Page 230
Chapter 5: Standard RLL Instructions - Logical
Or with Stack (ORS)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The ORS instruction is a 32 bit instruction that logically ORs the value in the accumulator with the first level of the accumulator stack. The result resides in the accumulator. The value in the first level of the accumulator stack is removed from the stack and all values are moved up one level. Discrete status flags indicate if the result of the ORS is zero or a negative number (the most significant bit is on). Discrete Bit Flags
OR S
Description
SP63 SP70
ON if the result in the accumulator is zero. ON if the result in the accumulator is negative.
In the following example when X1 is on, the binary value in the accumulator will be ORed with the binary value in the first level of the stack. The result resides in the accumulator.
DirectSOFT 5 DirectSOFT32 X1
V1401
LDD
5
V1400
4
7
E
2
V1400 8 7
A
Load the value in V1400 and V1401 in the accumulator 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8 7
6 5
4 3
2
1
0
Acc.
0
1
0 1
0
1
0
0 0
1
1
1
1 1
1
0
0
0
1 0
1
0
0
0 0
1
1
1
1 0
1
0
Acc.
0
1
0 1
0
1
0
0 0
1
1
1
1 1
1
0
0
0
1 0
1
0
0
0 0
1
1
1
1 0
1
0
36476A38 OR (top of stack)
0
0
1
0 1
1
0
1 0
0
0
1 1
0
1
1
1 0
1
0
0 1
1
1
0 0
0
1 0
1 0 0 1
0
1 0
0 0
1 0
1 0
1 0 0 1
1 0
0
1
1 0
1
1
0 0
1
1
1 0
6
F
A
A
ORS
OR the value in the accumulator with the value in the first level of the accumulator stack
Acc.
1
1
0
1 0
1
1 0
0
0
0
OUTD V1500 Copy the value in the accumulator to V1500 and V1501
7
7
V1501
Handheld Programmer Keystrokes $
B STR
1
ENT D
SHFT
L ANDST
D 3
3
Q
SHFT
S RST
ENT
SHFT
D
OR GX OUT
5–76
B
B 3
E 1
F 1
A 4
A 5
A 0
A 0
0
0
ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
6
7
V1500
1
0
1
0
Page 231
Chapter 5: Standard RLL Instructions - Logical
Exclusive Or (XOR) DS5
Used
HPP
Used
The XOR instruction is a 16 bit instruction that performs an exclusive OR of the value in the lower 16 bits of the accumulator and a specified V-memory location (Aaaa). The result resides in the in the accumulator. The discrete status flag indicates if the result of the XOR is zero. Operand Data Type
XOR A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P
See memory map See memory map
Discrete Bit Flags
Description
SP63 SP70
ON if the result in the accumulator is zero. ON if the result in the accumulator is negative.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the LD instruction. The value in the accumulator is exclusive ORed with V2006 using the XOR instruction. The value in the lower 16 bits of the accumulator are output to V2010 using the OUT instruction. DirectSOFT 5 Direct SOFT32 X1
V2000
LD
2
V2000 Load the value in V2000 into the lower 16 bits of the accumulator
8
7
A
The upper 16 bits of the accumulator will be set to 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Acc. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 1 0 0 1
0 0 0 1 1 1 1 0 1 0
XOR V2006 XOR the value in the accumulator with the value in V2006
Acc.
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 1 0 1 0 0 0 0 1 1 1 1 0 1 0
6A38 XOR (V2006)
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 1 1 0 1 0 1 0 0 0 1 1 1 0 0 0
Acc. 0 0 0 0 0 10 0 0 0 0 0 0 0 0 0 0
0 1 0 0 0 0 1 0 0 1 0 0 0 0 1 0
OUT V2010 4
Copy the lower 16 bits of the accumulator to V2010
2
4
2
V2010
Handheld Programmer Keystrokes $
SHFT
STR SHFT
D L ANDST 3
SHFT
X
GX OUT
SET
X
B SET
1 SHFT
SHFT
Q
SHFT
V AND
OR C 2
ENT V AND
C
SHFT
V AND
C
A
B
A
0
A 2
1
A 0
A 0
A 2 0
0 A
0
ENT G
0
6
ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–77
Page 232
Chapter 5: Standard RLL Instructions - Logical
Exclusive Or Double (XORD)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The XORD is a 32 bit instruction that performs an exclusive OR of the value in the accumulator and the value (Aaaa), which is either two consecutive V-memory locations or an 8 digit (max.) constant. The result resides in the accumulator. Discrete status flags indicate if the result of the XORD is zero or a negative number (the most significant bit is on).
