Page 193
Standard RLL Instructions Boolean Instructions
Store Positive Differential (STRPD)
430 440 450
DS
HPP
Store Negative Differential (STRND)
430 440 450
DS
HPP
The Store Positive Differential instruction begins a new rung or an additional branch in a rung with a normally open contact. The contact closes for one CPU scan when the state of the associated image register point makes an Off-to-On transition. Thereafter, the contact remains open until the next Off-to-On transition (the symbol inside the contact represents the transition). This function is sometimes called a “one-shot”.
Aaaa
The Store Negative Differential instruction begins a new rung or an additional branch in a rung with a normally closed contact. The contact closes for one CPU scan when the state of the associated image register point makes an On-to-Off transition. Thereafter, the contact remains open until the next On-to-Off transition (the symbol inside the contact represents the transition). Operand Data Type
5--21
Aaaa
DL450 Range A aaa
Inputs
X
0--1777
Outputs
Y
0--1777
Control Relays
C
0--3777
Stage
S
0--1777
Timer
T
0--377
Counter
CT
0--377
Global
GX
0--2777 (GX + GY)
In the following example, each time X1 is makes an Off-to-On transition, Y4 will energize for one scan. DirectSOFT X1
Handheld Programmer Keystrokes Y4 OUT
STR
SHFT
X(IN)
1
OUT
Y(OUT)
P
D
SHFT
4
DirectSOFT X1
Handheld Programmer Keystrokes Y4 OUT
STR
SHFT
X(IN)
1
OUT
Y(OUT)
N
D
SHFT
4
DL405 User Manual, 4th Edition
Standard RLL Instructions
In the following example, each time X1 is makes an On-to-Off transition, Y4 will energize for one scan.
Page 194
5--22
Standard RLL Instructions Boolean Instructions
Or Positive Differential (ORPD)
430 440 450 IMP
DS
HPP
Or Negative Differential (ORND)
430 440 450 IMP
DS
HPP
The Or Positive Differential instruction logically ors a normally open contact in parallel with another contact in a rung. The status of the contact will be open until the associated image register point makes an Off-to-On transition, closing it for one CPU scan. Thereafter, it remains open until another Off-to-On transition.
Aaaa
The Or Negative Differential instruction logically ors a normally open contact in parallel with another contact in a rung. The status of the contact will be open until the associated image register point makes an On-to-Off transition, closing it for one CPU scan. Thereafter, it remains open until another On-to-Off transition. Operand Data Type
DL450 Range A aaa
X
0--1777
Outputs
Y
0--1777
Control Relays
C
0--3777
Stage
S
0--1777
Timer
T
0--377
Counter
CT
0--377
Global
GX
0--2777 (GX + GY)
Inputs
Aaaa
In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2 transitions from Off to On. Handheld Programmer Keystrokes
DirectSOFT X1
Y5
STR
X(IN)
1
OUT
OR
SHFT
P
X2
X(IN)
2
OUT
Y(OUT)
D
SHFT
5
In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2 transitions from On to Off. DirectSOFT X1
Handheld Programmer Keystrokes Y5
Standard RLL Instructions
OUT X2
DL405 User Manual, 4th Edition
STR
X(IN)
1
OR
SHFT
N
X(IN)
2
OUT
Y(OUT)
5
D
SHFT
Page 195
5--23
Standard RLL Instructions Boolean Instructions
And Positive Differential (ANDPD)
430 440 450 IMP
DS
HPP
And Negative Differential (ANDND)
430 440 450 IMP
DS
HPP
The And Positive Differential instruction logically ands a normally open contact in series with another contact in a rung. The status of the contact will be open until the associated image register point makes an Off-to-On transition, closing it for one CPU scan. Thereafter, it remains open until another Off-to-On transition.
