The text of a manual · part 9 of 68
DL405 User Manual: Chapter 2: Installation, Wiring,and Specifications, pages 57 to 66
Pages 57 to 66 of 608, from DL405 User Manual
The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models
Page 57
Installation , Wiring, and Specifications
2--21
Connecting DC I/O In the previous section on Sourcing and Sinking concepts, we explained that DC I/O circuits sometimes will only allow current to flow one way. This is also true for many of to “Solid State” the field devices which have solid-state (transistor) interfaces. In other words, field Field Devices devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking. Solid State Several DL405 DC input modules are flexible in that they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a Input Sensors field device has an open-collector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the +24 auxiliary supply or another supply (+12 VDC or +24VDC), as long as the input specifications are met. Installation, Wiring, and Specifications
Field Device
PLC DC Input Input (sourcing)
Output (sinking) Supply Ground
--
+
Common
In the next circuit, a field device has an open-emitter PNP transistor output. It sources current to the PLC input point, which sinks the current back to ground. Since the field device is sourcing current, no additional power supply is required. Field Device +V
PLC DC Input Input Output (sourcing) Ground
Common
Sometimes an application requires connecting a PLC output point to a solid state input on a device. This type of connection is usually made to carry a low-level control signal, not to send DC power to an actuator. Several of the DL405 DC output modules are the sinking type. This means that each DC output provides a path to ground when it is energized. In the following circuit, the PLC output point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. PLC DC Sinking Output Power +DC pwr
Field Device +V
Output (sinking)
+
Common
--
Input (sourcing) 10--30 VDC Ground
DL405 User Manual, 4th Edition
Installation and Safety Guidelines
Solid State Output Loads
(sinking)
Page 58
2--22
Installation, Wiring, and Specifications In the next example we connect a PLC sinking DC output point to the sinking input of a field device. This is a bit tricky, because both the PLC output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, we add sourcing capability to the PLC output by using a pull-up resistor. In the circuit below, we connect Rpull-up from the output to the DC output circuit power input. PLC DC Output +DC pwr
Power Field Device
R pull-up
(sourcing)
Installation, Wiring, and Specifications
(sinking)
Output Supply Common
+
Input (sinking)
--
Ground
R input
NOTE 1: DO NOT attempt to drive a heavy load (>25 mA) with this pull-up method NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the PLC output is OFF, from a ladder logic point-of-view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device. It is important to choose the correct value of R pull-up. In order to do so, we need to know the nominal input current to the field device (I input) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use I input and the voltage of the external supply to compute R pull-up. Then calculate the power Ppull-up (in watts), in order to size R pull-up properly.
Installation and Safety Guidelines
I input
=
R pull-up =
V input (turn--on) R input V supply -- 0.7 I input
-- R input
P pull-up =
2 V supply R pullup
Of course, the easiest way to drive a sinking input field device as shown below is to use a DC sourcing output module. The Darlington NPN stage will have about 1.5 V ON-state saturation, but this is not a problem with low-current solid-state loads. PLC DC Sourcing Output +DC pwr
Common Field Device Output (sourcing) Supply
DL405 User Manual, 4th Edition
+
Input (sinking)
--
Ground
R input
Page 59
Installation , Wiring, and Specifications
Relay Output Guidelines
2--23
Four output modules in the DL405 I/O family feature relay outputs: D4--08TR, F4--08TRS--1, F4--08TRS--2, D4--16TR. Relays are best for the following applications: • • •
Loads that require higher currents than the solid-state outputs can deliver Cost-sensitive applications Some output channels need isolation from other outputs (such as when some loads require different voltages than other loads)
• S
Loads that require currents under 10 mA Loads which must be switched at high speed or heavy duty cycle Relay with Form A contacts
Relay with Form C contacts
Surge Suppression Inductive load devices (devices with a coil) generate transient voltages when de-energized with a relay contact. When a relay contact is closed it “bounces”, which For Inductive energizes and de-energizes the coil until the “bouncing” stops. The transient Loads voltages generated are much larger in amplitude than the supply voltage, especially with a DC supply voltage. When switching a DC-supplied inductive load the full supply voltage is always present when the relay contact opens (or “bounces”). When switching an AC-supplied inductive load there is one chance in 60 (60 Hz) or 50 (50 Hz) that the relay contact will open (or “bounce”) when the AC sine wave is zero crossing. If the voltage is not zero when the relay contact opens there is energy stored in the inductor that is released when the voltage to the inductor is suddenly removed. This release of energy is the cause of the transient voltages.