XORD K aaa
Operand Data Type
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
See memory map See memory map 0–FFFFFFFF
Discrete Bit Flags
Description
SP63 SP70
ON if the result in the accumulator is zero. ON if the result in the accumulator is negative
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the LDD instruction. The value in the accumulator is exclusively ORed with 36476A38 using the XORD instruction. The value in the accumulator is output to V2010 and V2011 using the OUTD instruction. DirectSOFT 5
Direct SOFT32 X1
V2001 5
LDD
4
7
V2000 E
2
8
7
A
V2000 Load the value in V2000 and V2001 into the accumulator
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6 5
4 3
2
1
0
Acc.
0
1
0
1
0
1
0
0
0
1
1
1
1
1
1
0
0
0
1
0
1
0
0
0
0
1
1
1
1
0
1
0
Acc.
0
1
0
1
0
1
0
0
0
1
1
1
1
1
1
0
0
0
1
0
1
0
0
0
0
1
1
1
1
0
1
0
XORD 36476A38
0
0
1
1
0
1
1
0
0
1
0
0
0
1
1
1
0
1
1
0
1
0
1
0
0
0
1
1
1
0
0
0
Acc.
0
1 0
1 0
0
0
0 1
1 0
0
0
0
1 0
1 0
1 0
0
0
1 0
0
1
0
0
0
0
1
0
0
1
0
0
0
0
1
0
2
3
9
4
2
4
2
XORD K36476A38 XORD the value in the accumulator with the constant value 36476A38 OUTD V2010 Copy the value in the accumulator to V2010 and V2011
6
V2011
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
X
Q
D
G
OR E
6
GX OUT
SHFT
5–78
D 3
SET
3
ENT
4 D
C 3
SHFT
D
H
G 7
6 2
A
A
0
0
SHFT
K JMP
SHFT
A
SHFT
D
A
B
A
ENT
3
C 3
A 2
0
0 1
0
ENT
0
I 3
8
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
V2010
Page 233
Chapter 5: Standard RLL Instructions - Logical
Exclusive Or Formatted (XORF) Used
HPP
Used
The XORF instruction performs an exclusive OR of the XO R F A aaa binary value in the accumulator and a specified range of K bbb discrete memory bits (1–32). The instruction requires a starting location (Aaaa) and the number of bits (Bbbb) to be exclusive ORed. Discrete status flags indicate if the result of the XORF is zero or negative (the most significant bit =1). Operand Data Type
DL06 Range aaa bbb
0-777 0-777 0-1777 0-1777 0-377 177 0-777 -
1-32
A/B Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter Bits . . . . . . . . . . . . . . . . . . . . . . . . . . CT Special Relays . . . . . . . . . . . . . . . . . . . . . . . . . SP Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
Discrete Bit Flags SP63 SP70
Description ON if the result in the accumulator is zero. ON if the result in the accumulator is negative
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the binary pattern of C10–C13 (4 bits) will be loaded into the accumulator using the LDF instruction. The value in the accumulator will be logically exclusive ORed with the bit pattern from Y20–Y23 using the XORF instruction. The value in the lower 4 bits of the accumulator are output to C20–C23 using the OUTF instruction. DirectSOFT 5 DirectSOFT32 X1
LDF
C10
Location
Constant
C13 C12 C11 C10
C10
K4
OFF ON
ON OFF
K4 Load the status of 4 consecutive bits (C10-C13) into the accumulator X0RF
The unused accumulator bits are set to zero
Y20 K4
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7 6 5
4 3
2
1
0
0
0
0 0
0
0
1 1
0
0
0
0 0
0
0
0
0
0 0
0 0
0
0
0
0
0
0 0
0 0
0
0
0
0
0
0
Acc.
