Page 173
Standard RLL Instructions
15
In This Chapter. . . ., Introduction, Boolean Instructions, Comparative Boolean Instructions, Immediate Instructions, Timer, Counter, and Shift Register Instructions, Accumulator / Data Stack and Output Instructions, Accumulator Logic Instructions, Math Instructions, Bit Operation Instructions, Number Conversion Instructions, Table Instructions, Clock / Calender Instructions, CPU Control Instructions, Program Control Instructions, Interrupt Instructions, Intelligent I/O Instructions, Network Instructions, Message Instructions
Page 174
5--2
Standard RLL Instructions
Introduction The DL405 instruction set can perform many different types of operations. This chapter shows you how to use these individual instructions. The following table provides a quick reference listing of the instruction mnemonic and the page(s) defining the instruction. Each instruction definition will show in parentheses the HPP keystrokes used to enter the instruction. There are two ways to locate instructions:
S
If you know the instruction category (Boolean, Comparative Boolean, etc.), just use the header at the top of the page to find the pages that discuss the instructions in that category.
S
If you know the individual instruction mnemonic, use the following table.
The DL450 provides all of the instructions in the table, the DL440 provides a subset, and the DL430 a smaller subset. The instruction definitions indicate which CPUs feature the instruction. In Example 1, only the DL440 and DL450 have the instruction. In Example 2, all CPUs have the instruction.
Example 1
Example 2
430 440 450
430 440 450
If you are using a DL450 PLC (with firmware v3.30 or later) with DirectSOFT5 programming software, you can also use the IBox instructions covered in the DL405--IBOX--S Supplement.
Standard RLL Instructions
Instruction
Page
ACON
5--196
ACOSR
5--119
ADD
5--87
ADDB
5--99
ADDBD
5--100
ADDBS
5--113
ADDD
5--88
ADDF
5--105
ADDR
5--89
ADDS
5--109
AND
5--14, 5--31, 5--70
Instruction
Page
Instruction
Page
5--16, 5--118
DEGR
5--134
ASINR
5--118
DISI
5--186
ATANR
5--119
DIV
5--96
ATH
5--135
DIVB
5--104
ATT
5--159
DIVBS
5--116
BCALL
7--27
DIVD
5--97
BCD
5--129
DIVF
5--108
DIVR
5--98
DIVS
5--112
DLBL
5--196
DRUM
6--15
EDRUM
6--18
ENCO
5--126
END
5--177
ENI
5--186
FAULT
5--195
FDGT
5--144
FILL
5--142
FIND
5--143
ANDSTR
BCDCPL
5--131
BEND
7--27
BIN
5--128
BLK
7--27
ANDD
5--71
BREAK
5--178
ANDND
5--23
BTOR
5--132
ANDS
5--73
CMP
5--82
CMPD
5--83
CMPF
5--84
CMPR
5--86
CMPS
5--85
CNT
5--47
FINDB
5--173
COSR
5--118
FOR
5--180
CV
7--25
GOTO
5--179
5--15
CVJMP
7--25
GRAY
5--139
ANDNE
5--28
DATE
5--175
GTS
5--181
ANDNI
5--34
DEC
5--117
HISTRY
5--197
ANDPD
5--23
DECB
5--120
HTA
5--136
ANDS
5--73
DECO
5--127
INC
5--117
ANDSTR
5--16
ANDB
5--15
ANDD
5--71
ANDE
5--28
ANDF
5--72
ANDI
5--34
ANDMOV
5--171
ANDN
5--14, 5--31
ANDNB
DL405 User Manual, 4th Edition
Page 175
5--3
Standard RLL Instructions
Instruction
Page
Instruction
Page
Instruction
Page
INCB
5--120
ORND
5--22
SGCNT
5--49
INT
5--185
ORNE
5--27
SHFL
5--122
INV
5--130
ORNI
5--33
SHFR
5--123
IRT
5--186
OROUT
5--19
SINR
5--118
IRTC
5--186
OROUTI
5--35
SQRTR
5--119
ISG
7--24
ORPD
5--22
SR
5--53
JMP
7--24
ORS
5--77
STOP
