The text of a manual · part 4 of 60
DL205 PLC User Manual, Volume 1 of 2, pages 31 to 40
Pages 31 to 40 of 598
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D2-04TD1, AutomationDirect D2-08TD2, AutomationDirect D2-16ND3-2, AutomationDirect D2-32ND3, Konnect-It D2-04TD1, Koyo D2-04TD1, Konnect-It D2-08TD2, Koyo D2-08TD2, and 5 more models
Page 31
Getting Started
Chapter
1
In This Chapter... Introduction. ..............................................................................1–2 Conventions Used.......................................................................1–3 DL205 System Components. ......................................................1–4 Programming Methods...............................................................1–7 DirectLOGIC™ Part Numbering System......................................1–8 Quick Start for PLC Validation and Programming. ......................1–10 Steps to Designing a Successful System......................................1–13
Page 32
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Introduction
1-2
The Purpose of this Manual Thank you for purchasing our DL205 family of products. This manual shows you how to install, program, and maintain the equipment. It also helps you understand how to interface them to other devices in a control system. This manual contains important information for personnel who will install DL205 PLCs and components and for the PLC programmer. If you understand PLC systems, our manuals will provide all the information you need to start and keep your system up and running.
Where to Begin If you already understand PLCs please read Chapter 2, “Installation, Wiring, and Specifications,” and proceed on to other chapters as needed. Keep this manual handy for reference when you have questions. If you are a new DL205 customer, we suggest you read this manual completely to understand the wide variety of features in the DL205 family of products. We believe you will be pleasantly surprised with how much you can accomplish with our products.
Supplemental Manuals If you have purchased operator interfaces or DirectSOFT, you will need to supplement this manual with the manuals that are written for those products.
Technical Support We strive to make our manuals the best in the industry. We rely on your feedback to let us know if we are reaching our goal. If you cannot find the solution to your particular application, or, if for any reason you need technical assistance, please call us at: 770–844–4200 Our technical support group will work with you to answer your questions. They are available Monday through Friday from 9:00 A.M. to 6:00 P.M. Eastern Time. We also encourage you to visit our web site where you can find technical and non-technical information about our products and our company. http://www.automationdirect.com If you have a comment, question or suggestion about any of our products, services, or manuals, please fill out and return the ‘Suggestions’ card included with this manual.
DL205 User Manual, 4th Edition, Rev. D
Page 33
Chapter 1: Getting Started
Conventions Used When you see the “notepad” icon in the left–hand margin, the paragraph to its immediate right will be a special note. The word NOTE in boldface will mark the beginning of the text. When you see the “exclamation mark” icon in the left–hand margin, the paragraph to its immediate right will be a warning. This information could prevent injury, loss of property, or even death (in extreme cases). The word WARNING in boldface will mark the beginning of the text.
Key Topics for Each Chapter The beginning of each chapter will list the key topics that can be found in that chapter.
Getting Started
CHAPTER
1
In This Chapter... General Information .................................................................1-2 Specifications...........................................................................1-4
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
1-3
Page 34
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DL205 System Components
1-4
The DL205 family is a versatile product line that provides a wide variety of features in an extremely compact package. The CPUs are small, but offer many instructions normally only found in larger, more expensive systems. The modular design also offers more flexibility in the fast moving industry of control systems. The following is a summary of the major DL205 system components.
CPUs This product line includes four feature-enhanced CPUs: the DL230, DL240, DL250–1 and DL260. All CPUs include built-in communication ports. Each CPU offers a large amount of program memory, a substantial instruction set and advanced diagnostics. The DL250–1 features drum timers, floating–point math, 4 built-in PID loops with automatic tuning and 2 bases of local expansion capability. The DL260 features ASCII IN/OUT and extended MODBUS communications, table and trigonometric instructions, 16 PID loops with autotuning and up to 4 bases of local expansion. Details of these CPU features and more are covered in Chapter 3, CPU Specifications and Operation.
Bases Four base sizes are available: 3, 4, 6 and 9 slot. The DL205 PLCs use bases that can be expanded. The part numbers for these bases end with –1. These bases have a connector for local expansion located on the right end of the base. They can serve in local, local expansion and remote I/O configurations. All bases include a built-in power supply. The bases with the –1 suffix can replace existing bases without a suffix if expansion is required.