DL405 User Manual, 4th Edition
Installation and Safety Guidelines
Relay outputs in the DL405 output modules are available in two contact arrangements, shown to the right. The Form A type, or SPST (single pole, single throw) type is normally open and is the simplest to use. The Form C type, or SPDT (single pole, double throw) type has a center contact which moves and a stationary contact on either side. This provides a normally closed contact and a normally open contact. Some relay output module’s relays share common terminals, which connect to the wiper contact in each relay of the bank. Other relay modules have relays which are completely isolated from each other. In all cases, the module drives the relay coil when the corresponding output point is on.
Installation, Wiring, and Specifications
Some applications in which NOT to use relays:
Page 60
2--24
Installation, Wiring, and Specifications
When inductive load devices (motors, motor starters, interposing relays, solenoids, valves, etc.) are controlled with relay contacts, it is recommended that a surge suppression device be connected directly across the coil of the field device. If the inductive device has plug-type connectors, the suppression device can be installed on the terminal block of the relay output.
Installation, Wiring, and Specifications
Transient Voltage Suppressors (TVS or transorb) provide the best surge and transient suppression of AC and DC powered coils, providing the fastest response with the smallest overshoot. Metal Oxide Varistors (MOV) provide the next best surge and transient suppression of AC and DC powered coils. For example, the waveform in the figure below shows the energy released when opening a contact switching a 24 VDC solenoid. Notice the large voltage spike. +24 VDC
--24 VDC
+24 VDC
Module Relay Contact --324 VDC
Installation and Safety Guidelines
This figure shows the same circuit with a transorb (TVS) across the coil. Notice that the voltage spike is significantly reduced. +24 VDC +24 VDC --42 VDC Module Relay Contact
DL405 User Manual, 4th Edition
--24 VDC
Page 61
Installation , Wiring, and Specifications
2--25
Use the following table to help select a TVS or MOV suppressor for your application based on the inductive load voltage. Type (TVS, MOV, Diode)
Inductive Load Voltage
Part Number
AutomationDirect
TVS TVS
110/120 VAC 24VDC
ZL--TD8--120 ZL--TD8--24
TVS
220/240 VAC
P6KE350CA
TVS
12/24 VDC or VAC
Diode
12/24 VDC
Contact Digi--Key, Corp.
MOV MOV
110/120 VAC 220/240 VAC
Transient Voltage Suppressors, LiteOn Diodes; from DigiKey Catalog; Phone: 1-800-344-4539 Digi--Key www.digikey.com
Prolonging Relay Contact Life
Contact Digi--Key, Corp.
Inductive Field Device
PLC Relay Output
Input
Output Supply Common
+
--
Common
DL405 User Manual, 4th Edition
Installation and Safety Guidelines
Relay contacts wear according to the amount of relay switching, amount of spark created at the time of open or closure, and presence of airborne contaminants. There are some steps you can take to help prolong the life of relay contacts, such as switching the relay on or off only when it is necessary, and if possible, switching the load on or off at a time when it will draw the least current. Also, take measures to suppress inductive voltage spikes from inductive DC loads such as contactors and solenoids. For inductive loads in DC circuits we recommend using a suppression diode as shown in the following diagram (DO NOT use this circuit with an AC power supply). When the load is energized the diode is reverse-biased (high impedance). When the load is turned off, energy stored in its coil is released in the form of a negative-going voltage spike. At this moment the diode is forward-biased (low impedance) and shunts the energy to ground. This protects the relay contacts from the high voltage arc that would occur just as the contacts are opening. Place the diode as close to the inductive field device as possible. Use a diode with a peak inverse voltage rating (PIV) at least 100 PIV, 3A forward current or larger. Use a fast-recovery type (such as Schottky type). DO NOT use a small-signal diode such as 1N914, 1N941, etc. Be sure the diode is in the circuit correctly before operation. If installed backwards, it short-circuits the supply when the relay energizes.
