DL405 User Manual: Chapter 2: Installation, Wiring,and Specifications, pages 37 to 46

Pages 37 to 46 of 608, from DL405 User Manual

The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models

Page 37

Installation, Wiring, and Specifications

12

In This Chapter. . . ., Safety Guidelines, Mounting Guidelines, Installing DL405 Bases, Installing Components in the Base, CPU and Expansion Unit Wiring Guidelines, I/O Wiring Strategies, I/O Module Wiring and Specifications, Glossary of Specification Terms

Page 38

2--2

Installation, Wiring, and Specifications

Safety Guidelines

Installation, Wiring, and Specifications

NOTE: Products with CE marks perform their required functions safely and adhere to relevant standards as specified by CE directives provided they are used according to their intended purpose and that the instructions in this manual are adhered to. The protection provided by the equipment may be impaired if this equipment is used in a manner not specified in this manual. A listing of our international affiliates is available on our web site: http://www.automationdirect.com.

WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. Sufficient emergency circuits should be provided to stop either partially or totally the operation of the PLC or the controlled machine or process. These circuits should be routed outside the PLC in the event of controller failure, so that independent and rapid shutdown are available. Devices, such as “mushroom” switches or end of travel limit switches, should operate motor starter, solenoids, or other devices without being processed by the PLC. These emergency circuits should be designed using simple logic with a minimum number of highly reliable electromechanical components. Every automation application is different, so there may be special requirements for your particular application. Make sure you follow all national, state, and local government requirements for the proper installation and use of your equipment.

Installation and Safety Guidelines

Plan for Safety

The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. • NEMA, The National Electrical Manufacturers Association, located in Washington, D.C., publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: ICS 1, General Standards for Industrial Control and Systems ICS 3, Industrial Systems ICS 6, Enclosures for Industrial Control Systems • NEC, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. S Local and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.

DL405 User Manual, 4th Edition

Page 39

Installation , Wiring, and Specifications Three Levels of Protection

Emergency Stops

2--3

Installation, Wiring, and Specifications

The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which provide three levels of system control. • Emergency stop switch for disconnecting system power • Mechanical disconnect for output module power • Orderly system shutdown sequence in the PLC control program It is recommended that emergency stop circuits be incorporated into the system for every machine controlled by a PLC. For maximum safety in a PLC system, these circuits must not be wired into the controller, but should be hardwired external to the PLC. The emergency stop switches should be easily accessed by the operator and are generally wired into a master control relay (MCR) or a safety control relay (SCR) that will remove power from the PLC I/O system in an emergency. MCRs and SCRs provide a convenient means for removing power from the I/O system during an emergency situation. by de--energizing an MCR (or SCR) coil, power to the input (optional) and output devices is removed. This event occurs when any emergency stop switch opens. However, the PLC continues to receive power and operate even though all its inputs and outputs are disabled. The MCR circuit could be extended by placing a PLC fault relay (closed during normal PLC operation) in series with any other emergency stop conditions. This would cause the MCR circuit to drop the PLC I/O power in case of a PLC failure (memory error, I/O communications error. etc.). Use E-Stop and Master Relay

Guard Limit Switch

E STOP

Power On

Emergency Stop

Guard Limit

Master Relay

Master Relay Contacts

PLC Power

Output Module

Saw Arbor

To disconnect output module power

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

Master Relay Contacts

Page 40

Installation, Wiring, and Specifications

2--4

Installation, Wiring, and Specifications

Emergency Power Disconnect

A properly rated emergency power disconnect should be used to power the PLC controlled system as a means of removing the power from the entire control system. It may be necessary to install a capacitor across the disconnect to protect against a condition known as “outrush”. This condition occurs when the output triacs are turned off by powering off the disconnect, thus causing the energy stored in the inductive loads to seek the shortest distance to ground, which is often through the triacs. After an emergency shutdown or any other type of power interruption, there may be requirements that must be met before the PLC control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to ensure a known starting point.

Orderly System Shutdown

Ideally, the first level of fault detection is the PLC control program, which can identify machine problems. Certain shutdown sequences should be performed. The types of problems are usually things such as jammed parts, etc., that do not pose a risk of personal injury or equipment damage. WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.

Jam Detect

Turn off Saw RST RST Retract Arm

Installation and Safety Guidelines

Class 1, Division 2 Approval

This equipment is suitable for use in Class 1, Division 2, groups A, B, C and D or non--hazardous locations only. WARNING: Explosion Hazard! Substitution of components may impair suitability for Class 1, Division 2. Do not disconnect equipment unless power has been switched off or area is known to be non--hazardous.

