Page 29
1--9
Getting Started
DirectLOGIC™ Part Numbering System DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family
D4/F4
Number of channels
02/04/08/16
Input (Analog to Digital)
AD
Output (Digital to Analog)
DA
Combination Isolated xADxDA S
Denotes a differentiation between Similar modules
--1, --2, --3, --4
Communication and Networking, Special I/O and Devices Programming DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family
D4/F4
Name Abbreviation see example
CoProcessors and ASCII BASIC Modules DL205 Product family
D2/F2
DL305 Product family
D3/F3
DL405 Product family
D4/F4
CoProcessor
CP
ASCII BASIC
AB
64K memory
64
128K memory
128
512K memory
512
Radio modem
R
Telephone modem
T
F3--
04
AD
S
Getting Started
Analog I/O
--1
Alternate example of Analog I/O using abbreviations F3--
08
THM
--n note: --n indicates thermocouple type such as: J, K, T, R, S or E
D4--
DCM
D3--
HSC
HSC (High Speed Counter)
D3--
HPP
HPP (RLL PLUS Handheld Programmer)
F4--
CP
128
DCM (Data Communication Module)
-- R
DL405 User Manual, 4th Edition
Page 30
1--10
Getting Started
Getting Started
Quick Start for PLC Checkout and Programming If you have experience with PLCs, or if you just want to setup a quick example, this section is for you! This example is not intended to tell you everything you need to start-up your system. It is only intended to give you a general picture of what you will need to do to get your system powered-up. Step 1: Unpack the Unpack the DL405 equipment and verify you have the parts necessary to build this DL405 Equipment demonstration system. The minimum parts you will need are: S Base S CPU (with a memory cartridge if you are using a DL440 or DL450) S D4--16ND2 DC input module or a D4--16SIM input simulator module S D4--16TR Relay output module S Power cord S Hook up wire S A 24 VDC toggle switch (if not using the input simulator module) S A screwdriver, regular or Philips type You will need at least one of the following programming options: S DirectSOFT Programming Software, DirectSOFT Manual, and a programming cable (connects the CPU to a personal computer), or S D4--HPP Handheld Programmer (programming cable is optional), and the Handheld Programmer Manual
DL405 User Manual, 4th Edition
Page 31
Getting Started
Insert the CPU and I/O into the base. The CPU must go into the far left side of the base in the position marked “CPU/Power Supply”. When inserting components into the base, tilt the component slightly forward sliding the tab on the bottom of the component into the slot in the base. Push the top of the component into the base until it is seated firmly, then tighten the securing screw at the top of the module/unit. Placement of discrete, analog and relay modules are not critical and may go in any slot in any base however for this example install the output module in the slot next to the CPU (slot 0) and the input module in the next slot (slot 1). Limiting factors for other types of modules are discussed in Chapter 4, Bases, Expansion Units and I/O Configuration. You must also make sure you do not exceed the power budget for each base in your system configuration. Power budgeting is discussed in Chapter 4, System Design and Configuration. S S
S
S
Step 3: Remove Terminal Strip Access Cover
Each unit has a plastic tab at the bottom and a screw at the top. With the unit tilted slightly forward, hook the module’s plastic tab on the base. Gently push the top of the unit back until it is firmly installed in the base. Secure the unit to the base by tightening the top screw.
Remove the terminal strip cover. It has a small retention snap on the left edge. Push in and up then pull the cover off. Push in and lift off
Step 4: Install Memory Cartridge
If you are using a DL440 CPU (optional on DL450) you need to install the memory cartridge in the slot to the right of the battery. Make sure it is firmly seated. To find out more about memory cartridges see Chapter 3. Memory Cartridge
Step 5: Select Operating Power Range
If you are using 110VAC install the voltage select jumper on the bottom two terminals. If you are using 220VAC power, do not install the jumper. You can find a detailed explanation of the terminal block on both the CPU and expansion units in Chapter 2, Installation, Wiring, and Specifications.
