For the AutomationDirect Direct Logic DL06 and Koyo DL06 D0-06DD1
Page 240
Chapter 5: Standard RLL Instructions - Math
Math Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Add (ADD) DS5
Used
HPP
Used
Operand Data Type
A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P
See memory map See memory map
Discrete Bit Flags
Description
SP63 SP66 SP67 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On when the 16 bit addition instruction results in a carry. On when the 32 bit addition instruction results in a carry. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in the lower 16 bits of the accumulator are added to the value in V2006 using the Add instruction. The value in the accumulator is copied to V2010 using the Out instruction. DirectSOFT Direct SOFT32 5
V2000
X1
4
9
3
5
The unused accumulator bits are set to zero 0 0 0 0 4
9
3
5
(Accumulator)
2
5
0
0
(V2006)
7
4
3
5
7
4
3
5
LD V2000 Load the value in V2000 into the lower 16 bits of the accumulator ADD
+
V2006
Acc.
Add the value in the lower 16 bits of the accumulator with the value in V2006 OUT V2010 Copy the value in the lower 16 bits of the accumulator to V2010 Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
A
D
GX OUT
5–86
ADD
Add is a 16 bit instruction that adds a BCD value in the accumulator with a BCD value in a V-memory location (Aaaa). (You cannot use a constant as the parameter in the box.) The result resides in the accumulator.
0
V2010
ENT A
C 2
3
A 0
C
D 3
3
SHFT
V AND
A 2
C
A 2
A 0 A 0
B 0
0
G 0
A 1
ENT
0
DL06 Micro PLC User Manual, 3rd Edition Rev. A
6 ENT
ENT
Page 241
Chapter 5: Standard RLL Instructions - Math
Add Double (ADDD) DS5
Used
HPP
Used
Add Double is a 32 bit instruction that adds the BCD value in the accumulator with a BCD value (Aaaa), which is either two consecutive V-memory locations or an 8–digit (max.) BCD constant. The result resides in the accumulator.
ADDD A aaa
Operand Data Type
DL06Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
See memory map See memory map 0–99999999
Discrete Bit Flags
Description
SP63 SP66 SP67 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On when the 16 bit addition instruction results in a carry. On when the 32 bit addition instruction results in a carry. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in the accumulator is added with the value in V2006 and V2007 using the Add Double instruction. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. DirectSOFT 5 Direct SOFT
V2000
V2001
X1
6
LDD
7
3
9
5
0
2
6
V2000 Load the value in V2000 and V2001 into the accumulator ADDD V2006 Add the value in the accumulator with the value in V2006 and V2007
6
7
3
9
5
0
2
6
(Accumulator)
+ 2
0
0
0
4
0
4
6
(V2006 and V2007)
Acc. 8
7
3
9
9
0
7
2
8
7
3
9
9
0
7
2
OUTD V2010
V2001
Copy the value in the accumulator to V2010 and V2011
V2010
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
A
D
GX OUT
SHFT
ENT D
3
0
C
D 3
D 3
A 2
3
C
D 3
A 0
3 SHFT
A
C
A
A 2
0
0
2 V AND
A 0
G 6
0 B
0
ENT
A 1
0
ENT ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–87
Page 242
Chapter 5: Standard RLL Instructions - Math
Add Real (ADDR)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–88
The Add Real instruction is a 32-bit instruction that adds a real number, which is either two consecutive V memory locations or a 32-bit constant, to a real number in the accumulator. Both numbers must conform to the IEEE floating point format. The result is a 32bit real number that resides in the accumulator. Operand Data Type
ADDR A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R
See memory map See memory map -3.402823E+ 38 to + -3.402823E+ 38
Discrete Bit Flags
Description
SP63 SP70 SP71 SP72 SP73 SP74
On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in a incorrect sign bit. On anytime a floating point math operation results in an underflow error.
NOTE: Status flags are valid only until another instruction uses the same flag. DirectSOFT 5 X1
LDR R7.0 Load the real number 7.0 into the accumulator
ADDR R15.0 Add the real number 15.0 to the accumulator contents, which is in real number format.
