Page 47

Installation , Wiring, and Specifications

Choosing the Base Type

Local S R M M

CPU

Expansion cable Expansion EXP

S M

The part numbers for standard bases and the new bases are listed below. Standard Bases

D4--04B

D4--06B

D4--08B

Expanded Bus Bases

D4--04B--1

Allows selected specialty modules in expansion bases

Installation, Wiring, and Specifications

There are two types of bases to choose from. The standard base type restricts the placement of specialty modules (or intelligent modules) to the local base with the CPU. By using the DL450 CPU and the new “expanded bus” base type, you can also use specialty modules in expansion bases as shown to the right. When all bases in the local/expansion system are of the new type, the DL450 can communicate with specialty modules in any base. In all other respects, the new base is an exact replacement for the standard bases.

2--11

D4--06B--1

D4--08B--1

NOTE: If you are designing a new DL450 CPU--based application, we recommend using the new bases (--1 type) so you can add specialty modules in any base later.

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

The base expansion connectors on the new bases have new data signals used in communicating with specialty I/O across bases. Accordingly, you must observe the following restrictions and guidelines with the new bases: • Only the DL450 type CPU (in the local base) can communicate with a specialty module in an expansion base. • In the above case, both local and expansion bases must be the new (--1) type. • Of course, you can still have specialty modules in the local base. • The new bases can also be used with DL430 and DL440 CPUs (however, these CPUs cannot communicate with specialty I/O in expansion bases). • You can mix standard bases with new bases in a system, but no specialty I/O modules may be used in expansion bases in this case (the standard bases do not pass through the specialty I/O signals on their expansion connectors).

Page 48

2--12

Installation, Wiring, and Specifications

Installing Components in the Base There is one bank of four configuration switches located on the back of DL430 and DL440 CPUs. These switches affect battery low detection, station address override and baud rate of the secondary port (25-pin D connector). The figure below indicates the location of these DIP switches. Equivalent configuration of the DL450 CPU requires selecting AUX functions on a programming device. Switch 1 S ON = Battery low indicator disabled S OFF= Battery low indicator enabled Switch 2 S ON = Station address override is enabled (address 1) S OFF= Station address is set by AUX function with programming device

ON 1 2 3 4

Installation, Wiring, and Specifications

Setting the CPU DIP Switches (DL430/440 Only)

Installation and Safety Guidelines

NOTE: Setting Switch 2 on forces the station address to 1. It does not change the address set by the programming device. When Switch 2 is turned off again the address will revert back to the address stored in memory via the AUX function. Port 1 Baud Rate

Switch 3

Switch 4

300

Off

Off

1200

Off

On

9600

On

Off

19200

On

On

NOTE: Parity, Mode and Station address for port 2 is selected by AUX functions using a programming device. 1. Note the components have plastic tabs at the bottom and a screw at the top. 2. With the device tilted slightly forward, hook the plastic tabs into the notch on the base. 3. Then gently push the top of the component back toward the base until it is firmly installed into the base. 4. Now tighten the screw at the top of the device to secure it to the base.

Spring loaded securing screw

WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component.

DL405 User Manual, 4th Edition

Page 49

Installation , Wiring, and Specifications

2--13

CPU and Expansion Unit Wiring Guidelines

Installation, Wiring, and Specifications

The main power terminal connections are under the front covers of the DL405 CPUs and Expansion Units. The list below describes the function of each of the terminal screws. Most of the terminal screws are identical between the CPU and the Expansion Unit. If the terminal screw only applies to one of the units it will be noted. • Run Relay -- (CPU only) indicates to an external device when the CPU is in Run Mode by contact closure. Its normally-open contacts can also remove power from critical I/O points if CPU comes out of Run mode. • 24VDC Auxiliary Power -- can be used to power field devices or I/O modules requiring external power. It supplies up to 400 mA of current at 20--28VDC, ripple less than 1 V P-P. (Not available on DC CPUs.) • Logic Ground -- internal ground to the system which can be tied to field devices/communication ports to unite ground signals. • Chassis Ground -- where earth ground is connected to the unit. • AC Power --where the line (hot) and the neutral (common) connections are made to the CPU/Expansion Unit. (This is also where the DC power source is connected for the 24/125 VDC CPU. The positive connection is tied to line and the negative connection is tied to ground.) • 110/220 Voltage Select -- a shunt across two of the terminals determines the voltage selection. Install the shunt to select 110VAC input power, and remove the shunt to select 220VAC power input (the shunt is not required for DC-powered CPUs or Expansion Units.) WARNING: Damage will occur to the power supply if 220 VAC is connected to the terminal connections with the 115 VAC shunt installed. Once the power wiring is connected, install the protective cover to avoid risk of accidental shock. CPU Wiring

The following diagram details the appropriate connections for each terminal. 24VDC Terminal Strip

AC Terminal Strip

Installation and Safety Guidelines

125VDC Terminal Strip

24V Auxiliary Power Logic Ground Chassis Ground + DC -- DC

Logic Ground Chassis Ground + DC -- DC

Logic Ground Chassis Ground AC Line AC Neutral 110/220 Voltage Select

Install shunt between LG and G Recommended screw torque: 10.6 lb--in (1.2Nm)

Install shunt for 110 VAC range, leave off for 220 VAC range.