0
0
0 0
0
0
0 0
0
0
0
0 0
0
0
0
0 0
1
1
0
1
0
0
0
0 0
0
0
0
0 0
0
0
0
0 1
1
1
0
Accumulator
Exclusive OR the binary bit pattern (Y20-Y23) with the value in the accumulator
Acc.
0
0 0
0
0
0
0
Y23 Y22 Y21 Y20 XORF (Y20-Y23) ON OFF OFF OFF
OUTF
0
C20 K4
Copy the specified number of bits from the accumulator to C20-C23
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
X SET
Q
SHFT
F
GX OUT
OR 5
Constant K4
C23 C22 C21 C20 ON ON ON OFF
ENT F
3
Location C20
NEXT
5 SHFT
F 5 PREV
PREV
NEXT
NEXT
NEXT
NEXT
C
A
C
A 2
2
B
A 1
0
4 E
0
E 0
E
4
4
ENT
Standard RLL
DS5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–79
Page 234
Chapter 5: Standard RLL Instructions - Logical
Exclusive Or with Stack (XORS)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The XORS instruction is a 32 bit instruction that performs an exclusive or of the value in the accumulator with the first level of the accumulator stack. The result resides in the accumulator. The value in the first level of the accumulator stack is removed from the stack and all values are moved up one level. Discrete status flags indicate if the result of the XORS is zero or a negative number (the most significant bit is on).
XO R S
NOTE: Status flags are valid only until another instruction uses the same flag.
Discrete Bit Flags
Description
SP63 SP70
ON if the result in the accumulator is zero. ON if the result in the accumulator is negative
In the following example, when X1 is on, the value in V1400 and V1401 will be loaded into the accumulator using the LDD instruction. The binary value in the accumulator will be exclusively ORed with 36476A38 using the XORS instruction. The value in the accumulator is output to V1500 and V1501 using the OUTD instruction. DirectSOFT 5 DirectSOFT32 V1401
LDD
X1
5
V1400
4
7
V1400 E
2
8
7
A
Load the value in V1400 and V1401 into the accumulator 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8 7
6 5
4 3
2
1
0
Acc.
0
1
0 1
0
1
0
0 0
1
1
1
1 1
1
0
0
0
1 0
1
0
0
0 0
1
1
1
1 0
1
0
Acc.
XORS
Exclusive OR the value in the accumulator with the value in the first level of the accumulator stack
0
1
0 1
0
1
0
0 0
1
1
1
1 1
1
0
0
0
1 0
1
0
0
0 0
1
1
1
1 0
1
0
36476A38 XOR (1st level of Stack) 0
0
1 1
0
1
1
0 0
1
0
0
0 1
1
1
0
1
1 0
1
0
1
0 0
0
1
1
1 0
0
0
0
1 0
1 0 0
0
0 1
1 0
0 0
0
1 0
1 0
1 0 0
0
1 0
0
1
0 0
0
0
1
0 0
1
0
0
0 0
1
0
2
9
2
2
Acc.