I/O Configuration The DL230 and DL240 CPUs can support up to 256 local I/O points. The DL250–1 can support up to 768 local I/O points with up to two expansion bases. The DL260 can support up to 1280 local I/O points with up to four expansion bases. These points can be assigned as input or output points. The DL240, DL250–1 and DL260 systems can also be expanded by adding remote I/O points. The DL250–1 and DL260 provide a built–in master for remote I/O networks. The I/O configurations are explained in Chapter 4, System Design and Configuration. I/O Modules
I/O Modules The DL205 has some of the most powerful modules in the industry. A complete range of discrete modules which support 24 VDC, 110/220 VAC and up to 10A relay outputs (subject to derating) are offered. The analog modules provide 12- and 16-bit resolution and several selections of input and output signal ranges (including bipolar). Several specialty and communications modules are also available.
DL205 User Manual, 4th Edition, Rev. D
Page 35
Chapter 1: Getting Started
DL205 System Diagrams
Machine Control
Packaging Conveyors
Simple Motion Control
Elevators
Flexible solutions in one package High-speed counting (up to 100 KHz) Pulse train output (up to 50KHz High–speed Edge timing
Handheld Programmer DL240
DL260 with H2–CTRIO(2) High Speed I/O Module
Stepper Motor
Pulse Output
RS232C (max.50ft/16.2m) Programming or Computer Interface
Local I/O Expansion
Programming or Computer Interface
Simple programming through the RLL Program
Drive Amplifier
Networking
Operator Interface
DCM
Handheld Programmer RS232C (max.50ft/16.2m) DL240
DL250–1 or DL260
RS232C (max.50ft/16.2m)
(max. 6.5ft / 2m) DL305
RS232/422 Convertor
RS232/422 Convertor
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Getting Started
The diagram below shows the major components and configurations of the DL205 system. The next two pages show specific components for building your system.
1-5
Page 36
1–6
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1-6
Direct LOGIC DL205 Family DC INPUT 8pt 12–24 VDC 16pt 24 VDC 32pt 24 VDC 32pt 5–15 VDC DC OUTPUT 4pt 12–24 VDC 8pt 12–24 VDC 16pt 12–24 VDC 2 Commons 32pt 12–24 VDC 4 Commons
AC INPUT 8pt 110 VAC 16pt 110 VAC AC OUTPUT 8pt 18–220 VAC 12pt 18–110 VAC 2 commons
RELAY OUTPUT 4pt 5–30 VDC 5–240VAC 8pt 5–30 VDC 5 –240 VAC 12pt 5–30VDC 5–240VAC (isolated pts.module available)
CPUs DL230 – 2.0K Built-in EEPROM Memory DL240 – 2.5K Built-in EEPROM Memory DL250–1 – 7.6K Built-in Flash Memory DL260 – 15.8K Built-in Flash Memory BASES 3 Slot Base, 110/220VAC, 24VDC 4 Slot Base, 110/220VAC, 24VDC 6 Slot Base, 110/220VAC, 24VDC, 125 VDC 9 Slot Base, 110/220VAC, 24VDC, 125 VDC
SPECIALTY MODULES High Speed Counters CPU Slot Controllers Remote Masters Remote Slaves Communications Temperature Input Filler Module
PROGRAMMING Handheld Programmer with Built-in RLL PLUS Direct SOFT Programming for Windows
DL205 User Manual, 4th Edition, Rev. D
ANALOG 4CH INPUT 8CH INPUT 2CH OUTPUT 8CH OUTPUT 4 IN/2 OUT 8 IN/4 OUT
Page 37
Chapter 1: Getting Started
Programming Methods Two programming methods are available for the DL205 CPUs: Relay Ladder Logic (RLL) and RLLPLUS (Stage Programming). Both the DirectSOFT5 programming package and the handheld programmer support RLL and Stage.
DirectSOFT Programming for Windows The DL205 can be programmed with one of the most advanced programming packages in the industry ––DirectSOFT5. DirectSOFT5 is a Windows-based software package that supports many Windows features you already know, such as cut and paste between applications, point and click editing, viewing and editing multiple application programs at the same time, etc. DirectSOFT5 universally supports the DirectLOGIC CPU families. This means you can use the same DirectSOFT5 package to program DL05, DL06, DL105, DL205, DL305, DL405 or any new CPUs we may add to our product line. A separate manual discusses the DirectSOFT5 programming software which is included with your software package.