OUTD V1400 Copy the result in the accumulator to V1400 and V1401.
NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT 5 for this feature.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 243
Chapter 5: Standard RLL Instructions - Math
Subtract (SUB) DS5
Used
HPP
Used
SUB
Subtract is a 16 bit instruction that subtracts the BCD value (Aaaa) in a V-memory location from the BCD value in the lower 16 bits of the accumulator. The result resides in the accumulator. Operand Data Type
A aaa
DL06Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P
See memory map See memory map
Discrete Bit Flags
Description
SP63 SP64 SP65 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On when the 16 bit subtraction instruction results in a borrow On when the 32 bit subtraction instruction results in a borrow On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in V2006 is subtracted from the value in the accumulator using the Subtract instruction. The value in the accumulator is copied to V2010 using the Out instruction.
DirectSOFT Direct SOFT325
V2000
X1
2
4
7
5
The unused accumulator bits are set to zero 0 0
0
0
2
4
7
5
1
5
9
2
0
8
8
3
0
8
8
3
LD V2000 Load the value in V2000 into the lower 16 bits of the accumulator
_
SUB V2006
Acc. Subtract the value in V2006 from the value in the lower 16 bits of the accumulator OUT V2010
V2010 Copy the value in the lower 16 bits of the accumulator to V2010 Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
S RST
U
GX OUT
ENT C
3
A 2
B ISG
1
SHFT
V AND
C 2
A
A
0
0
SHFT
V AND
C
A
B
A
0
1
0
ENT A
2 0
A 0
G 0
6
ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–89
Page 244
Chapter 5: Standard RLL Instructions - Math
Subtract Double (SUBD)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–90
Subtract Double is a 32 bit instruction that subtracts the BCD value (Aaaa), which is either two consecutive V-memory locations or an 8digit (max.) constant, from the BCD value in the accumulator. Operand Data Type
SUBD A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
See memory map See memory map 0–99999999
Discrete Bit Flags
Description
SP63 SP64 SP65 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On when the 16 bit subtraction instruction results in a borrow On when the 32 bit subtraction instruction results in a borrow On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in V2006 and V2007 is subtracted from the value in the accumulator. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. DirectSOFT Direct SOFT32 5
V2001 0
X1
1
V2000
0
6
3
2
7
4
LDD V2000 Load the value in V2000 and V2001 into the accumulator
0 1 _
SUBD V2006
ACC.
0
6
3
2
7
4
6
7
2
3
7
5
0
0
3
9
0
8
9
9
0
0
3
9
0
8
9
9
The in V2006 and V2007 is subtracted from the value in the accumulator OUTD V2010
V2011
V2010
Copy the value in the accumulator to V2010 and V2011 Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
S RST
SHFT
GX OUT
SHFT
D
ENT C
D 3 U
B ISG
A 0
D 1
C 3
A 2
3
C 3
A 2
A 0 A 2
B 0
A 1
0
0
ENT A
0 ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
G 0
6
ENT
Page 245
Chapter 5: Standard RLL Instructions - Math
Subtract Real (SUBR) DS5
Used
HPP
N/A
The Subtract Real instruction is a 32-bit instruction that subtracts a real number, which is either two consecutive V memory locations or a 32-bit constant, from a real number in the accumulator. Both numbers must conform to the IEEE floating point format. The result is a 32-bit real number that resides in the accumulator
1 2 3 Operand Data Type DL06 Range aaa 4 5 Discrete Bit Flags Description 6 7 8 9 10 11 12 13 14 A B C NOTE: Status flags are valid only until another instruction uses the same flag. NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE D ....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R
SP63 SP70 SP71 SP72 SP73 SP74
S UBR A aaa
See memory map See memory map -3.402823E + 38 to+-3.402823E + 38
On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in a incorrect sign bit. On anytime a floating point math operation results in an underflow error.
DirectSOFT 5 DirectSOFT32 LDR
4
1
B
0
0
0
0
0
R22.0
Load the real number 22.0 into the accumulator.