OUTD V1500 6
Copy the value in the accumulator to V1500 and V1501
3
V1501
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
X SET
Q
GX OUT
SHFT
D
5–80
ENT D
3 OR 3
B 3
SHFT
E 1
S RST
ENT
B
F 1
A 4
A 5
A 0
A 0
0
0
ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
4
4
V1500
Page 235
Chapter 5: Standard RLL Instructions - Logical
Compare (CMP) DS5
Used
HPP
Used
The CMP instruction is a 16 bit instruction that compares the value in the lower 16 bits of the accumulator with the value in a specified V-memory location (Aaaa). The corresponding status flag will be turned on indicating the result of the comparison. The data format for this instruction is BCD/Hex, Decimal and Binary. Operand Data Type
CMP A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P
See memory map See memory map
Discrete Bit Flags
Description
SP60 SP61 SP62
On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example when X1 is on, the constant 4526 will be loaded into the lower 16 bits of the accumulator using the LD instruction. The value in the accumulator is compared with the value in V2000 using the CMP instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value specified in the CMP instruction, SP60 will turn on Direct SOFT 5 X1
CONSTANT
LD
4
K4526 Load the constant value 4526 into the lower 16 bits of the accumulator
5
? 2
6
The unused accumulator bits are set to zero Acc.
0
0
0
0
44 55 2? 2 66 ?
Compared with
CMP V2000
8
Compare the value in the accumulator with the value in V2000 SP60
9
4
5
V2000
C30
OUT Handheld Programmer Keystrokes $
B 1
STR
ENT
SHFT
L ANDST
D
SHFT
C
SHFT
M ORST
P
SHFT
SP STRN
G
SHFT
C
D
$ STR GX OUT
2
SHFT
3
2
K JMP
E
F 4
C CV A 0 A 3
A 2
6
0
C 5
G 2
A 0
6 A
0
0
ENT ENT
ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–81
Page 236
Chapter 5: Standard RLL Instructions - Logical
Compare Double (CMPD)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
The Compare Double instruction is a 32–bit instruction that CMPD compares the value in the accumulator with the value (Aaaa), A aaa which is either two consecutive V-memory locations or an 8–digit (max.) constant. The corresponding status flag will be turned on indicating the result of the comparison. The data format for this instruction is BCD/Hex, Decimal and Binary. Operand Data Type aaa See memory map See memory map 0–FFFFFFFF
Discrete Bit Flags SP60 SP61 SP62
Description On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in the accumulator is compared with the value in V2010 and V2011 using the CMPD instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value specified in the Compare instruction, SP60 will turn on energizing C30. Direct SOFT 5 X1
V2000
V2001
LDD
4
5
2
6
7
2
9
9
Acc. 4
5
2
6
7
2
9
9
0
2
6
V2000 Load the value in V2000 and V2001 into the accumulator
Compared with
CMPD V2010 6
Compare the value in the accumulator with the value in V2010 and V2011 SP60
7
3
9
5
V2011
V2010
C30
OUT
Handheld Programmer Keystrokes $
B 1
STR
ENT
SHFT
L ANDST
D 3
3
SHFT
C
SHFT
M ORST
P
SHFT
SP STRN
G
SHFT
C
D
$ STR GX OUT
5–82
DL06 Range
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
2
D
C
2
A 2
A 0
D CV
C
A 0 A 3
0
0 A
2
3
6
A 0
ENT ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
ENT B
0
A 1
0
ENT
Page 237
Chapter 5: Standard RLL Instructions - Logical
Compare Formatted (CMPF) DS5
Used
HPP
Used
The Compare Formatted compares the value in the C MP F A aaa accumulator with a specified number of discrete locations K bbb (1–32). The instruction requires a starting location (Aaaa) and the number of bits (Kbbb) to be compared. The corresponding status flag will be turned on indicating the result of the comparison. The data format for this instruction is BCD/Hex, Decimal and Binary.
1 2 3 Operand Data Type DL06 Range 4 5 6 7 8 Discrete Bit Flags Description 9 10 NOTE: Status flags are valid only until another instruction uses the same flag. In the following example, when X1 is on the Load Formatted instruction loads the binary 11 value (6) from C10–C13 into the accumulator. The CMPF instruction compares the value in the accumulator to the value in Y20–Y23 (E hex). The corresponding discrete status flag will 12 be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value specified in the Compare instruction, SP60 will turn on 13 energizing C30. 14 A B C D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter Bits . . . . . . . . . . . . . . . . . . . . . . . . . . CT Special Relays . . . . . . . . . . . . . . . . . . . . . . . . . SP Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
SP60 SP61 SP62 aaa 0-777 0-777 0-1777 0-1777 0-377 0-177 0-777 - bbb 1-32
On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.