DL405 User Manual, 4th Edition

Page 41

Installation , Wiring, and Specifications

2--5

Mounting Guidelines

Base Dimensions

4.375” 111mm 3.94” 100mm

CPU Expansion Unit, Remote Slave

4 holes, clearance for M4 screw

4.312” 110mm

5.9” 150mm

4 Slot Base

6 Slot Base 14.45” 367mm 13.74” 349mm

11.54” 293mm 10.83” 275mm

0.47” 12 mm

0.75” 19 mm

Base mounting dimensions given to upper (fully seated) location

8 Slot Base Mounting hole close-up

0.47” 12 mm

17.36” 441mm 16.65” 423mm

5.91” 4.69” 150mm 119mm

0.75” 19 mm

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

5.91” 4.69” 150mm 119mm

0.28” 7 mm

Installation, Wiring, and Specifications

In addition to the panel layout guidelines, other specifications can affect the installation of a PLC system. Always consider the following: • Environmental specifications • Power supply specifications • Regulatory Agency Approvals • Enclosure Selection and Component Dimensions The following diagram shows the outside dimensions and mounting hole locations for the 4-slot, 6-slot, and 8-slot bases. Make sure you follow the installation guidelines to allow proper spacing from other components.

Page 42

2--6

Installation, Wiring, and Specifications

Installation, Wiring, and Specifications

Panel Layout & Clearances

There are many things to consider when designing the panel layout. The following items correspond to the diagram shown. Note: there may be additional requirements, depending on your application and use of other components in the cabinet. 1. The bases must be mounted horizontally to provide proper ventilation. 2. There should be a minimum of 7.2” (183mm) and a maximum of 13.75” (350mm) between bases. 3. A minimum clearance of 2” (50mm) between the base and the top, bottom and right side of the cabinet should be provided. 4. A minimum clearance of 3” (75mm) between the base and the left side of the cabinet should be provided. 5. There must be a minimum of 2” clearance between the panel door and the nearest DL405 component. Temperature Probe

2”

– ’ Power Source

‘ 50mm min.

DL405 CPU Base

3” 75mm min.

‘

2” 50mm min.

˜

7.2” -- 13.75”

DL405 Local Expansion Base

183 -- 350mm

Panel

Installation and Safety Guidelines

•

ƒ min.

BUS Bar

Star Washers Ground Braid Copper Lugs

Earth Ground

ƒ Star Washers

2” ” ‘ 50mm

Panel or Single Point Ground

“

Panel Ground Terminal Note: there is a minimum of 2” (50mm) clearance between the panel door and the nearest DL405 component. Not to scale

6. Connect the ground terminal on the DL405 base to a single point ground. Use copper stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact. Remove anodized finishes and use copper lugs and star washers at termination points. A rule of thumb is to achieve 0.1 ohm of DC resistance between the DL405 base and the single point ground.

DL405 User Manual, 4th Edition

Page 43

Installation , Wiring, and Specifications

2--7

7. There must be a single point ground (i.e. copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. For this connection you should use #12 AWG stranded copper wire as a minimum. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your area. A good common ground reference (Earth ground) is essential for proper operation of the DL405, which include:

8. Installations where the ambient temperature may approach the lower or upper limits of the specifications should be evaluated properly. To do this place a temperature probe in the panel, close the door and operate the system until the ambient temperature has stabilized. If the ambient temperature is not within the operating specification for the DL405 system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the DL405 operating specifications. 9. Device mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. Tapped holes instead of nut--bolt arrangements should be used whenever possible. To assure good contact on termination areas impediments such as paint, coating or corrosion should be removed in the area of contact. 10. The DL405 system is designed to be powered by 110 VAC, 220 VAC, or 24 VDC normally available throughout an industrial environment. Isolation transformers and noise suppression devices are not normally necessary, but may be helpful in eliminating/reducing suspect power problems. Your selection of a proper enclosure is important to ensure safe and proper operation of your DL405 system. Applications of DL405 systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access S Sufficient space for proper installation, cooling, and maintenance

Agency Approvals

Some applications require agency approvals. The DL405 agency approvals for which DL405 products are submitted are; • UL (Underwriters’ Laboratories, Inc.) • CE EMC (Electromagnetic Compatibility) • CUL (Canadian Underwriters’ Laboratories) A complete listing of agency approvals for each product in the DL405 family is available in the sales catalog, or you may call 1--800--633--0405 (U.S.).

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

Enclosures

Installation, Wiring, and Specifications a) Installing a ground rod as close to the panel as possible. b) Connection to incoming power system ground.