DL405 User Manual, 4th Edition
Getting Started
Step 2: Install the CPU and I/O Modules
1--11
Page 32
Getting Started
1--12
Getting Started
WARNING: Damage will occur to the power supply if 220 VAC is connected to the terminal connections with the 110 VAC shunt in place.
Run Relay
If using D4--0X--1 type bases, install this shunt to connect grounds, for proper noise immunity.
24V Auxiliary Power Logic Ground Chassis Ground
Install shunt to select 110 VAC range, leave shunt off to select 220 VAC range.
AC Power
110/220 Voltage Select
Step 6: Add I/O Simulation
To finish this quick-start exercise or study other examples in this manual, you’ll need to install an input simulator module (or wire an input switch as shown below), and add an output module. Using an input simulator is the quickest way to get physical inputs for checking out the system or a new program. To monitor output status, any discrete output module will do.
--
Toggle switch
Output Module
Input Module
Wire the switches or other field devices prior to applying power to the system to ensure a point is not accidentally turned on during the wiring operation. Wire the input module (X0) to the toggle switch and 24VDC auxiliary power supply on the CPU terminal strip as shown below for the 16ND2 input module. Chapter 2, Installation, Wiring, and Specifications provides a list of I/O wiring guidelines.
DL405 User Manual, 4th Edition
Page 33
1--13
Getting Started
Connect the wires as shown. Observe all precautions stated earlier in this manual. For details on wiring, see Chapter 2, Installation, Wiring, and Specifications. When the wiring is complete, replace the CPU and module covers. Do not apply power at this time.
Getting Started
Step 7: Connect the Power Wiring
Ground Line Neutral
Step 8: Connect the Handheld Programmer
Remove the connector cover at the top right of the CPU. Join the Handheld programmer’s 15 pin D type connector (located on the back) to the connector you just uncovered on the CPU. Finger tighten the securing screws on the top and bottom of the Handheld programmer.
Step 9: Switch On the System Power
Apply power to the system and ensure the PWR indicator on the CPU is on. If not, remove power from the system and check all wiring and refer to the troubleshooting section in Chapter 9 for assistance.
Step 10: Enter the Program
Turn the key switch on the CPU to the STOP position and then back to the TERM position. This puts the CPU in the program mode and allows access to the CPU program. The PGM indicator should be illuminated on the HPP. Enter the following keystrokes on the HPP:
Securing screws
NOTE: It is not necessary for you to configure the I/O for this system since the DL430 CPUs automatically configure I/O and the DL440 and DL450 CPUs default to automatic I/O configuration.
CLR
CLR
AUX
2
4
CLR
$(AD)
0
STR
X(IN)
0
OUT
Y(OUT)
0
X0
Y0
NXT
END
END
After entering the simple example program turn the key switch from the TERM position to the RUN position and back to TERM. The RUN indicator on the CPU will come on indicating the CPU has entered the run mode. If not repeat Step 10 insuring the program is entered properly or refer to the troubleshooting guide in chapter 9. During Run mode operation, the output status indicator 0 on the output module should reflect the switch status. When the switch is on the output should be on.
DL405 User Manual, 4th Edition
Page 34
1--14
Getting Started
Getting Started
Steps to Designing a Successful System Step 1: Review the Installation Guidelines
Always make safety your first priority in any system application. Chapter 2 provides several guidelines that will help provide a safer, more reliable system. This chapter also includes wiring guidelines for the various system components.
Step 2: Understand the CPU Setup Procedures
The CPU is the heart of your automation system. Make sure you take time to understand its various features and setup requirements.
Step 3: Understand It is important to understand how to configure the I/O system. You have the I/O System several different types of systems: Configurations S Local System S Expansion System S Remote I/O System S Network connections It is also important to understand how the system Power Budget is calculated. See Chapter 4 for more information. Step 4: Determine the I/O Module Specifications and Wiring Characteristics
Emergency Stop
16pt Input
8pt Input
32pt Input
X0
X20
X30
16pt Output
8pt Output
16pt Output
Y0
Y20
Y30
--
--
--
--
--
--
X17
X27
X67
Y17
Y27
Y47
There are many different I/O modules available with the DL405 system. Chapter 2 provides the specifications and wiring diagrams for the discrete I/O modules.
