Page 190
Chapter 5: Standard RLL Instructions - Immediate Instructions
Set Immediate (SETI)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The Set Immediate instruction immediately sets, or turns on an output or a range of outputs in the image register and the corresponding output point(s) at the time the instruction is executed. Once the outputs are set it is not necessary for the input to remain on. The Reset Immediate instruction can be used to reset the outputs.
Y aaa aaa SETI
Reset Immediate (RSTI) DS5
Used
HPP
Used
5–36
The Reset Immediate instruction immediately resets, or turns off an output or a range of outputs in the image register and the output point(s) at the time the instruction is executed. Once the outputs are reset it is not necessary for the input to remain on.
Y aaa aaa RSTI
Operand Data Type
DL06 Range aaa
Ouputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y
0–777
In the following example, when X1 is on, Y2 through Y5 will be set on in the image register and on the corresponding output points.
DirectSOFT 5 DirectSOFT32 X1
Handheld Programmer Keystrokes Y2
$
Y5
B STR
SETI
X SET
1
ENT C
I
SHFT
8
F 2
5
ENT
In the following example, when X1 is on, Y5 through Y22 will be reset (off ) in the image register and on the corresponding output module(s). DirectSOFT 5 DirectSOFT32 Handheld Programmer Keystrokes X1
Y5
Y22 RSTI
$
B STR
S RST
1 SHFT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
I
ENT C
F 8
5
C 2
2
ENT
Page 191
Chapter 5: Standard RLL Instructions - Immediate Instructions
Load Immediate (LDI) DS5
Used
HPP
Used
The Load Immediate instruction loads a 16-bit V-memory value into the accumulator. The valid address range includes all input point addresses on the local base. The value reflects the current status of the input points at the time the instruction is executed. This instruction may be used instead of the LDIF instruction which requires you to specify the number of input points.
1 V aaa 2 3 Operand Data Type DL06 Range aaa 4 In the following example, when C0 is on, the binary pattern of X0–X17 will be loaded into 5 the accumulator using the Load Immediate instruction. The Out Immediate instruction could be used to copy the 16 bits in the accumulator to output points, such as Y40–Y57. This 6 technique is useful to quickly copy an input pattern to output points (without waiting for a full CPU scan to occur). 7 8 9 10 11 12 13 14 A B C D Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
LDI
40400-40437
DirectSOFT 5 DirectSOFT32 C0
Location
LDI
X17 X16 X15 X14 X13 X12 X11 X10
V40400
V40400
Load the inputs from X0 to X17 into the accumulator, immediately
X7
X6
X5
X4
X3
X2
X1
X0
ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero
Acc.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7 6 5
4 3
2
1
0
0
0
1 0
1
1 0
1
0
0
0 0
0
0
0
0 0
0
0
0
0 0
0
1
0
1
1 0
1
0
1
0
OUTI
V40502
Output the value in the accumulator to output points Y40 to Y57
Location
Y57 Y56 Y55 Y54 Y53 Y52 Y51 Y50 Y47 Y46 Y45 Y44 Y43 Y42 Y41 Y40 ON OFF ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF ON
V40502
Handheld Programmer Keystrokes $ STR SHFT GX OUT
NEXT
NEXT
L ANDST
D
I
SHFT
I
3 8
NEXT
NEXT
A
E
A
8
0
4
NEXT
E
E
0
A
4
ENT
A
4
F
0
A
0
A
5
0
C
0
2
ENT ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–37
Page 192
Chapter 5: Standard RLL Instructions - Immediate Instructions
Load Immediate Formatted (LDIF)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The Load Immediate Formatted instruction loads a 1–32 bit binary value into the accumulator. The value reflects the current status of the input module(s) at the time the instruction is executed. Accumulator bits that are not used by the instruction are set to zero. Operand Data Type
X aaa
LDIF K bbb
DL06 Range
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K aaa bbb
0-777 --
-1-32
In the following example, when C0 is on, the binary pattern of X10–X17 will be loaded into the accumulator using the Load Immediate Formatted instruction. The Out Immediate Formatted instruction could be used to copy the specified number of bits in the accumulator to the specified outputs on the output module, such as Y30–Y37. This technique is useful to quickly copy an input pattern to outputs (without waiting for the CPU scan).