Install shunt between LG and G

DL405 User Manual, 4th Edition

Page 50

2--14

Installation, Wiring, and Specifications

Expansion Unit Wiring

The following diagram details the appropriate connections for each terminal.

125VDC Terminal Strip

24VDC Terminal Strip

AC Terminal Strip

Installation, Wiring, and Specifications

24V Auxiliary Power Logic Ground Chassis Ground + DC

Logic Ground Chassis Ground + DC

-- DC

-- DC

Chassis Ground AC Line AC Neutral 110/220 Voltage Select

Install shunt between LG and G Recommended screw torque: 10.6 lb--in (1.2Nm)

Connecting Programming Devices

Installation and Safety Guidelines

Logic Ground

Install shunt for 110 VAC range, leave off for 220 VAC range.

Install shunt between LG and G

You can mount the Handheld directly to Port 0 of any DL405 CPU (15-pin D-shell connector), or you can use a 9 foot (3m) or 4.6 ft (1.5m) cable as shown below. Cable Mount

Direct Mount

Use cable part no. D4--HPCBL--1, or D4--HPCBL--2

Retaining Screws

The standard port for use in DirectSOFT programming is the 15-pin port 0 on all DL405 CPUs. The cable shown below is approximately 12 feet (3.66m) long. All DL405 CPUs, port 0 15-pin Dshell male

9-pin D-shell female

Use cable part no. D4--DSCBL

DL405 User Manual, 4th Edition

Page 51

Installation , Wiring, and Specifications

2--15

On the DL450, you may use port 2 instead for DirectSOFT programming. The cable shown below is approximately 12 feet (3.66m) long. DL450 CPU, port 2

RJ12 phone style

9-pin D-shell female

Use cable part no. D2--DSCBL

Operator interfaces usually require data and power connections. However, the popular DV-1000 Data Access Unit may receive data and power directly from any DL405 CPU, using the 2 meter (6.56 ft.) long cable shown below. All DL405 CPUs, port 0

15-pin D-shell male

RJ12 phone style

DV-1000

Installation, Wiring, and Specifications

Connecting Operator Interface Devices

Use cable part no. D4--1000CBL

The DL450 can connect to a DV-1000 from port 2, using the 2 meter (6.56 ft.) long cable shown below. DL450 CPU, port 2 RJ12 phone style

RJ12 phone style

DV-1000

Use cable part no. DV--1000CBL

All DL405 CPUs, port 0 or port 1

15-pin D-shell male

15-pin D-shell male

Optimation Panel

OP--4CBL--1 25-pin D-shell male

OP--4CBL--2

DL450 CPU, port 2

Optimation Panel RJ12 phone style

15-pin D-shell male

OP--2CBL

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

Optimation operator interface panels require separate power and data connections. Connect the CPU port 0, port 1, or port 2 (DL450) to an Optimation panel choosing the appropriate 2 meter (6.56 ft.) long cable from the three shown below.

Page 52

2--16

Installation, Wiring, and Specifications

I/O Wiring Strategies

Installation, Wiring, and Specifications

PLC Isolation Boundaries

The DL405 PLC system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application . This will help to lower system cost, wiring errors, and avoid safety problems. PLC circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note that the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a PLC, it is extremely important to avoid making external connections that connect logic side circuits to any other. Primary Side

Secondary or Logic side

PLC Main Power Supply

Power Input

Installation and Safety Guidelines

Isolation Boundary

CPU

Field Side

(backplane)

Input Module

Inputs

(backplane)

Output Module

Outputs

Programming Device, Operator Interface, or Network

Isolation Boundary

The next figure shows the physical layout of a DL405 PLC system, as viewed from the front. In addition to the basic circuits covered above, AC-powered CPUs include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits! Primary Side Power Input

+24VDC Out

Main Power Supply

Auxiliary +24VDC Supply

DL405 User Manual, 4th Edition

DL405 PLC

Secondary, or Logic side Internal

CPU

Backplane

Comm.