32 pt. Module
OR
Ribbon connector
NOTE: Analog and other specialty modules have their own manuals and are not included in this manual.
DL405 User Manual, 4th Edition
Page 35
1--15
Getting Started
Step 5: Understand Before you begin to enter a program, it is the CPU Operation very helpful to understand how the DL405 CPU processes information. This involves not only program execution steps, but also involves the various modes of operation and memory layout characteristics. See Chapter 3 for more information.
Getting Started
Power up Initialize hardware Check I/O module config. and verify
Step 6: Review the The DL405 PLC provides four main approaches to solving the application program, including the PID loop task depicted in the next figure. Programming Concepts S RLL diagram-style programming is the best tool for solving boolean logic and general CPU register/accumulator manipulation. It includes dozens of instructions, which will augment drums, stages, and loops. S The DL450 has four timer/event drum types, each with up to 16 steps They offer both time and/or event-based step transitions. Drums are best for a repetitive process based on a single series of steps. S Stage programming (also called RLL Plus) is based on state-transition diagrams. Stages divide the ladder program into sections which correspond to the states in a flow chart you draw for your process. S The DL450 PID Loop Operation uses setup tables to configure up to 16 loops. Features include alarms, SP ramp/soak generation, and more. Timer/Event Drum Sequencer (see Chapter 6)
Standard RLL Programming (see Chapter 5) X0
LDD V1076 CMPD K309482
SP62
Y0 OUT
Stage Programming (see Chapter 7) Push--UP
PID Loop Operation (see Chapter 8)
RAISE
SP DOWN
LIGHT
UP
+
Σ
PID
Process
-PV
LOWER
Push-DOWN
Step 7: Choose the After installation and studying the main programming concepts, you can begin Instructions writing the application program or configuring loop operation. You’ll discover a powerful instruction set!
TMR
K30
T1 CNT
K10
CT3
DL405 User Manual, 4th Edition
Page 36
Getting Started
1--16
Getting Started
Step 8: Understand Sometimes equipment failures occur when we least expect it. Switches fail, the Maintenance loads short and need replacement, etc. and Often, the majority of the troubleshooting Troubleshooting time is spent in locating the problem. The Procedures DL405 system has many built-in features such as error codes that can help you quickly identify problems. See Chapter 9 for diagnostics and troubleshooting tips.
Frequently Asked Questions Q. How do I reset my DL405 CPU back to factory defaults A. Resetting the processor to factory defaults is a two step process. First clear the processor memory using DirectSOFT PLC>CLEAR PLC MEMORY. Next initialize the scratchpad PLC>SETUP>INITIALIZE SCRATCHPAD. Be aware that initializing the scratchpad will reset the system V--memory to defaults. System V--memory contains parameters such as retentive ranges, communications port settings, etc. Q. How often should the CPU backup battery be changed? A. All of the 405 CPUs have an LED indicator that will flash when the battery voltage is getting low. The typical battery life is 5 years. Q. Where can I obtain the most current firmware for the DL450? A. In the tech support section of www.automationdirect.com. The firmware and instructions on how to update the CPU are available. Q. Do the DL405 PLCs have ethernet capability? A. Yes, the H4--ECOM module is needed to support ethernet. Q. Can the DL405 use the Modbus protocol? A. The DL450 supports Modbus on port 1 or 3 as a master or slave. The DL--430/440 can support Modbus using the F4--MAS--MB master or F4--SLV--MB slave module. Q. Can I have more than 16 PID loops on a system using the DL450? A. Yes. You can still use the 16-loop PID module in the base, plus the DL450’s loops. Q. What are the networking capabilities of the DL450? A. The DL430/DL440 CPUs can serve as DirectNET slaves. The DL450 has two network ports, which can serve as DirectNET masters or slaves, or MODBUS masters or slaves. Q. Are more FAQs available for the DL405 and other products? A. Yes, visit www.automationdirect.com for more FAQs and other technical information.
DL405 User Manual, 4th Edition