DirectSOFT 5 DirectSOFT32 C0
LDIF
X10 K8
Load the value of 8 consecutive location into the accumulator starting with X10
Constant K8
X17 X16 X15 X14 X13 X12 X11 X10 ON OFF ON ON OFF ON OFF ON
Unused accumulator bits are set to zero
Acc.
OUTIF
Location X10
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7 6 5
4 3
2
1
0
0
0
1 0
1
1 0
1
0
0
0 0
0
0
0
0 0
0
0
0
0 0
0
0
0
0
0 0
0
0
1
0
Y30 K8
Copy the value of the lower 8 bits of the accumulator to Y30 - Y37
Location
Constant
Y37 Y36 Y35 Y34 Y33 Y32 Y31 Y30
Y30
K8
ON OFF ON ON OFF ON OFF ON
Handheld Programmer Keystrokes $ STR
NEXT
NEXT
NEXT
I
F
SHFT
L ANDST
D
GX OUT
SHFT
I
5–38
3
8 F
8
NEXT
0 1 A
3
ENT A
B 5 D
5
A
I 0
8 I
0
8
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
ENT
Page 193
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Timer, Counter and Shift Register Instructions
1 Timers are used to time an event for a desired length of time. The single input timer will time 2 as long as the input is on. When the input changes from on to off the timer current value is reset to 0. There is a tenth of a second and a hundredth of a second timer available with a 3 maximum time of 999.9 and 99.99 seconds respectively. There is a discrete bit associated with each timer to indicate that the current value is equal to or greater than the preset value. The timing diagram below shows the relationship between the timer input, associated discrete bit, 4 current value and timer preset. 5 6 7 8 There are those applications that need an accumulating timer, meaning it has the ability to time, stop, and then resume from where it previously stopped. The accumulating timer works similarly to the regular timer, but two inputs are required. The enable input starts and stops 9 the timer. When the timer stops, the elapsed time is maintained. When the timer starts again, the timing continues from the elapsed time. When the reset input is turned on, the elapsed 10 time is cleared and the timer will start at 0 when it is restarted. There is a tenth of a second and a hundredth of a second timer available with a maximum time of 9999999.9 and 999999.99 seconds respectively. The timing diagram below shows the relationship between 11 the timer input, timer reset, associated discrete bit, current value and timer preset. 12 13 14 A NOTE: Decimal points are not used in these timers, but the decimal point is implied. The preset and current B value for all four timers is in BCD format. C D
Using Timers
0
1
2
3
Seconds 4
5
6
7
8
X1
TMR
X1
T1
K30
Timer Preset
T1
T1
Current Value
0
0
10
20
1
2
3
30 40 1/10 Seconds
Seconds 4
5
50
60
6
7
Y0 OUT
0
8
X1
TMRA
T0
K30
Enable
X1
X2
X2
Reset Input
T0
Current Value
0
10
10
20 30 1/10 Seconds
40
50
0
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–39
Page 194
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Timer (TMR) and Timer Fast (TMRF)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–40
The Timer instruction is a 0.1 second single input timer that times to a maximum of 999.9 seconds. The Timer Fast instruction is a 0.01 second single input timer that times up to T aaa TMR a maximum of 99.99 seconds. These timers will be enabled if B bbb the input logic is true (on) and will be reset to 0 if the input logic is false (off ). Both timers use single word BCD values for Preset Timer# the preset and current value. The decimal place is implied. Instruction Specifications Timer Reference (Taaa): Specifies the timer number. Preset Value (Bbbb): Constant value (K) or a V-memory TMRF T aaa location specified in BCD. B bbb Current Value: Timer current values, in BCD format, are accessed by referencing the associated V or T memory Timer# Preset location*. For example, the timer current value for T3 physically resides in V-memory location V3. Discrete Status Bit: The discrete status bit is referenced by the associated T memory location. Operating as a “timer done bit”, it will be on if the current value is equal to or greater than the preset value. For example, the discrete status bit for Timer 2 is T2. NOTE: A V-memory preset is required only if the ladder program or an Operator Interface unit must change the preset.