Installation, Wiring, and Specifications hhVendor / Catalog
Page 62
2--26
Installation, Wiring, and Specifications Another method of surge suppression is to use a resistor and capacitor (RC) snubber network. The RC network must be located close to the relay module output connector. To find the values for the RC snubber network, first determine the voltage across the contacts when open, and the current through them when closed. If the load supply is AC, then convert the current and voltage values to peak values: Now we are ready to calculate values for R and C, according to the formulas:
C (μF) = Installation, Wiring, and Specifications
2
I
R (Ω) =
10
V 10 x I x
, where x= 1 +
50 V
C minimum = 0.001 μF, the voltage rating of C must be ≥ V, non-polarized R minimum = 0.5 Ω, 1/2 W, tolerance is 5% For example, suppose a relay contact drives a load at 120VAC, 1/2 A. Since this example has an AC power source, we first, we calculate the peak values: Ipeak = Irms x 1.414, = 0.5 x 1.414 = 0.707 Amperes Vpeak = Vrms x 1.414 = 120 x 1.414 = 169.7 Volts Now, finding the values of R and C, we have: I
C (μF) =
Installation and Safety Guidelines
=
10 V
R (Ω) = x= 1 +
2
10 x I 50 169.7
DL405 User Manual, 4th Edition x
0.707 10
2
= 0.05 μF, voltage rating ≥ 170 Volts
, where x= 1 +
= 1.29
R (Ω) =
50 V 169.7 10 x 0.707 1.29
= 16 Ω, 1/2 W, 5%
Page 63
Installation , Wiring, and Specifications
2--27
I/O Module Wiring and Specifications Module Placement
•
S
Do the power budget calculations for each base to verify the base power supply can power all the modules in the base. Information on how to do this is in Chapter 4, System Design and Configuration. Some specialty I/O modules may only be installed in particular slots (will not function properly, otherwise). Check the corresponding manuals before installation and wiring. Whenever possible, keep modules with high voltage and current wiring away from sensitive analog modules.
Installation, Wiring, and Specifications
•
I/O Module Status Indicators
?
Before wiring the I/O modules in your system to field devices, it’s very important to make sure each I/O module is in the right slot and base in the system. Costly wiring errors may be avoided by doing the following:
The diagram below shows the status indicator location for common I/O modules. Loose terminal block indicator
Status indicators Blown fuse (non-replaceable) indicator (Output modules only) Display status (selects a group of signals to be displayed)
Installation and Safety Guidelines
Wire tray
Color Coding of I/O Modules
The DL405 family of I/O modules have a color-coded stripe on the front bezel to help identify whether the module type is input, output, or special module. The color code meaning is listed below: Module Type Discrete/Analog Output Discrete/Analog Input Other
Color Code Red Blue White
110VAV
INPUT
TB A
Color Bar
´
B
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
D4--16NA
80--132VAC 80--20mA 50/60Hz CA 0
DL405 User Manual, 4th Edition
Page 64
2--28
Installation, Wiring, and Specifications
Installation, Wiring, and Specifications
Wiring a Module with a Terminal Block
You must first remove the front cover of the module prior to wiring. To remove the cover depress the bottom tab of the cover and tilt the cover up to loosen from the module. All DL405 I/O module terminal blocks are removable for your convenience. To remove the terminal block loosen the retaining screws and and lift the terminal block away from the module. When you return the terminal block to the module make sure the terminal block is tightly seated. Be sure to tighten the retaining screws. You should also verify the loose terminal block LED is off when system power is applied. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, disconnect all field device power before you remove the connector. Loose terminal block LED indicator
Retaining screw
Terminal screws Retaining screw
Installation and Safety Guidelines
Push tab and lift to remove
I/O module wiring tray
DL405 User Manual, 4th Edition
Page 65
Installation , Wiring, and Specifications Wiring 32 and 64 Point I/O Modules
2--29
The 32 point and 64 point I/O modules use a different style of connector due to the increased number of I/O points. There are several types of connection methods available to choose from. A ZIPLink connection system is shown in the figure below. Refer to the next section for complete information on ribbon and solder type connectors and accessories. Another option is to use the D4--IOCBL--1, a 3m prewired solder connector and cable with pigtail.