5--177
LBL
5--179
ORSTR
5--16
STR
5--10, 5--29
LD
5--59
5--17, 5--65
5--11
5--61
OUT
STRB
LDA
5--59
5--18
5--26
LDD
OUTB
STRE
5--65
5--32
5--60
OUTD
STRI
LDF
5--37
5--66
5--10, 5--29
LDI
OUTF
STRN
5--35, 5--39
5--11
5--38
OUTI
STRNB
LDIF
STRND
5--21
LDLBL
5--162
STRNE
5--26
LDR
5--64
STRNI
5--32
LDSX
5--63
STRPD
5--21
LDX
5--62
STT
5--153
MDRMD
6--21
SUB
5--90
MDRMW
6--24
SUBB
5--101
MLR
SUBBD
5--102
SUBBS
5--114
SUBD
5--91
SUBF
5--106
SUBR
5--92
SUBS
5--110
SUM
5--121
SWAP
5--174
TANR
5--118
TIME
5--176
TMR
5--42
5--40
OUTL
5--68
OUTM
5--68
OUTX
5--67
PAUSE
5--20
PD
5--20
5--183
POP
5--69
MLS
5--183
5--201
MOV
5--146
RADR
5--134
MOVMC
5--162
RD
5--189
MUL
5--93
RFB
5--150
MULB
5--103
RFT
5--156
MULBS
5--115
ROTL
5--124
MULD
5--94
ROTR
5--125
MULF
5--107
RST
5--24
MULR
5--95
RSTB
5--25
MULS
5--111
RSTBIT
5--167
NCON
5--197
RSTI
5--36
NEXT
5--180
TMRA
5--44
RSTWT
5--178
NJMP
7--24
TMRAF
5--44
RT
5--181
NOP
5--177
TMRF
5--42
RTC
5--181
NOT
5--19
TSHFL
5--169
RTOB
5--133
OR
5--12, 5--30, 5--74
TSHFR
5--169
RX
5--191
TTD
5--147
5--13
SBR
5--181
UDC
5--51
5--75
SEG
5--138
WT
5--190
ORE
5--27
SET
5--24
WX
5--192
ORF
5--76
SETB
5--25
XOR
5--78
ORI
5--33
SETBIT
5--167
XORD
5--79
ORMOV
5--171
SETI
5--36
XORF
5--80
ORN
5--12, 5--30
SFLDGT
5--140
XORMOV
5--171
ORNB
5--13
SG
7--23
XORS
5--81
ORB ORD
DL405 User Manual, 4th Edition
Standard RLL Instructions
OUTIF
Page 176
5--4
Standard RLL Instructions Boolean Instructions
Using Boolean Instructions Do you ever wonder why so many PLC manufacturers always quote the scan time for a 1K boolean program? Most all programs utilize many Boolean instructions. These are typically very simple instructions designed to join input and output contacts in various series and parallel combinations. Our DirectSOFT software is a similar program; therefore, you don’t necessarily have to know the instruction mnemonics in order to develop your program. However, knowledge of mnemonics will be helpful whenever it becomes necessary to troubleshoot the program using a handheld programmer (HPP). Many of the instructions in this chapter are not program instructions used in DirectSOFT, but are implied. In other words, they are not actually keyboard commands, however, they can be seen in a Mnemonic View of the program once the DirectSOFT program has been developed and accepted (compiled). Each instruction listed in this chapter will have a box to indicate how the instruction is used with DirectSOFT and the HPP. The box will either contain IMP for implied, a for used or an for not used. The abbreviation, DS, or HPP will appear beneath the appropriate box as shown below. IMP DS
END Statement
HPP
DS
DL405 programs require an END statement (coil) as the last instruction. This tells the CPU this is the end of the program. Normally, any instructions placed after the END statement will not be executed. There are exceptions to this such as interrupt routines, etc. Chapter 5 discusses the instruction set in detail. X0
Y0
All programs must have and END statement
OUT END
Simple Rungs
You use a contact to start rungs that contain both contacts and coils. The boolean instruction that does this is called a Store or, STR instruction. The output point is represented by the Output or, OUT instruction. The following example shows how to enter a single contact and a single output coil. DirectSOFT Example X0