Operand Data Type
DL06 Range
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T aaa bbb
0–777
V-memory for preset values . . . . . . . . . . . . . . . V
––
–– 400-677 1200–7377 7400–7577 10000-17777
Pointers (preset only) . . . . . . . . . . . . . . . . . . . . P Constants (preset only) . . . . . . . . . . . . . . . . . . K Timer discrete status bits . . . . . . . . . . . . . . . T/V Timer current values . . . . . . . . . . . . . . . . . V /T**
400-677 1200–7377 7400–7577* 10000-17777 –– 0–9999 0–377 or V41100–41117 0–377 ––
NOTE: *May be non-volatile if MOV instruction is used. ** With the HPP, both the Timer discrete status bits and current value are accessed with the same data reference. DirectSOFT 5 uses separate references, such as “T2” for discrete status bit for Timer T2, and “TA2” for the current value of Timer T2.
You can perform functions when the timer reaches the specified preset using the discrete status bit. Or, use comparative contacts to perform functions at different time intervals, based on one timer. The examples on the following page show these two methods of programming timers. DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 195
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Timer Example Using Discrete Status Bits In the following example, a single input timer is used with a preset of 3 seconds. The timer discrete status bit (T2) will turn on when the timer has timed for 3 seconds. The timer is reset when X1 turns off, turning the discrete status bit off and resetting the timer current value to 0.
1 2 3 4 5 6 7 8 Timer Example Using Comparative Contacts In the following example, a single input timer is used with a preset of 4.5 seconds. 9 Comparative contacts are used to energize Y3, Y4, and Y5 at one second intervals respectively. When X1 is turned off the timer will be reset to 0 and the comparative contacts will turn off 10 Y3, Y4, and Y5. 11 12 13 14 A B C D DirectSOFT 5 Direct SOFT32
Timing Diagram
X1
TMR
T2
0
K30
OUT
B
STR
N TMR $
C
STR
GX OUT
D
2
SHFT
T MLR
A
ENT
0
Seconds 4
5
6
7
0
10
20
30
40
50
60
C
A
3
ENT
0
ENT
2
DirectSOFT 5
Timing Diagram
X1
TMR
Seconds
T20
0
K45
Y3
K10
2
3
4
5
6
7
0
10
20
30
40
50
60
8
Y3
Y4
K20
1
X1
OUT
TA20
0
1/10th Seconds
Direct SOFT32
TA20
8
Y0
Current Value
ENT
1
3
T2
Handheld Programmer Keystrokes $
2
X1
Y0
T2
1
Y4
OUT
Y5
TA20
Y5
K30
T2
OUT
Current Value
1/10th Seconds
Handheld Programmer Keystrokes $
B
STR
1
ENT
N TMR
C
2
0
$
SHFT
T MLR
STR
GX OUT $
STR
GX OUT $
STR
GX OUT
A
D
3
SHFT
E
4
E
F
4
C
2
5
ENT
B
A
0
A
1
0
ENT
ENT
T MLR
A
C
2
C
0
A
2
0
ENT
ENT
SHFT
T MLR
F
ENT
5
0
A
C
2
A
D
0
3
0
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–41
Page 196
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Accumulating Timer (TMRA) The Accumulating Timer is a 0.1 second two input timer that will time to a maximum of 9999999.9. The TMRA uses two timer Used registers in V-memory.
