Page 183

Standard RLL Instructions Boolean Instructions

Store Bit-of-Word (STRB)

430 440 450

DS

HPP

Store Not Bit-of-Word (STRNB)

430 440 450

DS

HPP

The Store Bit-of-Word instruction begins a new rung or an additional branch in a rung with a normally open contact. Status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb

The Store Not instruction begins a new rung or an additional branch in a rung with a normally closed contact. Status of the contact will be opposite the state of the bit referenced in the associated memory location.

Aaaa.bb

Operand Data Type

5--11

DL450 Range A aaa bb

V--memory

B

All (See p. 3--42)

BCD, 0 to 15

Pointer

PB

All (See p. 3--42)

BCD, 0 to 15

In the following Store Bit-of-Word example, when bit 12 of V-memory location V1400 is on, output Y2 will energize. DirectSOFT B1400.12

Y2 OUT

Handheld Programmer Keystrokes STR

SHFT

B

K(con)

1

2

OUT

Y(OUT)

2

SHFT

V

1

4

0

0

In the following Store Not Bit-of-Word example, when bit 12 of V-memory location V1400 is off, output Y2 will energize. DirectSOFT B1400.12

Y2 OUT

STR

STR

SHFT

K(con)

1

2

OUT

Y(OUT)

2

B

SHFT

V

1

4

0

0

DL405 User Manual, 4th Edition

Standard RLL Instructions

Handheld Programmer Keystrokes

Page 184

5--12

Standard RLL Instructions Boolean Instructions

Or (OR)

430 440 450 IMP

DS

HPP

Or Not (ORN)

430 440 450 IMP

DS

HPP

The Or instruction logically ors a normally open contact in parallel with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

Aaaa

The Or Not instruction logically ors a normally closed contact in parallel with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location.

Operand Data Type

DL430 Range

Aaaa

DL440 Range

DL450 Range

A aaa aaa aaa

X

0--477

0--477

0--1777

Outputs

Y

0--477

0--477

0--1777

Control Relays

C

0--737

0--1777

0--3777

Stage

S

0--577

0--1777

0--1777

Timer

T

0--177

0--377

0--377

Counter

CT

0--177

0--177

0--377

Special Relay

SP

0--137, 320--617

0--137 320--717

0--137, 320--717

Global

GX

0--777

0--1777

0--1777

Global

GY

--

--

0--1777

Inputs

In the following Or example, when input X1 or X2 is on, output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

Y5

STR

X(IN)

1

OUT

OR

X(IN)

2

OUT

Y(OUT)

5

X2

In the following Or Not example, when input X1 is on or X2 is off, output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT

Standard RLL Instructions

X1

Y5 OUT

X2

DL405 User Manual, 4th Edition

STR

X(IN)

1

OR

NOT

X(IN)

OUT

Y(OUT)

5

2

Page 185

Standard RLL Instructions Boolean Instructions

Or Bit-of-Word (ORB)

430 440 450 IMP

DS

HPP

Or Not Bit-of-Word (ORNB)

430 440 450 IMP

DS

HPP

The Or Bit-of-Word instruction logically ors a normally open contact in parallel with another contact in a rung. Status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb

The Or Not Bit-of-Word instruction logically ors a normally closed contact in parallel with another contact in a rung. Status of the contact will be opposite the state of the bit referenced in the associated memory location.

Operand Data Type

5--13

Aaaa.bb

DL450 Range A aaa bb

V--memory

B

All (See p. 3--42)

BCD, 0 to 15

Pointer

PB

All (See p. 3--42)

BCD

In the following Or Bit-of-Word example, when input X1 or bit 7 of V1400 is on, output Y5 will energize. DirectSOFT X1

Y7 OUT

B1400.7 Handheld Programmer Keystrokes STR

X(IN)

1

OR

SHFT

B

K(con)

7

OUT

Y(OUT)

SHFT

V

1

4

0

0

5

In the following Or Bit-of-Word example, when input X1 or bit 7 of V1400 is off, output Y5 will energize. DirectSOFT X1

Y7 OUT

Handheld Programmer Keystrokes STR

X(IN)

1 N

OR

SHFT

K(con)

7

OUT

Y(OUT)

B

SHFT

V

1

4

0

0

5

DL405 User Manual, 4th Edition

Standard RLL Instructions

B1400.7

Page 186

5--14

Standard RLL Instructions Boolean Instructions

And (AND)

430 440 450 IMP

DS

HPP

And Not (ANDN)

430 440 450 IMP

DS

HPP

The And instruction logically ands a normally open contact in series with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

Aaaa

The And Not Bit-of-Word instruction logically ands a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location. Operand Data Type