DirectSOFT 5 DirectSOFT32 X1
C10
LDF
K4
CMPF
Y20
K4
SP60
Load the value of the specified discrete locations (C10- C13) into the accumulator Compare the value in the accumulator with the value of the specified discrete location (Y20- Y23)
Constant K4
C13 C12 C11 C10
OFF ON ON OFF
The unused accumulator bits are set to zero
Acc.
C30
OUT
Location
C10
Y23 Y22 Y21 Y20
0
0
0
0
0
0
0
6
Compared with
ON ON ON OFF
E
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–83
Page 238
Chapter 5: Standard RLL Instructions - Logical
Compare with Stack (CMPS)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–84
The Compare with Stack instruction is a 32-bit instruction that C MP S compares the value in the accumulator with the value in the first level of the accumulator stack. The data format for this instruction is BCD/Hex, Decimal and Binary. The corresponding status flag will be turned on indicating the result of the comparison. This does not affect the value in the accumulator. Discrete Bit Flags
Description
SP60 SP61 SP62
On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example when X1 is on, the value in V1400 and V1401 is loaded into the accumulator using the Load Double instruction. The value in V1410 and V1411 is loaded into the accumulator using the Load Double instruction. The value that was loaded into the accumulator from V1400 and V1401 is placed on top of the stack when the second Load instruction is executed. The value in the accumulator is compared with the value in the first level or the accumulator stack using the CMPS instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value in the stack, SP60 will turn on, energizing C30. DirectSOFT 5 DirectSOFT32
V1400
V1401
X1
Load the value in V1400 and V1401 into the accumulator
LDD
6
5
0
0
3
5
4
4
6
5
0
0
3
5
4
4
5
V1411 5 0 0
3
V1410 5 4 4
5
3
5
V1400 Load the value in V1410 and V1411 into the accumulator
LDD
Acc.
V1410 Compare the value in the accumulator with the value in the first level of the accumulator stack
CMPS
SP60
C30 OUT
Acc. 5
B STR
1
ENT
SHFT
L ANDST
D
SHFT
L ANDST
D 3
3
SHFT
C
SHFT
M ORST
P
$
PREV
G
A
ENT
STR GX OUT
2
D 3
B 3
E 1
B
D
6
0
NEXT
NEXT
0
4
4
Compared with Top of Stack
Handheld Programmer Keystrokes $
0
CV
NEXT
A 4
E
A 0
B
1
4
S RST
ENT
SHFT
C
A 1
D 2
0 0
A 3
0
ENT ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 239
Chapter 5: Standard RLL Instructions - Logical
Compare Real Number (CMPR) DS5
Used
HPP
Used
The Compare Real Number instruction compares a real number value in the accumulator with two consecutive V-memory locations containing a real number. The corresponding status flag will be turned on indicating the result of the comparison. Both numbers being compared are 32 bits long. Operand Data Type ....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R
Discrete Bit Flags SP60 SP61 SP62 SP71
CMPR A aaa
DL06 Range aaa See memory map See memory map -3.402823E+ 038 to + -3.402823E+ 038
Description On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value. On anytime the V-memory specified by a pointer (P) is not valid
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example when X1 is on, the LDR instruction loads the real number representation for 7 decimal into the accumulator. The CMPR instruction compares the accumulator contents with the real representation for decimal 6. Since 7 > 6, the corresponding discrete status flag is turned on (special relay SP62) turning on control relay C1. DirectSOFT DirectSOFT32 5 X1
LDR R7.0
CMPR R6.0
SP62
Load the real number representation for decimal 7 into the accumulator
Acc.
4
0
E
0
0
0
0
0
Compare the value with the real number representation for decimal 6
CMPR
4
0
D
0
0
0
0
0
C1 OUT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–85