DS5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Used
HPP
Enable
T aaa TMRA B bbb
Reset
Accumulating Fast Timer (TMRAF) DS5 HPP
5–42
The Accumulating Fast Timer is a 0.01 second two-input timer Timer# Preset that will time to a maximum of 99999.99. The TMRA uses two Used timer registers in V-memory. Each timer uses two timer registers in V-memory. The preset and T aaa Enable TMRAF B bbb current values are in double word BCD format, and the decimal point is implied. These timers have two inputs, an enable and a Reset reset. The timer starts timing when the enable is on and stops when the enable is off (without resetting the count). The reset Timer# will reset the timer when on and allow the timer to time when off. Preset Timer Reference (Taaa): Specifies the timer number. Preset Value (Bbbb): Constant value (K) or V-memory. Current Value: Timer current values are accessed by referencing the associated V or T memory location*. For example, the timer current value for T3 resides in V-memory, V3. Discrete Status Bit: The discrete status bit is accessed by referencing the associated T memory location. Operating as a “timer done bit,” it will be on if the current value is equal to or greater than the preset value. For example the discrete status bit for timer 2 would be T2. Used
NOTE: The accumulating timer uses two consecutive V-memory locations for the 8-digit value, therefore two consecutive timer locations. For example, if TMRA T1 is used, the next available timer number is T3. NOTE: A V-Memory preset is required if the ladder program or an OIP must be used to change the preset.
Operand Data Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T V-memory for preset values . . . . . . . . . . . . . . . V
Pointers (preset only) . . . . . . . . . . . . . . . . . . . . P Constants (preset only) . . . . . . . . . . . . . . . . . . K Timer discrete status bits . . . . . . . . . . . . . . . T/V Timer current values . . . . . . . . . . . . . . . . . V /T**
DL06 Range aaa bbb
0–777
–– 400-677 1200–7377 –– 7400–7577 10000-17777 400-677 1200–7377 –– 7400–7577* 10000-17777 –– 0–99999999 0–377 or V41100–41117 0–377
NOTE: *May be non-volatile if MOV instruction is used. ** With the HPP, both the Timer discrete status bits and current value are accessed with the same data reference. DirectSOFT 5 uses separate references, such as “T2” for discrete status bit for Timer T2, and “TA2” for the current value of Timer T2.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 197
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Accumulating Timer Example using Discrete Status Bits In the following example, a two input timer (accumulating timer) is used with a preset of 3 seconds. The timer discrete status bit (T6) will turn on when the timer has timed for 3 seconds. Notice in this example that the timer times for 1 second , stops for one second, then resumes timing. The timer will reset when C10 turns on, turning the discrete status bit off and resetting the timer current value to 0. DirectSOFT 5
Timing Diagram
Direct SOFT32 X1
TMRA
0
T6
1
2
3
Seconds 4
5
6
7
0
10
10
20
30
40
50
8
X1
K30 C10
C10
T6
Y7
T6
OUT
Current Value
Handheld Programmer Keystrokes
Handheld Programmer Keystrokes (cont)
$
D
B 1
STR $
SHFT
A 3
C
SHFT
STR N TMR
ENT B 2
A 1
A
STR
G 0
ENT
0
$
ENT
0
GX OUT
6
0
SHFT
T MLR
G
B
A
ENT
0
1
ENT
6
Accumulator Timer Example Using Comparative Contacts In the following example, a single input timer is used with a preset of 4.5 seconds. Comparative contacts are used to energized Y3, Y4, and Y5 at one second intervals respectively. The comparative contacts will turn off when the timer is reset. DirectSOFT 5
Timing Diagram
X1 TMRA
0
T20 K45
1
2
3
0
10
10
Seconds 4
5
6
7
20
30
40
50
8
X1
C10 C10
TA20
Y3
Y3
K10
OUT Y4 TA20
Y4
K20
Y5
OUT T20 TA20
Y5
K30
Current Value
OUT
??????????
