Page 203
5--31
Standard RLL Instructions Comparative Boolean Instructions
The Comparative And instruction connects a normally open comparative contact in series with another contact. The contact will be on when Aaaa ² Bbbb.
And (AND)
430 440 450 IMP
DS
HPP
The Comparative And Not instruction connects a normally open comparative contact in series with another contact. The contact will be on when Aaaa < Bbbb.
And Not (ANDN)
430 440 450 IMP
DS
HPP Operand Data Type
DL430 Range
A aaa
B bbb
A aaa
B bbb
DL440 Range
DL450 Range
A/B aaa bbb aaa bbb aaa bbb
V--memory
V
All (See p. 3--40)
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Pointer
P
----
----
All (See p. 3--41)
All (See p. 3--41)
All (See p. 3--42)
All (See p. 3--42)
Constant
K
----
0--FFFF
----
0--FFFF
----
0--FFFF
Timer
T
0--177
0--377
0--377
Counter
CT
0--177
0--177
0--377
In the following example, when the value in V-memory location V1400 = 5000, and V1402 ² 2345, Y3 will energize. DirectSOFT V1400
K5000
V1402
K2345
Y3 OUT
Handheld Programmer Keystrokes STR
SHFT
E
SHFT
V
K(CON)
5
0
0
0
AND
V
1
4
0
K(CON)
2
3
4
5
OUT
Y(OUT)
3
1
4
0
0
2
In the following example, when the value in V-memory location V1400 = 7000 and V1402 < 2500, Y3 will energize. DirectSOFT V1400
K7000
V1402
K2500
Y3
Handheld Programmer Keystrokes STR
SHFT
E
SHFT
V
K(CON)
7
0
0
0
AND
NOT
V
1
4
K(CON)
2
5
0
0
OUT
Y(OUT)
3
1
4
0
2
0
0
DL405 User Manual, 4th Edition
Standard RLL Instructions
OUT
Page 204
5--32
Standard RLL Instructions Immediate Instructions
Immediate Instructions Store Immediate (STRI)
430 440 450
DS
HPP
Store Not Immediate (STRNI)
430 440 450
DS
HPP
The Store Immediate instruction begins a new rung or additional branch in a rung. The status of the contact will be the same as the status of the associated input point on the module at the time the instruction is executed. The image register is not updated.
X aaa
The Store Not Immediate instruction begins a new rung or additional branch in a rung. The status of the contact will be opposite the status of the associated input point on the module at the time the instruction is executed. The image register is not updated.
X aaa
Operand Data Type
Inputs
X
DL430 Range
DL440 Range aaa aaa
DL450 Range aaa
0--477
0--477
0--1777
In the following example, when X1 is on, Y2 will energize. DirectSOFT Y2
X1
OUT
Handheld Programmer Keystrokes STR
SHFT
I
OUT
Y(OUT)
2
SHFT
X(IN)
1
In the following example when X1 is off, Y2 will energize. DirectSOFT Y2
X1
OUT
Standard RLL Instructions
Handheld Programmer Keystrokes
DL405 User Manual, 4th Edition
STR
NOT
SHFT
OUT
Y(OUT)
2
I
SHFT
X(IN)
1
Page 205
Standard RLL Instructions Immediate Instructions
Or Immediate (ORI)
430 440 450 IMP
DS
HPP
Or Not Immediate (ORNI)
430 440 450 IMP
DS
HPP
The Or Immediate connects two contacts in parallel. The status of the contact will be the same as the status of the associated input point on the module at the time the instruction is executed. The image register is not updated.
X aaa
The Or Not Immediate connects two contacts in parallel. The status of the contact will be opposite the status of the associated input point on the module at the time the instruction is executed. The image register is not updated.