Handheld Programmer All DL205 CPUs have a built-in programming port for use with the handheld programmer (D2–HPP). The handheld programmer can be used to create, modify and debug your application program. A separate manual that discusses the DL205 Handheld Programmer is available.
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
1-7
Page 38
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DirectLOGIC™ Part Numbering System
1-8
As you examine this manual, you will notice there are many different products available. Sometimes it is difficult to remember the specifications for any given product. However, if you take a few minutes to understand the numbering system, it may save you some time and confusion. The charts below show how the part numbering systems work for each product category. Part numbers for accessory items such as cables, batteries, memory cartridges, etc, are typically an abbreviation of the description for the item. CPUs Specialty CPUs DL05/06 Product family DL105 Product family DL205 Product family DL305 Product family DL405 Product family
D0/F0 D1/F1 D2/F2 D3/F3 D4/F4
Class of CPU / Abbreviation
230...,330...,430...
Denotes a differentiation between similar modules
–1, –2, –3, –4
D4–
440DC
–1
D3–
05B
DC
D4–
16
N
D
2
D3–
16
N
D
2
Bases DL205 Product family DL305 Product family DL405 Product family
D2/F2 D3/F3 D4/F4
Number of slots Type of Base
##B DC or empty
Discrete I/O DL05/06 Product family DL205 Product family DL305 Product family DL405 Product family
D0/F0 D2/F2 D3/F3 D4/F4
Number of points
04/08/12/16/32/64
Input
N
Output
T
Combination AC
C A
DC
D
Either
E
Relay Current Sinking
R 1
Current Sourcing
2
Current Sinking/Sourcing High Current
3 H
Isolation
S
Fast I/O Denotes a differentiation between similar modules
F –1, –2, –3, –4
DL205 User Manual, 4th Edition, Rev. D
F –1
Page 39
Chapter 1: Getting Started
1–8
Analog I/O
F3–
DL05/06 Product family
D0/F0
DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family Number of channels
D4/F4 02/04/08/16
Input (Analog to Digital)
AD
Output (Digital to Analog)
DA
Combination Isolated Denotes a differentiation between Similar modules
AND S –1, –2, –3, –4
Communication and Networking Special I/O and Devices Programming DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family
D4/F4
Name Abbreviation see example
CoProcessors and ASCII BASIC Modules DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family
D4/F4
CoProcessor
CP
ASCII BASIC
AB
64K memory
64
128K memory
128
512K memory Radio modem
512 R
Telephone modem
T
04
AD
S
–1
Alternate example of Analog I/O using abbreviations F3–
08
THM
–n
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D note: –n indicates thermocouple type such as: J, K, T, R, S or E
D4–
DCM
DCM (Data Communication Module)
D3–
HSC
D3–
HPP
HSC (High Speed Counter) HPP (RLL PLUS Handheld Programmer)
F4–
CP
128
– R
DL205 User Manual, 4th Edition, Rev. D
1-9
Page 40
Chapter 1: Getting Started
Quick Start for PLC Validation and Programming
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1-10
If you have experience using PLCs, or want to set up a quick example, this section is what you want to use. This example is not intended to explain everything needed to start up your system. It is only intended to provide a general picture of what is needed to get your system powered up.
Step 1: Unpack the DL205 Equipment Unpack the DL205 equipment and verify you have the parts necessary to build this demonstration system. The minimum parts needed are as follows: • Base • CPU • discrete input module such as a D2–16ND3–2 DC or a F2–08SIM input simulator module • A discrete output module such as a D2–16TD1–2 DC • *Power cord • *Hook up wire • *One or more toggle switches (if not using the input simulator module) • *A screwdriver, blade or Phillips type *These items are not supplied with your PLC.
You will need at least one of the following programming options: •D irectSOFT5 Programming Software, DirectSOFT5 Manual, and a programming cable (connects the CPU to a personal computer), or • D2–HPP Handheld Programmer and the Handheld Programmer Manual.
DL205 User Manual, 4th Edition, Rev. D