Handheld Mnemonics Y0
Standard RLL Instructions
OUT END
DL405 User Manual, 4th Edition
STR X0 OUT Y0 END
Page 177
Standard RLL Instructions Boolean Instructions Normally Closed Contact
5--5
Normally closed contacts are also very common. This is accomplished with the Store Not or, STRN instruction. The following example shows a simple rung with a normally closed contact. DirectSOFT Example
Handheld Mnemonics
X0
Y0 OUT
STRN X0 OUT Y0 END
END
Contacts in Series
Use the AND instruction to join two or more contacts in series. The following example shows two contacts in series and a single output coil. The instructions used would be STR X0, AND X1, followed by OUT Y0. DirectSOFT Example X0
Handheld Mnemonics
X1
Y0 OUT
STR X0 AND X1 OUT Y0 END
END
Midline Outputs
Sometimes it is necessary to use midline outputs to get additional outputs that are conditional on other contacts. The following example shows how you can use the AND instruction to continue a rung with more conditional outputs. DirectSOFT Example X0
Handheld Mnemonics
X1
Y0 OUT X2
Y1 OUT X3
Y2
STR X0 AND X1 OUT Y0 AND X2 OUT Y1 AND X3 OUT Y2 END
OUT
END
Standard RLL Instructions
DL405 User Manual, 4th Edition
Page 178
5--6
Standard RLL Instructions Boolean Instructions
Parallel Elements
You also have to join contacts in parallel. The OR instruction allows you to do this. The following example shows two contacts in parallel and a single output coil. The instructions would be STR X0, OR X1, followed by OUT Y0. DirectSOFT Example
X0
Y0 OUT
X1
Handheld Mnemonics STR X0 OR X1 OUT Y0 END
END
Joining Series Branches in Parallel
Quite often it is necessary to join several groups of series elements in parallel. The Or Store (ORSTR) instruction allows this operation. The following example shows a simple network consisting of series elements joined in parallel. DirectSOFT Example X0
X1
Handheld Mnemonics Y0 OUT
X2
X3 END
STR X0 AND X1 STR X2 AND X3 ORSTR OUT Y0 END
Quite often it is also necessary to join one or more parallel branches in series. The Joining Parallel Branches in Series And Store (ANDSTR) instruction allows this operation. The following example shows a simple network with contact branches in series with parallel contacts. DirectSOFT Example X0
X1
Handheld Mnemonics Y0 OUT
X2
Standard RLL Instructions
END
DL405 User Manual, 4th Edition
STR X0 STR X1 OR X2 ANDSTR OUT Y0 END
Page 179
5--7
Standard RLL Instructions Boolean Instructions Combination Networks
You can combine the various types of series and parallel branches to solve most any application problem. The following example shows a simple combination network. X0
X2
X5
Y0 OUT
X1
X3
X4
X6
END
Comparative Boolean
Handheld Mnemonics STR X0 OR X1 STR X2 STR X3 ANDN X4 ORSTR AND X5 ORN X6 ANDSTR OUT Y0
The Comparative Boolean evaluates two 4-digit BCD/hex values using boolean contacts. The valid evaluations are: equal to, not equal to, equal to or greater than, and less than. In the following example when the value in V-memory location V1400 is equal to the constant BCD value 1234, Y3 will energize.