Operand Data Type
Inputs
X
5--33
X aaa
DL430 Range
DL440 Range
DL450 Range aaa aaa aaa
0--477
0--477
0--1777
In the following example, when X1 or X2 is on, Y5 will energize. DirectSOFT Y5
X1
OUT X2
Handheld Programmer Keystrokes STR
X(IN)
1
OR
SHFT
I
OUT
Y(OUT)
5
SHFT
X(IN)
2
In the following example, when X1 is on or X2 is off, Y5 will energize. DirectSOFT Y5
X1
OUT
Handheld Programmer Keystrokes STR
X(IN)
1
OR
NOT
SHFT
OUT
Y(OUT)
5
I
SHFT
X(IN)
2
DL405 User Manual, 4th Edition
Standard RLL Instructions
X2
Page 206
5--34
Standard RLL Instructions Immediate Instructions
The And Immediate connects two contacts in series. The status of the contact will be the same as the status of the associated input point on the module at the time the instruction is executed. The image register is not updated.
X aaa
And Not Immediate The And Not Immediate connects two contacts in series. The status of the contact (ANDNI) will be opposite the status of the associated input point on the module at the 430 440 450 time the instruction is executed. The image IMP register is not updated. HPP
X aaa
And Immediate (ANDI)
430 440 450 IMP
DS
HPP
DS
Operand Data Type
DL430 Range
Inputs
X
DL440 Range
DL450 Range aaa aaa aaa
0--477
0--477
0--1777
In the following example, when X1 and X2 is on, Y5 will energize. DirectSOFT X1
Y5
X2
OUT
Handheld Programmer Keystrokes STR
X(IN)
1
AND
SHFT
I
OUT
Y(OUT)
5
SHFT
X(IN)
2
In the following example, when X1 is on and X2 is off, Y5 will energize. DirectSOFT X1
Y5
X2
OUT
Standard RLL Instructions
Handheld Programmer Keystrokes
DL405 User Manual, 4th Edition
STR
X(IN)
1
AND
NOT
SHFT
OUT
Y(OUT)
5
I
SHFT
X(IN)
2
Page 207
Standard RLL Instructions Immediate Instructions
Out Immediate (OUTI)
430 440 450
DS
HPP
Or Out Immediate (OROUTI)
430 440 450
DS
HPP
The Out Immediate instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) status to the specified module output point and the image register at the time the instruction is executed. If multiple Out Immediate instructions referencing the same discrete point are used it is possible for the module output status to change multiple times in a CPU scan. See Or Out Immediate.
Y aaa OUTI
The Or Out Immediate instruction has been designed to use more than 1 rung of discrete logic to control a single output. Multiple Or Out Immediate instructions referencing the same output coil may be used, since all contacts controlling the output are ored together. If the status of any rung is on at the time the instruction is executed, the output will also be on. Operand Data Type
Outputs
Y
5--35
Y aaa OROUTI
DL430 Range
DL440 Range aaa aaa
DL450 Range aaa
0--477
0--477
0--1777
In the following example, when X1 is on, output point Y2 on the output module will turn on. DirectSOFT Y2
X1
OUTI
Handheld Programmer Keystrokes STR
X(IN)
1
OUT
SHFT
I
SHFT
Y(OUT)
2
In the following example, when X1 or X4 is on, Y2 will energize. DirectSOFT Y2
X1
OR OUTI
OR OUTI
Handheld Programmer Keystrokes STR
X(IN)
1
OR
OUT
SHFT
STR
X(IN)
4
OR
OUT
SHFT
I
SHFT
Y(OUT)
2
I
SHFT
Y(OUT)
2
DL405 User Manual, 4th Edition
Standard RLL Instructions
Y2
X4
Page 208
5--36
Standard RLL Instructions Immediate Instructions
Set Immediate (SETI)
430 440 450
DS
HPP
Reset Immediate (RSTI)
430 440 450
DS
HPP
The Set Immediate instruction immediately sets or turns on an output or a range of outputs and the corresponding output module(s) at the time the instruction is executed. The image register is not updated. Once the outputs are set it is not necessary for the input to remain on. The Reset Immediate instruction can be used to reset the outputs.