Input Module

Output Module

To Programming Device, Operator Interface, Network

Inputs Commons

Outputs Commons

Field Side

Supply for Output Circuit

Page 53

Installation , Wiring, and Specifications

Powering I/O Circuits with the Auxiliary Supply

2--17

In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 400 mA. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply. All DL405 CPUs feature the internal auxiliary supply. If input devices AND output loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram (400 mA limit). AC Power

Auxiliary +24VDC Supply

+

DL405 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

--

Installation, Wiring, and Specifications

Power Input

Loads

DC-powered DL405 CPUs are designed for application environments in which low-voltage DC power is more readily available than AC. These include a wide range of battery--powered applications, such as remotely-located control, in vehicles, portable machines, etc. For this application type, all input devices and output loads typically use the same DC power source. Typical wiring for DC-powered applications is shown in the following diagram. +

--

--

DC Power

DL405 PLC Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Loads

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

+

Page 54

2--18

Installation, Wiring, and Specifications

Powering I/O Circuits Using Separate Supplies

In most applications it will be necessary to power the input devices from one power source, and to power output loads from another source. Loads often require high-energy AC power, while input sensors use low-energy DC. If a machine operator is likely to come in close contact with input wiring, then safety reasons also require isolation from high-energy output circuits. It is most convenient if the loads can use the same power source as the PLC, and the input sensors can use the auxiliary supply, as shown to the left in the figure below. If the loads cannot be powered from the PLC supply, then a separate supply must be used as shown to the right in the figure below.

Installation, Wiring, and Specifications

AC Power Power Input

Auxiliary +24VDC Supply

+

AC Power Power Input

DL405 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

--

Auxiliary +24VDC Supply

+

DL405 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

--

Installation and Safety Guidelines

Loads

Loads

Load Supply

Some applications will use the PLC external power source to also power the input circuit. This typically occurs on DC-powered PLCs, as shown in the drawing below to the left. The inputs share the PLC power source supply, while the outputs have their own separate supply. A worst-case scenario, from a cost and complexity view-point, is an application which requires separate power sources for the PLC, input devices, and output loads. The example wiring diagram below on the right shows how this can work, but also that the auxiliary supply output is an unused resource. For these reasons, you’ll probably want to avoid this situation if possible. +

+

--

--

DC Power AC Power

DL405 PLC Power Input

Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Auxiliary +24VDC Supply

+ Loads

DL405 User Manual, 4th Edition

Load Supply

DL405 PLC Input Module

Output Module

Inputs

Com.

Outputs Com.

Input Supply

Loads

-Load Supply

Page 55

2--19

Installation , Wiring, and Specifications Sinking/Sourcing Concepts

Before going further in our study of wiring strategies, we must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First we give the following short definitions, followed by practical applications.

Sinking = provides a path to supply ground (--) Sourcing = provides a path to supply source (+)

For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, we just have to connect it so the input provides a path to ground (--). So, we start at the PLC input terminal, follow through the input sensing circuit, exit at the common terminal, and connect the supply (--) to the common terminal. By adding the switch, between the supply (+) and the input, we have completed the circuit. Current flows in the direction of the arrow when the switch is closed.

Input (sinking) +

PLC

Input Sensing

-Common

Input + --

Common

PLC Input Sensing

Sourcing Input Common + --

Input

Sinking Output PLC

Output Switch

Output

Load + --

Common

Sourcing Output PLC Input Sensing

PLC Output Switch

Common + Output

Load

--

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

By applying the circuit principle above to the four possible combinations of input/output sinking/sourcing types, we have the four circuits as shown below. The I/O module specifications at the end of this chapter list the input or output type. Sinking Input

Installation, Wiring, and Specifications

First you will notice that these are only associated with DC circuits and not AC, because of the reference to (+) and (--) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are sinking or sourcing only can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, we can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”.

Page 56

2--20

Installation, Wiring, and Specifications

Installation, Wiring, and Specifications

I/O “Common” In order for a PLC I/O circuit to operate, Terminal Concepts current must enter at one terminal and exit at another. This means at least two terminals are associated with every I/O point. In the figure to the right, the Input or Output terminal is the main path for the current. One additional terminal must provide the return path to the power supply. If we had unlimited space and budget for I/O terminals, then every I/O point could have two dedicated terminals just as the figure above shows. However, providing this level of flexibility is not practical or even necessary for most applications. So, most Input or Output points on PLCs are in groups which share the return path (called commons). The figure to the right shows a group (or bank) of 4 input points which share a common return path. In this way, the four inputs require only five terminals instead of eight.

PLC

Main Path (I/O Point)

Field Device

I/O Circuit

+ -Return Path

PLC Input Sensing

Input 1 Input 2 Input 3 Input 4 + --

Common

Installation and Safety Guidelines

NOTE: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons. Most DL405 input and output modules group their I/O points into banks that share a common return path. The best indication of I/O common grouping is on the wiring label, such as the one shown to the right. The miniature schematic shows two circuit banks with eight input points in each. The common terminal for each is labeled “CA” and “CB”, respectively. In the wiring label example, the positive terminal of a DC supply connects to the common terminals. Some symbols you will see on the wiring labels, and their meanings are: AC supply

DC supply --

Input Switch

AC or DC supply

+

Output Load L

DL405 User Manual, 4th Edition

12--24VDC

INPUT

TB A 0 1 2 3

B 4 5 6 7

0 1 2 3

D4--16ND2 10.2--26.4VDC 4--12mA

CA 0 4 1 5 2 6 3 7 CB 4 0 5 1 6 2 7 3

4 5 6 7