-
2
2
4
1
B
0
0
0
0
0
(Accumulator)
1
5
+ 4
1
7
0
0
0
0
0
(SUBR)
7
Acc. 4
0
E
0
0
0
0
0
0
0
(decimal)
SUBR
R15.0
V1401
Subtract the real number 15.0 from the accululator contents, which is in real number format.
4
0
E
V1400 0
0
0
(Hex number)
Real Value
OUTD
Acc.
8 4
2
1
8
4 2
1
8
4
2 1
8
4
2
1
8 4
2
1
8
4 2
1
8
4
2 1
8
4
2
1
0 1
0
0
0
0 0
0
1
1
1 0
0
0
0
0
0 0
0
0
0
0 0
0
0
0
0 0
0
0
0
0
V1400
Copy the result in the accumulator to V1400 and V1401.
Sign Bit
Exponent (8 bits)
128 + 1 = 129 129 - 127 = 2 Implies 2 (exp 2)
Mantissa (23 bits)
1.11 x 2 (exp 2) = 111. binary= 7 decimal ndard RLL s tructions
X1 format. You must use DirectSOFT 5 for this feature
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–91
Page 246
Chapter 5: Standard RLL Instructions- - Math
Multiply (MUL)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–92
Multiply is a 16 bit instruction that multiplies the BCD value (Aaaa), which is either a V-memory location or a 4–digit (max.) constant, by the BCD value in the lower 16 bits of the accumulator The result can be up to 8 digits and resides in the accumulator.
MUL A aaa
Operand Data Type
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
See memory map See memory map 0–9999
Discrete Bit Flags
Description
SP63 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in V2006 is multiplied by the value in the accumulator. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. V2000
Direct SOFT32 5 DirectSOFT X1
1 0
LD
0 0
V2000 The unused accumulator bits are set to zero
Load the value in V2000 into the lower 16 bits of the accumulator
0
0
0
0
1 0 0 0
X
MUL
Acc.
V2006
0
0
0
0
2
5
0
2
5
0
0
0
0
2
5
0
0
0
The value in V2006 is multiplied by the value in the accumulator
OUTD
V2011
V2010
V2010
Copy the value in the accumulator to V2010 and V2011
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
M ORST
U ISG
GX OUT
SHFT
D
ENT C
3
A 2 C
L ANDST
A
A 2
A 0
2 C
3
A 0
A 0
B 0
0
G 0
A 1
ENT
0
DL06 Micro PLC User Manual, 3rd Edition Rev. A
6 ENT
ENT
(Accumulator) (V2006)
Page 247
Chapter 5: Standard RLL Instructions - Math
Multiply Double (MULD) DS5
Used
HPP
Used
Multiply Double is a 32 bit instruction that multiplies the 8-digit BCD value in the accumulator by the 8-digit BCD value in the two consecutive V-memory locations specified in the instruction. The lower 8 digits of the results reside in the accumulator. Upper digits of the result reside in the accumulator stack. Operand Data Type
MULD A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P
See memory map See memory map
Discrete Bit Flags
Description
SP63 SP70 SP75
On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the constant Kbc614e hex will be loaded into the accumulator. When converted to BCD the number is ”12345678”. That numbers stored in V1400 and V1401. After loading the constant K2 into the accumulator, we multiply it times 12345678, which is 24691356. DirectSOFT 5 Direct SOFT32 Display X1
1
2
3
4
5
6
7
8
(Accumulator)
Load the hex equivalent of 12345678 decimal into the accumulator.
LDD Kbc614e
V1401
Convert the value to BCD format. It will occupy eight BCD digits (32 bits).
BCD
1
Output the number to V1400 and V1401 using the OUTD instruction.
OUTD V1400
V1400
2
3
4
5
6
7
8
2
4
6
9
1
3
5
6
2
4
6
9
1
3
5
6
X Acc.
2
(Accumulator)
Load the constant K2 into the accumulator.
LD K2
V1400
Multiply the accumulator contents (2) by the 8-digit number in V1400 and V1401.
V1402
Move the result in the accumulator to V1402 and V1403 using the OUTD instruction.