ZIPLINK Cable
ZIPLINK Connector Module
64pt. Module
Both types of connectors are available from AutomationDirect. AutomationDirect Part Numbers S D4--IO3264R, Ribbon cable connectors, 2 in a pack. Can be used on either 32 point or 64 point modules. S
D4--IO3264S, Solder type connector, 2 in a pack. Can be used on either 32 point or 64 point modules.
DL405 User Manual, 4th Edition
Installation and Safety Guidelines
The ZIPLink system offers “plug and play” capability, eliminating the need for traditional wiring. Simply plug one end of the ZIPLink cable into a 32 or 64 point I/O module and the other end into a ZIPlink Connector Module. Refer to the Connection Systems section in the catalog for a complete list of cable and connector part numbers. Part Numbers for Module Connectors
Installation, Wiring, and Specifications
32 pt. Module
Page 66
2--30
Installation, Wiring, and Specifications
Installation and Safety Guidelines
Installation, Wiring, and Specifications
Ribbon Cable
Ribbon Cable Connectors
Interface Terminal Block
The chart below lists cables which can be used to connect the terminal block with a 32 I/O module. They have 40 conductors and .050” pitch PVC stranded ribbon cable. Description/Type
Vendor
Part Number
Gray / 26 AWG
3M
3801 / 40
Gray / 26 AWG
Belden
9L260 40
Gray / 28 AWG
Belden
9L280 40
Gray / 28 AWG
DuPont
76825--040
Gray / 28 AWG
AMP
499116--5
Color coded / 26 AWG
3M
3811 / 40
Color coded / 28 AWG
Belden
9R280 40
Color coded / 28 AWG
DuPont
76177--040
These ribbon cable connectors are for attaching the ribbon cable to the terminal block. They are all .100” x .100” 2 x20 female ribbon connectors with a center bump. Description/Type
Vendor
Part Number
Connector Strain Relief
3M 3M
3417--7640 3448--3040
Connector Strain Relief
3M 3M
3417--7640 3448--3040
Connector (pre-assembled) Strain Relief
3M 3M
89140--0103--T0 3448--89140
Connector (with strain relief)
Thomas & Betts
622--4041
Connector (pre-assembled) Strain Relief
AMP AMP
746286--9 499252--1
Connector (with strain relief)
DuPont
66902--240
Connector (with strain relief)
Molex
15--29--9940
Below are terminal blocks which can be used to transition a 40 conductor ribbon cable to 40 discrete field wires. The terminal block features are: 2 x 20 .100” x .100” pin center (male) connector head terminals (.2” centers) accepting 22--12 AWG, no fuses. Description/Type
Vendor
Part Number
Panel Mount Rail Mount
Weidmuller
RI--40A /914897 RI--40A /914908
Rail Mount
Phoenix Contacts
FLKM 40 / 2281076
Special Mount (DIN rail compatible) includes ribbon connector
Augat/RDI
2M40FC
DL405 User Manual, 4th Edition