Aaaa

DL430 Range

DL440 Range

A aaa aaa

DL450 Range aaa

Inputs

X

0--477

0--477

0--1777

Outputs

Y

0--477

0--477

0--1777

Control Relays

C

0--737

0--1777

0--3777

Stage

S

0--577

0--1777

0--1777

Timer

T

0--177

0--377

0--377

Counter

CT

0--177

0--177

0--377

Special Relay

SP

0--137, 320--617

0--137 320--717

0--137, 320--717

Global

GX

0--777

0--1777

0--1777

Global

GY

--

--

0--1777

In the following And example, when inputs X1 and X2 are on output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5

STR

OUT

X(IN)

1

AND

X(IN)

2

OUT

Y(OUT)

5

In the following And Not example, when input X1 is on and X2 is off output Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

X2

Y5

Standard RLL Instructions

OUT

DL405 User Manual, 4th Edition

STR

X(IN)

1

AND

NOT

X(IN)

OUT

Y(OUT)

5

2

Page 187

Standard RLL Instructions Boolean Instructions

And Bit-of-Word (ANDB)

430 440 450 IMP

DS

HPP

And Not Bit-of-Word (ANDNB)

430 440 450 IMP

DS

HPP

The And Bit-of-Word instruction logically ands a normally open contact in series with another contact in a rung. The status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb

The And Not Bit-of-Word instruction logically ands a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of the bit referenced in the associated memory location.

Aaaa.bb

Operand Data Type

5--15

DL450 Range A aaa bb

V--memory

B

All (See p. 3--42)

BCD, 0 to 15

Pointer

PB

All (See p. 3--42)

BCD

In the following And Bit-of-Word example, when input X1 and bit 4 of V1400 is on output Y5 will energize. DirectSOFT X1

B1400.4

Y5 OUT

Handheld Programmer Keystrokes STR

X(IN)

1 B

AND

SHFT

K(con)

4

OUT

Y(OUT)

SHFT

V

1

4

0

0

5

In the following And Not Bit-of-Word example, when input X1 is on and bit 4 of V1400 is off output Y5 will energize. DirectSOFT X1

Y5

B1400.4

Handheld Programmer Keystrokes STR

X(IN)

1

AND

SHFT

N

K(con)

4

OUT

Y(OUT)

B

SHFT

V

1

4

0

0

5

DL405 User Manual, 4th Edition

Standard RLL Instructions

OUT

Page 188

5--16

Standard RLL Instructions Boolean Instructions

And Store (ANDSTR)

430 440 450 IMP

DS

HPP

Or Store (ORSTR)

430 440 450 IMP

DS

HPP

The And Store instruction logically ands two branches of a rung in series. Both branches must begin with the Store instruction.

OUT

The Or Store instruction logically ors two branches of a rung in parallel. Both branches must begin with the Store instruction.

OUT

In the following And Store example, the branch consisting of contacts X2, X3, and X4 have been ANDed with the branch consisting of contact X1. Handheld Programmer Keystrokes

DirectSOFT X1

X2

X3

Y5 OUT

X4

STR

X(IN)

1

STR

X(IN)

2

AND

X(IN)

3

OR

X(IN)

4

AND

STR

OUT

Y(OUT)

5

In the following Or Store example, the branch consisting of X1 and X2 have been ORed with the branch consisting of X3 and X4. Handheld Programmer Keystrokes

DirectSOFT X1

Standard RLL Instructions

X3

DL405 User Manual, 4th Edition

X2

X4

Y5

STR

X(IN)

1

OUT

AND

X(IN)

2

STR

X(IN)

3

AND

X(IN)

4

OR

STR

OUT

Y(OUT)

5

Page 189

Standard RLL Instructions Boolean Instructions

Out (OUT)

430 440 450

DS

HPP

The Out instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified image register point or memory location. Multiple Out instructions referencing the same discrete location should not be used since only the last Out instruction in the program will control the physical output point. Operand Data Type

DL430 Range

Aaaa OUT

DL440 Range

DL450 Range

A aaa bb bb

X

0--477

0--477

0--1777

Outputs

Y

0--477

0--477

0--1777

Control Relays

C

0--737

0--1777

0--3777

Global I/O

GX

0--777

0--1777

0--2777 (GX + GY)

Inputs

5--17

In the following Out example, when input X1 is on, output Y2 and Y5 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

Y2 OUT Y5

STR

X(IN)

1

OUT

Y(OUT)

2

OUT

Y(OUT)

5

OUT

In the following Out example the program contains two Out instructions using the same location (Y10). The physical output of Y10 is ultimately controlled by the last rung of logic referencing Y10. X1 will override the Y10 output being controlled by X0. To avoid this situation, multiple outputs using the same location should not be used in programming. X0

Y10 OUT

X1

Y10 OUT

Standard RLL Instructions

DL405 User Manual, 4th Edition

Page 190

5--18

Standard RLL Instructions Boolean Instructions

Out Bit-of-Word (OUTB)