Y aaa aaa SETI
The Reset Immediate instruction immediately resets, or turns off an output or a range of outputs and the output module(s) at the time the instruction is executed. The image register is not updated. Once the outputs are reset it is not necessary for the input to remain on. Operand Data Type
Outputs
Y aaa aaa RSTI
DL430 Range
DL440 Range
DL450 Range aaa aaa aaa
0--477
0--477
0--1777
Y
In the following example, when X1 is on, Y5 through Y22 will be set (on) for the corresponding output module(s). DirectSOFT X1
Y5
Y22 SETI
Handheld Programmer Keystrokes STR
X(IN)
1
SET
SHFT
I
SHFT
Y(OUT)
5
Y(OUT)
2
2
In the following example, when X1 is on, Y5 through Y22 will be reset (off) for the corresponding output module(s). DirectSOFT X1
Y22
Y5
Standard RLL Instructions
RSTI
Handheld Programmer Keystrokes
DL405 User Manual, 4th Edition
STR
X(IN)
1
RST
SHFT
I
SHFT
Y(OUT)
5
Y(OUT)
2
2
Page 209
5--37
Standard RLL Instructions Immediate Instructions
The Load Immediate instruction loads a 16-bit V-memory value into the accumulator. The valid address range includes all input point addresses on the local base. The value reflects the current status of the input points at the time the instruction is executed. This instruction may be used instead of the LDIF instruction which requires you to specify the number of input points.
Load Immediate (LDI)
430 440 450
DS
HPP
Operand Data Type
LDI V aaa
DL450 Range aaaaa
Inputs
V
40400 -- 40477
In the following example, when C0 is on, the binary pattern of X10--X17 will be loaded into the accumulator using the Load Immediate instruction. The Out Immediate instruction could be used to copy the 16 bits in the accumulator to output points, such as Y40--Y57. This technique is useful to quickly copy an input pattern to output points (without waiting on a full CPU scan to occur). DirectSOFT C0
Location
LDI
X17 X16 X15 X14 X13 X12 X11 X10 X7
V40400
V40400 Load the inputs from X0 to X17 into the accumulator, immediately.
X6
X5
X4
X3
X2
X1
X0
ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero
Acc.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6 5
4 3
2
1
0
0
0
1
0
1
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
1
0
1
0
1
0
OUTI V40502 Output the value in the accumulator to output points Y40 to Y57.
Location
Y57 Y56 Y55 Y54 Y53 Y52 Y51 Y50 Y47 Y46 Y45 Y44 Y43 Y42 Y41 Y40
V40502
ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
Handheld Programmer Keystrokes STR
C(CR)
0
LD
SHFT
I
SHFT
V
4
0
4
0
0
OUT
SHFT
I
SHFT
V
4
0
5
4
0
Standard RLL Instructions
DL405 User Manual, 4th Edition
Page 210
5--38
Standard RLL Instructions Immediate Instructions
The Load Immediate Formatted instruction loads a 1--32 bit binary value into the accumulator. The value reflects the current status of the input module(s) at the time the instruction is executed. Accumulator bits that are not used by the instruction are set to zero.
Load Immediate Formatted (LDIF)
430 440 450
DS
HPP
Operand Data Type
X aaa
LDIF K bbb
DL440 Range
DL450 Range aaa bbb aaa bbb
Inputs
X
0--477
----
0--1777
----
Constant
K
----
1--32
----
1--32
In the following example, when C0 is on, the binary pattern of X10--X17 will be loaded into the accumulator using the Load Immediate Formatted instruction. The Out Immediate Formatted instruction could be used to copy the specified number of bits in the accumulator to the specified outputs on the output module, such as Y30--Y37. This technique is useful to quickly copy an input pattern to outputs (without waiting for the CPU scan). DirectSOFT C0
LDIF
X10 K8
Load the value of 8 consecutive location into the accumulator starting with X10
Constant K8
X17 X16 X15 X14 X13 X12 X11 X10 ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6 5
4 3
2
1
0
0
0
1
0
1
1
0
1
Acc.