Aaaa
The And Negative Differential instruction logically ands a normally open contact in series with another contact in a rung. The status of the contact will be open until the associated image register point makes an On-to-Off transition, closing it for one CPU scan. Thereafter, it remains open until another On-to-Off transition. Operand Data Type
Aaaa
DL450 Range A aaa
X
0--1777
Outputs
Y
0--1777
Control Relays
C
0--3777
Stage
S
0--1777
Timer
T
0--377
Counter
CT
0--377
Global
GX
0--2777 (GX + GY)
Inputs
In the following example, Y5 will energize for one CPU scan whenever X1 is on and X2 transitions from Off to On. DirectSOFT X1
Handheld Programmer Keystrokes X2
Y5 OUT
STR
X(IN)
1
AND
SHFT
P
X(IN)
2
OUT
Y(OUT)
D
SHFT
5
In the following example, Y5 will energize for one CPU scan whenever X1 is on and X2 transitions from On to Off. DirectSOFT X1
Handheld Programmer Keystrokes X2
Y5
STR
X(IN)
1
AND
SHFT
N
X(IN)
2
OUT
Y(OUT)
D
SHFT
5
DL405 User Manual, 4th Edition
Standard RLL Instructions
OUT
Page 196
5--24
Standard RLL Instructions Boolean Instructions
Set (SET)
430 440 450
DS
HPP
Reset (RST)
430 440 450
DS
HPP
The Set instruction sets or turns on an image register point/memory location or a consecutive range of image register points/memory locations. Once the point/location is set it will remain on until it is reset using the Reset instruction. It is not necessary for the input controlling the Set instruction to remain on.
Optional memory range
A aaa aaa SET
The Reset instruction resets or turns off an image register point/memory location or a range of image registers points/memory locations. Once the point/location is reset it is not necessary for the input to remain on.
Operand Data Type
Optional memory range
A aaa aaa RST
DL430 Range
DL440 Range
A aaa aaa
DL450 Range aaa
Inputs
X
0--477
0--477
0--1777
Outputs
Y
0--477
0--477
0--1777
Control Relays
C
0--737
0--1777
0--3777
Stages
S
0--577
0--1777
0--1777
Timers*
T
0--177
0--377
0--377
Counters*
CT
0--177
0--177
0--377
Global
GX
0--777
0--1777
0--2777 (GX + GY)
* Timer and counter operand data types are not valid using the Set instruction.
In the following example when X1 turns on, Y5 through Y22 will be set to the on state. DirectSOFT X1
Y5
Y22 SET
Handheld Programmer Keystrokes STR
X(IN)
1
SET
Y(OUT)
5
Y(OUT)
2
2
In the following example when X1 turns on, Y5 through Y22 will be reset to the off state. DirectSOFT
Standard RLL Instructions
X1
Y5
Y22 RST
Handheld Programmer Keystrokes
DL405 User Manual, 4th Edition
STR
X(IN)
1
RST
Y(OUT)
5
Y(OUT)
2
2
Page 197
Standard RLL Instructions Boolean Instructions
Set Bit-of-Word (SETB)
430 440 450
DS
HPP
Reset Bit-of-Word (RSTB)
430 440 450
DS
HPP
The Set Bit-of-Word instruction sets or turns on a bit in a V--memory location. Once the bit is set it will remain on until it is reset using the Reset Bit-of-Word instruction. It is not necessary for the input controlling the Set Bit-of-Word instruction to remain on.
Aaaa.bb SET
The Reset Bit-of-Word instruction resets or turns off a bit in a V--memory location. Once the bit is reset it is not necessary for the input to remain on.