430 440 450

DS

HPP

The Out Bit-of-Word instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified bit in the referenced memory location. Multiple Out Bit-of-Word instructions referencing the same bit of the same word generally should not be used since only the last Out instruction in the program will control the status of the bit. Operand Data Type

Aaaa.bb OUT

DL450 Range A aaa bb

V--memory

B

All (See p. 3--42)

BCD, 0 to 15

Pointer

PB

All (See p. 3--42)

BCD

In the following Out Bit-of-Word example, when input X1 is on, bit 3 of V1400 and bit 6 of V1401 will turn on. DirectSOFT X1

B1400.3 OUT B1401.6 OUT

Handheld Programmer Keystrokes STR

X(IN)

1

OUT

SHFT

B

SHFT

V

1

4

0

0

K(con)

3

OUT

SHFT

B

SHFT

V

1

4

0

1

K(con)

6

The following Out Bit-of-Word example contains two Out Bit-of-Word instructions using the same bit in the same memory word. The final state bit 3 of V1400 is ultimately controlled by the last rung of logic referencing it. X1 will override the logic state controlled by X0. To avoid this situation, multiple outputs using the same location must not be used in programming. X0

V1400

K3

Standard RLL Instructions

OUT

X1

V1400

K3 OUT

DL405 User Manual, 4th Edition

Page 191

Standard RLL Instructions Boolean Instructions

Or Out (OROUT)

430 440 450

DS

HPP

The Or Out instruction has been designed to use more than 1 rung of discrete logic to control a single output. Multiple Or Out instructions referencing the same output coil may be used, since all contacts controlling the output are ORed together. If the status of any rung is on, the output will also be on. Operand Data Type

DL430 Range

A aaa OROUT

DL440 Range

DL450 Range

A aaa aaa aaa

X

0--477

0--477

0--1777

Outputs

Y

0--477

0--477

0--1777

Control Relays

C

0--737

0--1777

0--3777

Global I/O

GX

0--777

0--1777

0--2777 (GX + GY)

Inputs

5--19

In the following example, when X1 or X4 is on, Y2 will energize. Handheld Programmer Keystrokes

DirectSOFT X1

Y2 OR OUT

X4

STR

X(IN)

1

OR

OUT

Y(OUT)

STR

X(IN)

4

OR

OUT

Y(OUT)

2

2

Y2 OR OUT

Not (NOT)

The Not instruction inverts the status of the rung at the point of the instruction.

430 440 450

DS

HPP

In the following example when X1 is off, Y2 will energize. This is because the Not instruction inverts the status of the rung at the Not instruction. Handheld Programmer Keystrokes

DirectSOFT X1

Y2 OUT

X(IN)

1

N

O

OUT

Y(OUT)

2

T

NOTE: DirectSOFT Release 1.1i and later supports the use of the NOT instruction. The above example rung is merely intended to show the visual representation of the NOT instruction. The rung cannot be created or displayed in DirectSOFT versions earlier than 1.1i.

DL405 User Manual, 4th Edition

Standard RLL Instructions

STR SHFT

Page 192

5--20

Standard RLL Instructions Boolean Instructions

Pause (PAUSE)

430 440 450

DS

HPP

The Pause instruction disables the output update on a range of outputs. The ladder program will continue to run and update the image register however the outputs in the range specified in the Pause instruction will be turned off at the output module. Operand Data Type

Outputs

Y aaa aaa PAUSE

DL430 Range

DL440 Range

A aaa aaa

DL450 Range aaa

Y

0--477

0--477

0--1777

In the following example, when X1 is ON, Y10--Y17 will be turned OFF at the output module. The execution of the ladder program will not be affected. DirectSOFT

Handheld Programmer Keystrokes

X1

Y10

Y17

PAUSE

Positive Differential (PD)

430 440 450

DS

HPP

STR

X(IN)

1

SHFT

P

A

U

SHFT

Y(OUT)

1

0

Y(OUT)

1

7

S

The Positive Differential instruction is typically known as a one-shot. When the input logic produces an Off-to-On transition, the output will energize for one CPU scan. Thereafter, it remains off until its input makes another Off-to-On transition. Operand Data Type

DL430 Range

A aaa PD

DL440 Range

DL450 Range

A aaa aaa aaa

X

0--477

0--477

0--1777

Outputs

Y

0--477

0--477

0--1777

Control Relays

C

0--737

0--1777

0--3777

Inputs

E

Standard RLL Instructions

In the following example, every time X1 is makes an Off-to-On transition, C0 will energize for one scan. Handheld Programmer Keystrokes

DirectSOFT X1

C0 PD

STR

X(IN)

1

SHFT

P

D

SHFT

C(CR)

0

Note that you can place a “NOT” instruction immediately before the PD instruction to generate a “one-shot” pulse on an on-to-off transition.

DL405 User Manual, 4th Edition