V1400
K1234
Y3 OUT
Standard RLL Instructions
DL405 User Manual, 4th Edition
Page 180
5--8
Standard RLL Instructions Boolean Instructions
Boolean Stack
There are limits to how many elements you can include in a rung. This is because the DL405 CPUs use an 8-level boolean stack to evaluate the various logic elements. The boolean stack is a temporary storage area that solves the logic for the rung. Each time you enter a STR instruction, the instruction is placed on the top of the boolean stack. Any other STR instructions on the boolean stack are pushed down a level. The ANDSTR, and ORSTR instructions combine levels of the boolean stack when they are encountered. Since the boolean stack is only eight levels, an error will occur if the CPU encounters a rung that uses more than the eight levels of the boolean stack. All of you software programmers may be saying, “I use DirectSOFT, so I don’t need to know how the stack works.” Not quite true. Even though you can build the network with the graphic symbols, the limits of the CPU are still the same. If the stack limit is exceeded when the program is compiled, an error will occur. The following example shows how the boolean stack is used to solve boolean logic. X0
STR
STR
STR
X1
AND X4
ORSTR
Y0 OUT
X2 AND X3
X5
Output
ANDSTR
OR
STR X0
STR X1
STR X2
AND X3
1
1
STR X1
1
STR X2
1
X2 AND X3
2
2
STR X0
2
STR X1
2
STR X1
3
3
3
STR X0
3
STR X0
4
4
4
STR X0
4
ORSTR
AND X4
OR X5
1
X1 OR (X2 AND X3)
1
X4 AND [X1 OR (X2 AND X3)]
1
NOT X5 OR X4 AND [X1 OR (X2 AND X3)]
2
STR X0
2
STR X0
2
STR X0
3
3
ANDSTR 1
X0 AND (NOT X5 OR X4) AND [X1 OR (X2 AND X3)]
2
Standard RLL Instructions
3
DL405 User Manual, 4th Edition
3
Page 181
Standard RLL Instructions Boolean Instructions
5--9
Immediate Boolean The DL405 CPUs usually can complete an operation cycle in a matter of milliseconds. However, in some applications you may not be able to wait a few milliseconds until the next I/O update occurs. The DL405 CPUs offer Immediate input and outputs which are special boolean instructions that allow reading directly from inputs and writing directly to outputs during the program execution portion of the CPU cycle. You may recall this is normally done during the input or output update portion of the CPU cycle. The immediate instructions take longer to execute because the program execution is interrupted while the CPU reads or writes the module. This function is not normally done until the read inputs or the write outputs portion of the CPU cycle. NOTE: Even though the immediate input instruction reads the most current status from the module, it only uses the results to solve that one instruction. It does not use the new status to update the image register. Therefore, any regular instructions that follow will still use the image register values. Any immediate instructions that follow will access the module again to update the status. The immediate output instruction will write the status to the module and update the image register. 8pt Input
16pt Input
8pt Input
X0 -X07
X10 -X27
X30 -X37
8pt 8pt 16pt Output Output Output Y0 -Y07
Y10 -Y17
Y20 -Y37
CPU Scan Read Inputs X320 OFF
... X2 X1 X0 ... ON OFF OFF Input Image Register
The CPU reads the inputs from the local and expansion bases and stores the status in an input image register.
OFF
X0
OFF
X1
Read Inputs from Specialty I/O
Solve the Application Program X0 I
Y0
Immediate instruction does not use the input image register, but instead reads the status from the module immediately.
I/O Point X0 Changes X0 X1
Write Outputs Write Outputs to Specialty I/O Diagnostics
DL405 User Manual, 4th Edition
Standard RLL Instructions
ON OFF
Page 182
5--10
Standard RLL Instructions Boolean Instructions
Boolean Instructions Store (STR)
430 440 450
DS
HPP
Store Not (STRN)
430 440 450
DS
HPP
The Store instruction begins a new rung or an additional branch in a rung with a normally open contact. Status of the contact will be the same state as the associated image register point or memory location.
Aaaa
The Store Not instruction begins a new rung or an additional branch in a rung with a normally closed contact. Status of the contact will be opposite the state of the associated image register point or memory location.
Aaaa
Operand Data Type
DL430 Range
DL440 Range
A aaa aaa aaa
X
0--477
0--477
0--1777
Outputs
Y
0--477
0--477
0--1777
Control Relays
C
0--737
0--1777
0--3777
Stage
S
0--577
0--1777
0--1777
Timer
T
0--177
0--377
0--377
Inputs
DL450 Range
Counter
CT
0--177
0--177
0--377
Special Relay
SP
0--137, 320--617
0--137 320--717
0--137, 320--717
Global
GX
0--777
0--1777
0--2777
Global
GY
--
--
0--2777
In the following Store example, when input X1 is on, output Y2 will energize. Handheld Programmer Keystrokes
DirectSOFT X1
Y2
STR
X(IN)
1
OUT
OUT
Y(OUT)
2
Standard RLL Instructions
In the following Store Not example, when input X1 is off output Y2 will energize. Handheld Programmer Keystrokes
DirectSOFT X1
Y2 OUT
DL405 User Manual, 4th Edition
STR
NOT
X(IN)
OUT
Y(OUT)
2
1