Operand Data Type
5--25
A aaa.bb RST
DL450 Range A aaa bb
V--memory
B
All (See p. 3--42)
0 to 15
Pointer
PB
All (See p. 3--42)
0 to 15
In the following example when X1 turns on, bit 0 in V1400 is set to the on state. DirectSOFT X1
B1400.0 SET
Handheld Programmer Keystrokes STR
X(IN)
1
SET
SHFT
B
K(con)
0
SHFT
V
1
4
0
0
In the following example when X1 turns on, bit 15 in V1400 is reset to the off state. DirectSOFT X1
V1400.15 RST
Handheld Programmer Keystrokes X(IN)
1
RST
SHFT
B
K(con)
1
5
SHFT
V
1
4
0
0
DL405 User Manual, 4th Edition
Standard RLL Instructions
STR
Page 198
5--26
Standard RLL Instructions Comparative Boolean Instructions
Comparative Boolean Instructions The Store If Equal instruction begins a new rung or additional branch in a rung with a normally open comparative contact. The contact will be on when Aaaa = Bbbb.
Store If Equal (STRE)
430 440 450
DS
HPP
The Store If Not Equal instruction begins a new rung or additional branch in a rung with a normally closed comparative contact. The contact will be on when Aaaa ¸ Bbbb.
Store If Not Equal (STRNE)
430 440 450
DS
HPP
Operand Data Type
DL430 Range
A aaa
B bbb
A aaa
B bbb
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
In the following example, when the value in V--memory location V1400 = 4933 , Y3 will energize. DirectSOFT V1400
Y3
K4933
OUT
Handheld Programmer Keystrokes STR
SHFT
E
SHFT
V
K(CON)
4
9
3
3
OUT
Y(OUT)
3
1
4
0
0
In the following example, when the value in V--memory location V1400 ¸ 5060, Y3 will energize. Standard RLL Instructions
DirectSOFT V1400
Y3
K5060
OUT
Handheld Programmer Keystrokes STR
DL405 User Manual, 4th Edition
NOT
SHFT
E
SHFT
K(CON)
5
0
6
0
OUT
Y(OUT)
3
V
1
4
0
0
Page 199
5--27
Standard RLL Instructions Comparative Boolean Instructions
The Or If Equal instruction connects a normally open comparative contact in parallel with another contact. The contact will be on when Aaaa = Bbbb.
Or If Equal (ORE)
430 440 450 IMP
DS
HPP
The Or If Not Equal instruction connects a normally closed comparative contact in parallel with another contact. The contact will be on when Aaaa ¸ Bbbb.
Or If Not Equal (ORNE)
430 440 450 IMP
DS
HPP Operand Data Type
DL430 Range
A aaa
B bbb
A aaa
B bbb
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
In the following example, when the value in V--memory location V1400 = 4500 or V1402 = 2345 , Y3 will energize. DirectSOFT V1400
K4500
Y3 OUT
V1402
K2345
Handheld Programmer Keystrokes STR
SHFT
E
SHFT
V
K(CON)
4
5
0
0
OR
SHFT
E
SHFT
V
K(CON)
2
3
4
5
OUT
Y(OUT)
3
1
4
0
0
1
4
0
2
In the following example, when the value in V--memory location V1400 = 3916 or V1402 ¸ 2500, Y3 will energize. DirectSOFT V1400
K3916
Y3 OUT
V1402
K2500
STR
SHFT
E
SHFT
V
K(CON)
3
9
1
6
OR
NOT
SHFT
E
SHFT
K(CON)
2
5
0
0
OUT
Y(OUT)
3
1
4
0
0
V
1
4
0
2
DL405 User Manual, 4th Edition
Standard RLL Instructions
Handheld Programmer Keystrokes
Page 200
5--28
Standard RLL Instructions Comparative Boolean Instructions
The And If Equal instruction connects a normally open comparative contact in series with another contact. The contact will be on when Aaaa = Bbbb.