MULD
OUTD
V1403
V1402
Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
B
C
ENT D
3
1
D 2
GX OUT
SHFT
D
SHFT
L ANDST
D
SHFT
M ORST
U
GX OUT
SHFT
D
3 3
3
B
E
A
A
1 PREV
3 L ANDST
4 C 2
D
C 1
0
2
B
SHFT
G
A
ENT
6
E 1
4
SHFT
E 4
ENT
B
E 1
E 1
0
A 4
ENT
ENT
3 B
3
SHFT
ENT B
ISG
PREV
A 4
C 0
2
0
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–93
Page 248
Chapter 5: Standard RLL Instructions - Math
Multiply Real (MULR)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
Used
5–94
The Multiply Real instruction multiplies a real number in the accumulator with either a real constant or a real number occupying two consecutive V-memory locations. The result resides in the accumulator. Both numbers must be Real data type (IEEE floating point format). Operand Data Type
MULR A aaa
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Real Constant . . . . . . . . . . . . . . . . . . . . . . . . . . R
See memory map See memory map -3.402823E +38 to + -3.402823E +38
Discrete Bit Flags
Description
SP63 SP70 SP71 SP72 SP73 SP74
On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in a incorrect sign bit. On anytime a floating point math operation results in an underflow error.
NOTE: Status flags are valid only until another instruction uses the same flag. DirectSOFT 5 DirectSOFT32 Display X1
LDR
4
0
E
0
0
0
0
0
R 7.0 Load the real number 7.0 into the accumulator. 4
0
E
0
0
0
0
0
(Accumulator)
x
1
5
X 4
1
7
0
0
0
0
0
(MULR)
1
0
5
Acc. 4
2
D
2
0
0
0
0
2
0
7
(decimal)
MULR R 15.0
V1401
Multiply the accumulator contents by the real number 15.0
4
2
D
V1400 0
0
0
(Hex number)
Real Value
OUTD
Acc.
8 4
2
1
8
4 2
1
8
4
2 1
8
4
2
1
8 4
2
1
8
4 2
1
8
4
2 1
8
4
2
1
0 1
0
0
0
0 1
0
1
1
0 1
0
0
1
0
0 0
0
0
0
0 0
0
0
0
0 0
0
0
0
0
V1400 Copy the result in the accumulator to V1400 and V1401.
Exponent (8 bits)
Sign Bit 128 + 4 + 1 = 133 133 - 127 = 6 Implies 2 (exp 6)
Mantissa (23 bits)
1.101001 x 2 (exp 6) = 1101001. binary= 105 decimal
NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT 5 for this feature.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 249
Chapter 5: Standard RLL Instructions - Math
Divide (DIV) DS5
Used
HPP
Used
Divide is a 16 bit instruction that divides the BCD value in the accumulator by a BCD value (Aaaa), which is either a V-memory location or a 4-digit (max.) constant. The first part of the quotient resides in the accumulator and the remainder resides in the first stack location.
DIV A aaa
Operand Data Type
DL06 Range aaa
....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
See memory map See memory map 0–9999
Discrete Bit Flags
Description
SP53 SP63 SP70 SP75
On when the value of the operand is larger than the accumulator can work with. On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON–BCD number was encountered.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in the accumulator will be divided by the value in V2006 using the Divide instruction. The value in the accumulator is copied to V2010 using the Out instruction. Direct SOFT32 5 DirectSOFT
V2000
X1
5 0
0
0
0
0
0
(Accumulater)
4
9
V2006
0
2
0
LD V2000 Load the value in V2000 into the lower 16 bits of the accumulator
The unused accumulator bits are set to zero 0 0 0 0 5
DIV
÷ V2006 1
Acc.
The value in the accumulator is divided by the value in V2006
0
0
0
0
0
0
2
First stak location contains the remainder
1
OUT V2010
0
2
V2010
Copy the value in the lower 16 bits of the accumulator to V2010 Handheld Programmer Keystrokes $
B STR
1
SHFT
L ANDST
D
SHFT
D
I
GX OUT
3
ENT C
3 8 SHFT
A 2
V AND V AND
A 0
C
A 2
C
A 2
A 0 A 0
B 0
0
G 0
A 1
ENT
0
6
ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
5–95