2 SHFT

B

K

1

ENT V

1

4

0

0

ENT

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5-25

Page 250

Chapter 5: Standard RLL Instructions

1

2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Pause (PAUSE) The Pause instruction disables the output update on a range of outputs. The ladder program will continue to run and update the image register; however, the outputs in the range specified in the Pause instruction will be turned off at the output points.

230 240 250-1 260

Operand Data Type

DL230 Range DL240 Range DL250-1 Range DL260 Range

Outputs

DS HPP

5-26

Y aaa aaa PAUSE

Y aaa aaa aaa aaa

0-177

0-477

0-777

0-1777

In the following example, when X1 is ON, Y5–Y7 will be turned OFF. The execution of the ladder program will not be affected. Used Used

DirectSOFT X1

Y5

Y7

PAUSE

Since the D2–HPP Handheld Programmer does not have a specific Pause key, you can use the corresponding instruction number for entry (#960) or type each letter of the command. Handheld Programmer Keystrokes $

B

STR

O INST#

J

9

G

1 6

ENT A

0

ENT

ENT

F

5

H

7

ENT

In some cases, you may want certain output points in the specified pause range to operate normally. In that case, use Aux 58 to override the Pause instruction.