And If Equal (ANDE)
430 440 450 IMP
DS
HPP
The And If Not Equal instruction connects a normally closed comparative contact in series with another contact. The contact will be on when Aaaa ¸ Bbbb
And If Not Equal (ANDNE)
430 440 450 IMP
DS
HPP Operand Data Type
DL430 Range
A aaa
B bbb
A aaa
B bbb
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
In the following example, when the value in V--memory location V1400 = 5000 and V1402 = 2345, Y3 will energize. DirectSOFT V1400
K5000
V1402
K2345
Y3 OUT
Handheld Programmer Keystrokes STR
SHFT
E
SHFT
V
K(CON)
5
0
0
0
AND
SHFT
E
SHFT
V
K(CON)
2
3
4
5
OUT
Y(OUT)
3
1
4
0
0
1
4
0
2
In the following example, when the value in V--memory location V1400 = 2550 and V1402 ¸ 2500, Y3 will energize. DirectSOFT V1400
K2550
V1402
Y3
K2500
Standard RLL Instructions
OUT
Handheld Programmer Keystrokes
DL405 User Manual, 4th Edition
STR
SHFT
E
SHFT
V
K(CON)
2
5
5
0
AND
NOT
SHFT
E
SHFT
K(CON)
2
5
0
0
OUT
Y(OUT)
3
1
4
0
0
V
1
4
0
2
Page 201
5--29
Standard RLL Instructions Comparative Boolean Instructions
Store (STR)
430 440 450
DS
HPP
Store Not (STRN)
430 440 450
DS
HPP
The Comparative Store instruction begins a new rung or additional branch in a rung with a normally open comparative contact. The contact will be on when Aaaa ² Bbbb.
A aaa
B bbb
The Comparative Store Not instruction begins a new rung or additional branch in a rung with a normally closed comparative contact. The contact will be on when Aaaa < Bbbb.
A aaa
B bbb
Operand Data Type
DL430 Range
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
Timer
T
0--177
0--377
0--377
Counter
CT
0--177
0--177
0--377
In the following example, when the value in V--memory location V1400 ² 1000, Y3 will energize. DirectSOFT V1400
Y3
K1000
OUT
Handheld Programmer Keystrokes STR
V
1
4
0
K(CON)
1
0
0
0
OUT
Y(OUT)
3
0
In the following example, when the value in V--memory location V1400 < 4050, Y3 will energize. DirectSOFT V1400
K4050
Y3
Handheld Programmer Keystrokes STR
NOT
V
1
4
K(CON)
4
0
5
0
OUT
Y(OUT)
3
0
0
DL405 User Manual, 4th Edition
Standard RLL Instructions
OUT
Page 202
5--30
Standard RLL Instructions Comparative Boolean Instructions
The Comparative Or instruction connects a normally open comparative contact in parallel with another contact. The contact will be on when Aaaa ² Bbbb.
Or (OR)
430 440 450 IMP
DS
HPP
430 440 450
DS
HPP
B bbb
A aaa
B bbb
The Comparative Or Not instruction connects a normally open comparative contact in parallel with another contact. The contact will be on when Aaaa < Bbbb.
Or Not (ORN)
IMP
A aaa
Operand Data Type
DL430 Range
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
Timer
T
0--177
0--377
0--377
Counter
CT
0--177
0--177
0--377
In the following example, when the value in V--memory location V1400 = 6045 or V1402 ² 2345, Y3 will energize. Handheld Programmer Keystrokes
DirectSOFT V1400
Y3
K6045
OUT
V1402
K2345
STR
SHFT
E
SHFT
V
K(CON)
6
0
4
5
OR
V
1
4
0
K(CON)
2
3
4
5
OUT
Y(OUT)
3
1
4
0
0
2
In the following example when the value in V--memory location V1400 = 1000 or V1402 < 2500, Y3 will energize. Handheld Programmer Keystrokes
DirectSOFT V1400
K1000
Y3
Standard RLL Instructions
OUT
V1402
K2500
DL405 User Manual, 4th Edition
STR
SHFT
E
SHFT
V
K(CON)
1
0
0
0
OR
NOT
V
1
4
K(CON)
2
5
0
0
OUT
Y(OUT)
3
1
4
0
2
0
0