Handheld Programmer Keystrokes
Handheld Programmer Keystrokes (cont)
$
GX OUT
B STR
1
$
SHFT
STR N TMR $ STR GX OUT $ STR
SHFT
ENT C
B 2
A
A 1
C 0
SHFT D 3 SHFT
0 A
2 T MLR
C
ENT
SHFT
STR
0
2
4
$ E
A
E
F 5
4 B
0
A 1
0
ENT ENT
D
A 3
GX OUT
0
ENT T MLR
C
A 2
0
ENT F 5
ENT
ENT T MLR
C
A 2
C 0
A 2
0
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–43
Page 198
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Using Counters
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–44
Counters are used to count events . The counters available are up counters, up/down counters, and stage counters (used with RLLPLUS programming). The up counter (CNT) has two inputs, a count input and a reset input. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, counter reset, associated discrete bit, current value, and counter preset. The CNT counter preset and current value are bothe single word BCD values. X1 X1
CNT
CT1 K3
Up X2
X2
Reset CT1 Current alue
1
2
3
4
0
Counter preset
Counts
The up down counter (UDC) has three inputs, a count up input, count down input and reset input. The maximum count value is 99999999. The timing diagram below shows the relationship between the counter up and down inputs, counter reset, associated discrete bit, current value, and counter preset. The UDC counter preset and current value are bothe double word BCD values. NOTE: The UDC uses two consecutive V-memory locations for the 8-digit value, therefore two consecutive timer locations. For example, if UDC CT1 is used, the next available counter number is CT3. X1
UDC
X1 X2
X2
Down
X3
X3
CT2 Current Value
CT2 K3
Up
Reset 1
2
1 Counts
2
3
0
Counter Preset
The stage counter (SGCNT) has a count input and is reset by the RST instruction. This instruction is useful when programming using the RLLPLUS structured programming. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, associated discrete bit, current value, counter preset and reset instruction. X1
X1
SGCNT
CT2 K3
CT2 Current Value
1
2
3
4
0
Counts
RST CT2
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Counter preset
Page 199
Chapter 5: Standard RLL Instructions - Timer, Counter and Shift Register Instructions
Counter (CNT) DS5
Used
HPP
Used
The Counter is a two input counter that increments when the count input logic transitions from off to on. When the counter reset input is on the counter resets to 0. When the current value equals the preset value, the counter status bit comes on and the counter continues Counter# to count up to a maximum count of 9999. The maximum value will be held until the counter is reset. Count CNT CT aaa Instruction Specifications B bbb Counter Reference (CTaaa): Specifies the counter Reset number. Preset Value (Bbbb): Constant value (K) or a V-memory location. Preset Current Values: Counter current values are accessed by referencing the associated V or CT memory locations*. The V-memory location is the counter location + 1000. For example, the counter current value for CT3 resides in V-memory location V1003. Discrete Status Bit: The discrete status bit is accessed by referencing the associated CT memory location. It will be on if the value is equal to or greater than the preset value. For example the discrete status bit for counter 2 would be CT2. NOTE: A V-memory preset is required if the ladder program or OIP must change the preset.
Operand Data Type
DL06 Range
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CT aaa bbb
0–177
V-memory (preset only) . . . . . . . . . . . . . . . . . . V
––
–– 400-677 1200–7377 7400–7577 10000-17777
Pointers (preset only) . . . . . . . . . . . . . . . . . . . . P
1 2 3 4 5 6 7 8 9 10 11
400-677 1200–7377 –– 7400–7577* 10000-17777 –– 0–9999 0–177 or V41140–41147 1000-1177
14 A NOTE: * B ** With the HPP, both the Counter discrete status bits and current value are accessed with the same data reference. DirectSOFT 5 uses separate references, such as “CT2” for discrete status bit for Counter CT2, and C “CTA2” for the current value of Counter CT2. D Constants (preset only) . . . . . . . . . . . . . . . . . . K Counter discrete status bits . . . . . . . . . . . . CT/V Counter current values . . . . . . . . . . . . . . V /CT**
May be non-volatile if MOV instruction is used.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–45