Page 44

2--8

Installation, Wiring, and Specifications

Installation, Wiring, and Specifications

Environmental Specifications

Specification

Rating

Storage temperature

--4° F to 158° F (--20° C to 70° C)*

Ambient operating temperature

32° F to 140° F (0° C to 60° C)

Ambient humidity

5% -- 95% relative humidity (non--condensing) **

Vibration resistance

MIL STD 810C, Method 514.2

Shock resistance

MIL STD 810C, Method 516.2

Noise immunity

NEMA (ICS3--304)

Atmosphere

No corrosive gases

*Storage temperature for the Handheld Programmer is 14° to 149°F (--10° to 65° C) **Ambient humidity for the Handheld Programmer is 20% to 90% non-condensing.

Power

Installation and Safety Guidelines

The following table lists the environmental specifications that generally apply to the DL405 system (CPU, Expansion Unit, Bases, I/O Modules). The ranges that vary for the Handheld Programmer are noted at the bottom of this chart. I/O module operation may fluctuate depending on the ambient temperature and your application. Please refer to the appropriate I/O module chapters for the temperature derating curves applying to specific modules.

The external power source must be capable of suppling voltage and current complying with the PLC power supply specifications. Specifications

DL405 Series CPUs

Voltage withstand (dielectric strength)

1 min. @ 1500 VAC between primary, secondary, field ground and run relay

Insulation resistance

> 10MΩ at 500 VDC

Input voltage range D4--430 / D4--440 / D4--450 / D4--EX

85--132 VAC (110 range) / 170--264 VAC (220 range)

Input voltage range D4--440DC--1 / D4--EXDC

20--29 VDC (24VDC) less than 10% ripple

Input voltage range D4--440DC--2 / D4--EXDC--2

90--146 VDC (125 VDC) less than 10% ripple

Maximum inrush current D4--430 / D4--440 / D4--EX

20A

Maximum inrush current D440DC--1 / D4--EXDC

10A

Maximum inrush current DL440DC--2 / 20A D4--EXDC--2 Maximum power DL430/DL440/DL450, D4--EX

50VA

Maximum power DL440DC--1, D4--EXDC

38W

Maximum power DL440DC--2, D4--EXDC--2

30W

24VDC Auxiliary Power Supply (D4--EX only)

20--28 VDC @ 0.4A maximum, ripple > 1V p-p

DL405 User Manual, 4th Edition

Page 45

Installation , Wiring, and Specifications

Component Dimensions

2--9

Before installing your PLC system you will need to know the dimensions for the components in your system. The diagram on this page provide the component dimensions and should be used to define your enclosure specifications. Remember to leave room for potential expansion. Appendix E provides the weights for each component. Handheld programmer 5.7” 145mm

1.2” 30mm

3.14” 80mm

4.65” 118mm

I/O modules 4.375” 111mm 4” 100mm

Installation, Wiring, and Specifications

Memory Cartridge

I/O module w/Ribbon connector 1.37” 34.8mm

NOTE: Ribbon connector and D shell extend out past module and may affect depth of cabinet

5.9” 150m

4.5 ft.(1.5m) 9.1 ft. (3m)

Base Expansion Cable 1.6ft. (.5m) 3.3 ft. (1m)

DL405 User Manual, 4th Edition

Installation and Safety Guidelines

Handheld programmer cable

Page 46

2--10

Installation, Wiring, and Specifications

Installing DL405 Bases Three Sizes of Bases

All I/O configurations of the DL405 (except for Slice I/O) will use a selection of either 4, 6 or 8 slot base(s). Local and expansion bases can be 4, 6, or 8-slot in size. Local and expansion bases differ only in how they are wired in a system. Expansion cable input connection

Installation, Wiring, and Specifications

Local Base Expansion cable output connection

Expansion cable

8 slot base

Expansion Bases

Expansion Power Supplies

6 slot base

Installation and Safety Guidelines

4 slot base

WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component. Mounting the Base

The CPU/Expansion Unit/Remote Slave must always be installed in the left-most slot in a base. This slot is marked on the base as P/S, CPU. The I/O modules can be installed in any remaining slots. It is not necessary for all slots to be filled for your system to work correctly. You may use filler modules to fill the empty slots in the base. The base is secured to the equipment panel or machine using four M4 screws in the corner locations shown to the right. The mounting cut-outs allow removal of the base after installation, without completely removing the mounting screws. Full mounting template dimensions are given in the previous section on Mounting Guidelines.

DL405 User Manual, 4th Edition

Base mounting holes, 4 locations

Mounting hole close-up