OUTIF
Location X10
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
Y30 K8
Copy the value of the lower 8 bits of the accumulator to Y30 --Y37
Location
Constant
Y37 Y36 Y35 Y34 Y33 Y32 Y31 Y30
Y30
K8
ON OFF ON ON OFF ON OFF ON
Handheld Programmer Keystrokes C(CR)
0
LD
SHFT
I
F
SHFT
X(IN)
1
0
K(CON)
8
OUT
SHFT
I
F
SHFT
Y(OUT)
3
0
K(CON)
8
Standard RLL Instructions
STR
DL405 User Manual, 4th Edition
Page 211
5--39
Standard RLL Instructions Immediate Instructions
The Out Immediate instruction outputs a 16-bit binary value from the accumulator to a V-memory address at the time the instruction is executed. The valid address range includes all output point addresses on the local base. This instruction may be used instead of the OUTIF instruction which requires you to specify the number of input points.
Out Immediate (OUTI)
430 440 450
DS
HPP
Operand Data Type
OUTI V aaaaa
DL450 Range aaaaa
Inputs
V
40400 -- 40477
In the following example, when C0 is on, the binary pattern of X10--X17 will be loaded into the accumulator using the Load Immediate instruction. The Out Immediate instruction could be used to copy the 16 bits in the accumulator to output points, such as Y40--Y57. This technique is useful to quickly copy an input pattern to outputs (without waiting for the CPU scan). DirectSOFT C0
Location
LDI
X17 X16 X15 X14 X13 X12 X11 X10 X7
V40400
V40400 Load the inputs from X0 to X17 into the accumulator, immediately.
X6
X5
X4
X3
X2
X1
X0
ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero
Acc.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6 5
4 3
2
1
0
0
0
1
0
1
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
1
0
1
0
1
0
OUTI V40542 Output the value in the accumulator to output points Y40 to Y57.
Location
Y57 Y56 Y55 Y54 Y53 Y52 Y51 Y50 Y47 Y46 Y45 Y44 Y43 Y42 Y41 Y40
V40542
ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
Handheld Programmer Keystrokes STR
C(CR)
0
LD
SHFT
I
SHFT
V
4
0
4
0
0
OUT
SHFT
I
SHFT
V
4
0
5
4
0
Standard RLL Instructions
DL405 User Manual, 4th Edition
Page 212
5--40
Standard RLL Instructions Immediate Instructions
The Out Immediate Formatted instruction outputs a 1--32 bit binary value from the accumulator to specified output points at the time the instruction is executed. Accumulator bits that are not used by the instruction are set to zero.
Out Immediate Formatted (OUTIF)
430 440 450
DS
HPP
Operand Data Type
Y aaa OUTIF K bbb
DL440 Range
DL450 Range aaa bbb aaa bbb
Output
Y
0--477
----
0--1777
----
Constant
K
----
1--32
----
1--32
In the following example when C0 is on,the binary pattern for X10 --X17 is loaded into the accumulator using the Load Immediate Formatted instruction. The binary pattern in the accumulator is written to Y30--Y37 using the Out Immediate Formatted instruction. This technique is useful to quickly copy an input pattern to outputs (without waiting for the CPU scan). DirectSOFT C0
LDIF
X10 K8
Load the value of 8 consecutive location into the accumulator starting with X10
Constant K8
X17 X16 X15 X14 X13 X12 X11 X10 ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6 5
4 3
2
1
0
0
0
1
0
1
1
0
1
Acc.
OUTIF
Location X10
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
Y30 K8
Copy the value in the lower 8 bits of the accumulator to Y30 --Y37
Location
Constant
Y37 Y36 Y35 Y34 Y33 Y32 Y31 Y30
Y30
K8
ON OFF ON ON OFF ON OFF ON
Handheld Programmer Keystrokes C(CR)
0
LD
SHFT
I
F
SHFT
X(IN)
1
0
K(CON)
8
OUT
SHFT
I
F
SHFT
Y(OUT)
3
0
K(CON)
8
Standard RLL Instructions
STR
DL405 User Manual, 4th Edition